EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER

5

95-7520—02

Fig. 7. Termination modules (place a wire nut on each remaining wire that is not connected to a controller or device).

NOTE: When two or more wires are to be attached to the same terminal, other than 14 AWG (2.0 mm

2

), be sure to twist them 

together. Deviation from this rule can result in improper electrical contact. See Fig. 8.

Wire to the terminal blocks as follows:

1.

Strip 3/8 in. (10 mm) insulation from the conductor.

2.

Insert the wire in the required terminal location and 

tighten the screw to complete the termination.

3.

If two or more wires are being inserted into one terminal 

location, strip 1/2 in. (13 mm) of insulation from the con-

ductors then twist the wires together a minimum of three 

turns before inserting them.

4.

Cut the twisted end of the wires to 3/16 in. (5 mm) 

before inserting them into the terminal and tightening 

the screw.

5.

Pull on each wire in all terminals to check for good 

mechanical connection.

Wiring Details

The W7753A Controller has the terminal arrangements shown 

in Fig. 9 through 14. Connection for operator access to the 

E-Bus is provided by plugging the Serial LonTalk® Adapter 

(SLTA) connector into the E-Bus jack.

NOTE: If an Excel 10 Controller or Zone Manager is not 

connected to a good earth ground, the controller 

internal transient protection circuitry is compromised 

and the function of protecting the controller from 

noise and power line spikes cannot be fulfilled. This 

can result in a damaged circuit board and require 

replacement of the controller. Refer to job drawings 

for specific installation wiring diagrams.

Fig. 8. Attaching two or more wires at terminal blocks.

M12690

PART NO. 209541B

TERMINATION

MODULE

PART NO. 209541B

TERMINATION

MODULE

W7753A

1415

1415

W7753A

1415

W7753A

BROWN

BROWN

ORANGE

ORANGE

3/8

(10)

STRIP 3/8 IN. (10 MM) FROM WIRES 

TO BE ATTACHED AT ONE TERMINAL.

1.

2. TWIST WIRES TOGETHER 

WITH PLIERS (A MINIMUM 

OF THREE TURNS).

TWO 14 AWG

(2.0 MM

2

) WIRES

3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) 

BEFORE INSERTING INTO TERMINAL AND TIGHTENING

SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS

TO CHECK FOR GOOD MECHANICAL CONNECTION.

M10086

Содержание EXCEL 10 W7753A

Страница 1: ...7753A Controller communicates via the 78 kilobaud Echelon LonWorks E Bus Network Allowable input output connections consist of wall module points plus two additional resistive sensor inputs two voltage current inputs four digital inputs and eight digital Triac outputs For the W7753A any hardware driven by the Triac outputs must have a minimum current draw when energized of 25 mA and a maximum curr...

Страница 2: ...lastic cover Use the screws appropriate for the mounting surface The W7753A can be mounted in any orientation Ventilation openings were designed into the cover to allow proper heat dissipation regardless of the mounting orientation The W7753A can also be mounted using DIN rail obtain locally If using DIN rail also purchase from Augat Inc part number 2TK2D DIN rail adapter two each See Fig 3 Fig 2 ...

Страница 3: ...II restrictions U S only transformers must not be larger than 100 VA A transformer that meets CE mark requirements and that meets the Low Voltage Directive LVD requirements must be used in Europe for all installations of this product More than one W7753A Controller can be powered by a single transformer Fig 4 shows power wiring details for a single controller and Fig 5 depicts multiple controllers...

Страница 4: ...o pair can be used Unswitched 24 Vac power wiring can be run in the same conduit as the E Bus cable Do not bundle output wires with sensor digital input or communications E Bus wires Do not use different wire types or gauges on the same E Bus segment The step change in line impedance characteristics would cause unpre dictable reflections on the E Bus When using dif ferent types is unavoidable use ...

Страница 5: ... Wiring Details The W7753A Controller has the terminal arrangements shown in Fig 9 through 14 Connection for operator access to the E Bus is provided by plugging the Serial LonTalk Adapter SLTA connector into the E Bus jack NOTE If an Excel 10 Controller or Zone Manager is not connected to a good earth ground the controller internal transient protection circuitry is compromised and the function of...

Страница 6: ...ET 2 7 8 5 6 9 10 LED SET PT FAN BYPASS 1 2 3 4 5 6 7 8 E BUS 24 VAC W7753A UNIT VENTILATOR CONTROLLER 1 2 1 2 3 3 3 EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM USE THE HEAVIEST GAUGE WIRE AVAILABLE UP TO 14 AWG 2 O MM2 WITH A MINIMUM OF 18 AWG 1 O MM2 FOR EARTH GROUND WIRE TO ASSURE PROPER ELECTRICAL CONTACT WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK CONTACTS...

Страница 7: ...1 OUT 7 OUT 6 OUT 5 OUT 4 OUT 8 OUT 1 OUT 3 OUT 2 DI 2 DI 4 DI 1 DI 3 GROUND PNEUMATIC VALVE M12693 GROUND M B M 1 2 3 4 5 6 7 8 E BUS 24 VAC W7753A UNIT VENTILATOR CONTROLLER 1 2 E BUS E GND GND SNSR SETPT LED BYPASS GND GND 9 10 11 12 14 J3 15 31 30 29 28 27 26 25 24 23 22 21 20 24 VAC COM E BUS JACK 22 VDC OUT 19 18 17 16 AI 1 OHM AI 2 OHM AI 4 V mA OUT 7 OUT 6 OUT 5 OUT 4 OUT 8 OUT 1 OUT 3 OUT...

Страница 8: ...nd ordinances or as specified on installation wiring diagrams Fig 14 Typical 2 to 10 Volt DC humidity sensor to W7753A For note 2 refer to Fig 8 1 2 3 4 5 6 7 8 E BUS 24 VAC 1 2 E BUS E GND GND SNSR SETPT LED BYPASS GND GND 9 10 11 12 14 J3 15 31 30 29 28 27 26 25 24 23 22 21 20 24 VAC COM E BUS JACK 22 VDC OUT 19 18 17 16 AI 1 OHM AI 2 OHM AI 4 V mA OUT 7 OUT 6 OUT 5 OUT 4 OUT 8 OUT 1 OUT 3 OUT 2...

Страница 9: ...roadcasting the Service Message The Service Message allows a device on the E Bus to be positively identified The Service Message contains the controller ID number and therefore can be used to confirm the physical location of a particular Excel 10 in a building There is one method of broadcasting the Service Message from an Excel 10 W7753A Controller This uses a hardware push button on the side of ...

Страница 10: ...cycled or the node is reset The alarm is not issued until FanFailTime seconds have elapsed since the loss of flow condition was first reported DIRTY_FILTER 7 The pressure drop across the filter exceeds the limit and the filter requires maintenance The control runs normally SMOKE_ALARM 8 The smoke detector has detected smoke and the node has entered an emergency state IAQ_OVERRIDE 9 The indoor air ...

Страница 11: ...EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER 11 95 7520 02 ...

Страница 12: ...nal Inc 95 7520 02 K K Rev 03 09 Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 Honeywell GmbH Böblinger Straße 17 D 71101 Schönaich customer honeywell com ...