Honeywell F111 Series 1 Скачать руководство пользователя страница 3

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

3

68-0198-2

Table 2. F111 Air Volume Specifications for 3 Speed Models (Series 3).

a

Same for Single Speed Models (Series 1 & 2).

.

Fig. 1. Approximate dimensions of F111 

(Series 1,2,3) in in. (mm).

Installation Weight:

Approximately 115 lb to 155 lb (kg) depending on the filter 

configuration. Refer to Table 3.

Table 3. Sorbent Module Weight.

Sound Level at 3.3 ft (1m):

Low speed: 53 dBA (3 speed models only).
Medium speed: 57 dBA (3 speed models only)
High speed: 61 dBA.

Grille Type: 

Perforated metal.

Mounting: 

Recesses into opening on the ceiling.

Approvals:

Underwriters Laboratories Inc.: Listed. 
Canadian Standards Association: Listed.

Accessories: 

Black Color Grill
Remote 3-Speed Wall Switch 

Replacement Parts 

See Parts List, Table 5.

PLANNING THE INSTALLATION

The number of F111 (series 1,2,3) air cleaners that are needed 
is determined by taking into account the number of occupants 
and the volume of the space. Type of contamination, outdoor 
air quality and use of the area are also factors. Refer to Table 
3 for general guidelines when determining how many air 
cleaners are needed.

EXAMPLE: One air cleaner can provide 2.5 air changes per 

hour in a 24,000 cubic feet (720 cubic meters) no 
smoking area. Table 3 suggests two air cleaners 
for a 24,000 cubic feet area because most areas 
have contaminants that require more units to
 provide quality air.

If any questions should arise concerning determining the 
number of air cleaners needed for an area, consult your 
distributor or local Honeywell Commercial Air Cleaner 
Distributor.

Table 4. Determining the Minimum Number of

Air Cleaners Needed for a Space.

Model

Voltage

Particulates at 

0.3 Micron 

(DOP Test)

Gas, V.O.C. and 

Odor Control 

Modules (2)

High

a

in cfm 

(m

3

/hr)

Medium 

in cfm 

(m

3

/hr)

Low 

in cfm 

(m

3

/hr)

F111A1253W-3S 120 Vac, 60 Hz, 8.5A

95% ASHRAE

N/A

1250 (2120)

800 (1360)

450 (760)

F111A1063W-3S 120 Vac, 60 Hz,  7.2A

99.97% HEPA

N/A

  950 (1610)

775 (1310)

450 (760)

F111C1073W-3S 120 Vac, 60 Hz, 7.5A

95% ASHRAE

CPZ™ modules 1150 (1950)

825 (1400)

450 (760)

F111C1003W-3S 120 Vac, 60 Hz, 7.0A

99.97% HEPA

CPZ™ modules   825 (1400)

700 (1190)

450 (760)

F111C1012W-3S  120 Vac, 60 Hz, 8.0A

95% at 0.3 micron CPZ™ modules 1125 (1910)

825 (1400)

450 (760)

F111A2253W-3S 230 Vac, 50 Hz, 4.2A

95% ASHRAE

N/A

1125 (1910)

700 (1190)

475 (810)

F111A2007W-3S 230 Vac, 50 Hz, 3.5A

99.97% HEPA

N/A

  900 (1530)

600 (1020)

400 (680)

F111C2073W-3S 230 Vac, 50 Hz, 4.0A

95% ASHRAE

CPZ™ modules 1025 (1740)

675 (1150)

450 (760)

F111C2003W-3S 230 Vac, 50 Hz, 3.2A

99.97% HEPA

CPZ™ modules   825 (1400)

550 (930)

375 (640)

F111C1053W-3S 230 Vac, 50 Hz, 3.5A

95% at 0.3 micron CPZ™ modules   950 (1610)

625 (1060)

425 (720)

Media

Weight in lb (kg)

CPZ™ modules (2)

43 (20)

22-1/2 (572)

24 (610)

3/8 X 16
INTERNAL 
THREAD (4)

46-3/4 (1187)

48 (1219)

17-1/4

(438)

4-1/2

(114)

TOP VIEW

POWER CONNECTION 
POINT

CEILING

LINE

M11996A

Space Volume 

 (L x W x H) in Cubic 

Feet (Cubic Meter)

Number of 

Persons Present

Minimum 

Number of Air 

Cleaners

12000 to 18000 

(360 to 540)

30 to 60

1

18001 to 35000 

(540 to 1050)

61 to 90

2

Содержание F111 Series 1

Страница 1: ...ollen and some cooking smoke from the air circulated through the filter FEATURES High Efficiency Particulate Air HEPA filter models are 99 97 efficient and the hospital grade particle filter models are 95 efficient at 0 3 micron particles Both models are more efficient on particles smaller and larger There is also a 95 ASHRAE model Circulates up to 1250 cfm Designed to overcome the increase in air...

Страница 2: ...ect drive forward curve Dimensions See Fig 1 for dimensions Table 1 F111 Series 3 Description a For single speed and three speed systems set to High b F111C1061 has a new model number F111C1012B To Order F111 with a Black Grill Replace the W with a B to any model number in Table 1 Model Voltage Efficiency Gas V O C and Odor Control Modules 2 Air Volumea in cfm m3 hr Particulates at 0 3 Micron DOP ...

Страница 3: ...f any questions should arise concerning determining the number of air cleaners needed for an area consult your distributor or local Honeywell Commercial Air Cleaner Distributor Table 4 Determining the Minimum Number of Air Cleaners Needed for a Space Model Voltage Particulates at 0 3 Micron DOP Test Gas V O C and Odor Control Modules 2 Higha in cfm m3 hr Medium in cfm m3 hr Low in cfm m3 hr F111A1...

Страница 4: ...ed air up from the center of the area See Fig 2 When multiple air cleaners are installed the allotted areas to be cleaned should be equal The air throw in one direction is approximately 55 ft 17m Air velocity at 90 ft per minute 27m per minute is considered end of throw IMPORTANT Never hang the air cleaner higher than 16 ft 5m above the floor INSTALLATION WARNING Explosion Hazard Possible Can caus...

Страница 5: ...g diagram Fig 4 Typical F111 Series 3 only 120V 60 Hz or 230V 50 Hz wiring diagram Mount Air Cleaner Cabinet The air cleaner can be mounted in a drop ceiling system or hung in an open area Both mounting methods require the air cleaner to be level and positioned facing downward for correct operation 1 Remove the door grille from the carton and set it aside 2 Remove all filters 3 Fit the cabinet int...

Страница 6: ...te location 3 Attach 3 4 extension ring to outlet box 4 Run five conductor color coded 18 gauge wires from the remote switch location to the air cleaner 5 Use three wire nuts to connect three color coded lead wires on the remote switch to three color coded wires from the air cleaner Red Blue Violet 6 Use one wire nut to connect white color coded lead wire from the air cleaner to single color coded...

Страница 7: ...mmercial and industrial applications The filters are the most practical and effective filtering system for removing atmospheric dust pollens bacteria viruses mold spores smoke fumes mists and aerosols Refer to Fig 8 Fig 8 F111 series 1 2 3 air cleaner operation The air cleaner is either operating power on or off power off There are no other operational options available Even when the area is unocc...

Страница 8: ...h hands Slide the filter toward you 3 Place spent filter in a plastic trash bag and dispose of properly 4 Inspect the motor brackets for loose fasteners and tighten as necessary 5 Install the new filter noting the direction of airflow arrow 6 For Series 1 and 2 only Fasten the filter tabs Be sure there is a snapping sound when they are fastened The tabs are commercial Velcro and require more force...

Страница 9: ...1 32000265 4 Motor 120 V 60 Hz Series 1 1 32000270 Motor 208 230V 50 60 Hz Series 1 1 32000263 Motor 120 V 60 Hz Series 2 1 32002415 001 Motor 208 230V 50 60 Hz Series 2 1 32002415 002 Motor 120 V 3 Speed 60 Hz Series 3 1 32002415 004 Motor 230V 3 Speed 50Hz Series 3 1 32002415 005 5 99 97 HEPA media filter 3 Series 1 and 2 1 32000204 001 99 97 HEPA media filter 4 5 Series 3 1 32000204 002 95 hosp...

Страница 10: ...vised 5 09 10 CABINET ASSEMBLY LID ASSEMBLY WITH HINGES AND LATCHES PREFILTER MEDIA FILTER MOTOR MOTOR CAPACITOR BLOWER WHEEL SORBENT MEDIA MODULE 2 REQUIRED M11995E 1 6 3 4 5 7 2 Fig 9 Exploded view of F111 series 1 2 3 in Ceiling Media Air Cleaner components ...

Страница 11: ...F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER 11 68 0198 2 NOTES ...

Страница 12: ...OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PROD UCT Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation may not apply to you THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND AIR PURE SYSTEMS EXPRESSLY DISCLAIMS A...

Отзывы: