F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

5

68-0198-2

latches (2)

3-speed switch module ( 3 Series only)

Make Opening (if Mounting in a Drop Ceiling)

1.

Size the opening to fit the air cleaner cabinet as closely 
as possible. 

2.

Frame the opening to provide adequate support for the 
cabinet. The cabinet must fit snugly in the opening; 
allow no more than 1/4 in. (6 mm) from the opening to 
each side of the cabinet.

3.

Cover the framing and any unused portion of the open-
ing with wallboard, plywood, or other material and finish 
to match the ceiling.

Electrical Hookup

All wiring must comply with applicable codes and ordinances. 
The power source must agree with the model type: 120V, 
60 Hz or 230V, 50 Hz.

1.

Locate the prepunched hole in the side of the cabinet.

2.

Remove the air cleaner lid.

3.

For Series 1 and 2 only.

Remove the connection box 

cover plate in the center cavity of the air cleaner.

4.

For Series 3 only. 

Remove the connection box cover 

plate on the bottom, underneath the tray. 

5.

Refer to Fig. 3 and 4 for typical electrical diagrams.

WARNING

Risk of Fire or Electric Shock.
Can cause personal injury or equipment damage.

Use only Honeywell 190097C Remote Speed Switch 
(3-speed models only) to regulate air cleaner speed. 
Using a different speed switch may void the warranty.

IMPORTANT

Be sure the air cleaner is grounded for correct
operation and safety.

Canadian installation: NEVER install in ceilings with 
thermal insulation value greater than R-40.

Fig. 3. Typical F111 (series 1 & 2) 120V, 60 Hz or 

208/230V, 50/60 Hz wiring diagram.

Fig. 4.  Typical F111 Series 3 only 120V, 60 Hz or 

230V, 50 Hz wiring diagram.

Mount Air Cleaner Cabinet

The air cleaner can be mounted in a drop ceiling system or 
hung in an open area. Both mounting methods require the air 
cleaner to be level and positioned facing downward for correct 
operation.

1.

Remove the door/grille from the carton and set it aside. 

2.

Remove all filters.

3.

Fit the cabinet into the prepared ceiling opening or 
position on the ceiling.

4.

Use the four 3/8 x 16T internal nuts (one at each corner) 
to fasten the cabinet to a structural support (bar joist, 
concrete slab or timber framing). See Fig. 5.

NOTES:

All external hardware is furnished by the installer.

When using the suspension system of mounting, 
be sure to include a means for leveling adjust-
ment after installation.

Never rest the air cleaner on the T-bar.

5.

Level the air cleaner.

6.

Turn the air cleaner power on and check for proper 
operation for 2 to 3 minutes. There should be a smooth, 
powerful blower sound and air discharging from both 
ends of the air cleaner.

7.

Turn off the power.

8.

Install the particle filter. Note airflow direction arrows if 
present. Install the filter with the direction arrow pointing 
towards the motor.

9.

For Series 1 and 2 only.

 Fasten the filter tabs. Be sure 

there is a snapping sound when fastened. The tabs are 
commercial Velcro and require more force than lightly 
pushing them together.

10.

For Series 3 only.

 Lock and secure the particle filter 

into place by closing both latches.

M12657

CAPACITOR

WHITE
GREEN

BLACK

FACTORY WIRING

BROWN

EXTERNAL
WIRING BY
INSTALLER

MOTOR

A100002

CAP

ACIT

OR 

WHITE 
GREEN 

BLACK

FACTORY WIRING

BROWN 

EXTERNAL 

WIRING BY 

INSTALLER 

MOTOR 

BLUE

VIOLET

RED

BLACK

REMOTE 3-SPEED

 SWITCH

Содержание F111 Series 1

Страница 1: ...ollen and some cooking smoke from the air circulated through the filter FEATURES High Efficiency Particulate Air HEPA filter models are 99 97 efficient and the hospital grade particle filter models are 95 efficient at 0 3 micron particles Both models are more efficient on particles smaller and larger There is also a 95 ASHRAE model Circulates up to 1250 cfm Designed to overcome the increase in air...

Страница 2: ...ect drive forward curve Dimensions See Fig 1 for dimensions Table 1 F111 Series 3 Description a For single speed and three speed systems set to High b F111C1061 has a new model number F111C1012B To Order F111 with a Black Grill Replace the W with a B to any model number in Table 1 Model Voltage Efficiency Gas V O C and Odor Control Modules 2 Air Volumea in cfm m3 hr Particulates at 0 3 Micron DOP ...

Страница 3: ...f any questions should arise concerning determining the number of air cleaners needed for an area consult your distributor or local Honeywell Commercial Air Cleaner Distributor Table 4 Determining the Minimum Number of Air Cleaners Needed for a Space Model Voltage Particulates at 0 3 Micron DOP Test Gas V O C and Odor Control Modules 2 Higha in cfm m3 hr Medium in cfm m3 hr Low in cfm m3 hr F111A1...

Страница 4: ...ed air up from the center of the area See Fig 2 When multiple air cleaners are installed the allotted areas to be cleaned should be equal The air throw in one direction is approximately 55 ft 17m Air velocity at 90 ft per minute 27m per minute is considered end of throw IMPORTANT Never hang the air cleaner higher than 16 ft 5m above the floor INSTALLATION WARNING Explosion Hazard Possible Can caus...

Страница 5: ...g diagram Fig 4 Typical F111 Series 3 only 120V 60 Hz or 230V 50 Hz wiring diagram Mount Air Cleaner Cabinet The air cleaner can be mounted in a drop ceiling system or hung in an open area Both mounting methods require the air cleaner to be level and positioned facing downward for correct operation 1 Remove the door grille from the carton and set it aside 2 Remove all filters 3 Fit the cabinet int...

Страница 6: ...te location 3 Attach 3 4 extension ring to outlet box 4 Run five conductor color coded 18 gauge wires from the remote switch location to the air cleaner 5 Use three wire nuts to connect three color coded lead wires on the remote switch to three color coded wires from the air cleaner Red Blue Violet 6 Use one wire nut to connect white color coded lead wire from the air cleaner to single color coded...

Страница 7: ...mmercial and industrial applications The filters are the most practical and effective filtering system for removing atmospheric dust pollens bacteria viruses mold spores smoke fumes mists and aerosols Refer to Fig 8 Fig 8 F111 series 1 2 3 air cleaner operation The air cleaner is either operating power on or off power off There are no other operational options available Even when the area is unocc...

Страница 8: ...h hands Slide the filter toward you 3 Place spent filter in a plastic trash bag and dispose of properly 4 Inspect the motor brackets for loose fasteners and tighten as necessary 5 Install the new filter noting the direction of airflow arrow 6 For Series 1 and 2 only Fasten the filter tabs Be sure there is a snapping sound when they are fastened The tabs are commercial Velcro and require more force...

Страница 9: ...1 32000265 4 Motor 120 V 60 Hz Series 1 1 32000270 Motor 208 230V 50 60 Hz Series 1 1 32000263 Motor 120 V 60 Hz Series 2 1 32002415 001 Motor 208 230V 50 60 Hz Series 2 1 32002415 002 Motor 120 V 3 Speed 60 Hz Series 3 1 32002415 004 Motor 230V 3 Speed 50Hz Series 3 1 32002415 005 5 99 97 HEPA media filter 3 Series 1 and 2 1 32000204 001 99 97 HEPA media filter 4 5 Series 3 1 32000204 002 95 hosp...

Страница 10: ...vised 5 09 10 CABINET ASSEMBLY LID ASSEMBLY WITH HINGES AND LATCHES PREFILTER MEDIA FILTER MOTOR MOTOR CAPACITOR BLOWER WHEEL SORBENT MEDIA MODULE 2 REQUIRED M11995E 1 6 3 4 5 7 2 Fig 9 Exploded view of F111 series 1 2 3 in Ceiling Media Air Cleaner components ...

Страница 11: ...F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER 11 68 0198 2 NOTES ...

Страница 12: ...OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PROD UCT Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation may not apply to you THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND AIR PURE SYSTEMS EXPRESSLY DISCLAIMS A...

Отзывы: