EXCEL 10 W7751H SMART VAV ACTUATOR

7

95-7553—04

Fig. 14. Auxiliary switch cam adjustment.

NOTE: For 2 or 3 switch models, cams align with their 

respective switches and are individually set 

using the same procedure described above.

6.

Ensure switch activation at the desired degree of stroke 

by commanding the actuator to both fully open and fully 

closed; see step 3.

NOTE: Switches can also be preset prior to actuator 

installation if angular switch position is known.

Communications

Refer to 

L

ON

W

ORKS

® Bus Wiring Guidelines, form 74-8565

for complete description of L

ON

W

ORKS

® Bus network topology 

rules.f

If a longer L

ON

W

ORKS

® Bus network is required, a Q7740A 

2-way or Q7740B 4-way Repeater can be added to extend 

L

ON

W

ORKS

® Bus length, only if this is an Energy 

Management (PAZX) Bus.

IMPORTANT

The Q7740A,B Repeaters cannot be used in 

smoke control applications.

A Q7751A Router can only be added to an Energy 

Management Bus to partition system into two segments 

(effectively doubling L

ON

W

ORKS

® Bus length). Only one 

router is allowed with each Excel 10 Zone Manager (or Excel 

15 Building Manager), and each network segment can have a 

maximum of one repeater.

Pull the cable to each device on the L

ON

W

ORKS

® Bus and 

connect to communication terminals 11 and 12 (W7751H).

IMPORTANT

Screw type terminal blocks are designed to accept 

no more than one 14 AWG (2.0 mm

2

) conductor. 

Multiple 14 AWG (2.0 mm

2

) wires can be connected 

with a wire nut. Include a pigtail with this wire group 

and attach the pigtail to the individual terminal block.

Notes on LonWorks® Bus Communications Wiring:

• All field wiring must conform to local codes and ordinances 

(or as specified on the installation drawings).

• Approved cable type is Level IV 22 AWG (0.34 mm

2

plenum or non-plenum rated unshielded, twisted pair, solid 

conductor wire:

— For nonplenum areas, use CMP listed cable.

— In plenum areas, use CMP listed cable.

• Do not bundle output wires with sensor, digital input or 

L

ON

W

ORKS

® Bus wires.

• Ensure that neither L

ON

W

ORKS

® Bus wire is grounded.

• In noisy (high EMI) environments, avoid wire runs parallel 

to noisy power cables, motor control centers, or lines 

containing lighting dimmer switches. Keep at least 3 in. 

(76 mm) of separation between noisy lines and 

L

ON

W

ORKS

® Bus cable.

• Do not use different wire types or gauges on the same 

L

ON

W

ORKS

® Bus segment:

— Step changes in line impedance characteristics cause 

unpredictable reflections on the L

ON

W

ORKS

® Bus.

Wiring Details

Wire to the terminal blocks as follows:

1.

Strip 3/16 in. (5 mm) insulation from the conductor.

2.

Insert the wire in the required terminal location and 

tighten the screw to complete the termination.

NOTE: With the exception of 14 AWG (2.0 mm

2

), if 

inserting two or more wires into one terminal 

location, twist wires together before inserting 

them. See Fig. 15. Deviation from this rule can 

result in improper electrical contact.

The controller on the W7751H has the terminal arrangement 

shown in Fig. 16. Fig. 16 through 21 provide detailed wiring 

diagrams for the W7751H. Refer to installation diagrams for 

specific wiring.

NOTE: Ensure Configuration DIP Switch is set as shown in 

Fig. 19. Switches 1 through 3 set ML7984B Valve 

Actuator timing to match W7751H outputs (0.1 sec. 

minimum with maximum time of 25.6 sec.). Switch 4 

determines actuator action (Off = Direct Acting, On = 

Reverse Acting).

Fig. 15. Attaching two or more wires at terminal blocks.

SWITCH CAMS

M2076A

1/2

(13)

STRIP 1/2 IN. 

(13 MM) FROM 

WIRES TO BE 

ATTACHED AT 

ONE TERMINAL.

1.

2.

TWIST WIRES 

TOGETHER 

WITH PLIERS 

(A MINIMUM OF 

THREE TURNS).

3.

CUT TWISTED END OF WIRES TO 

3/16 IN. (5 MM) BEFORE INSERTING 

INTO TERMINAL AND TIGHTENING

SCREW. THEN PULL ON EACH WIRE

IN ALL TERMINALS TO CHECK FOR 

GOOD MECHANICAL CONNECTION.

M11413

CONTROLLER OR

WALL MODULE 

E-BUS CONNECTOR

TERMINALS

Содержание Excel 10 W7751H

Страница 1: ...riac output loads must draw a minimum current of 25 mA at 24 Vac 60 Hz nominal Triac maximum current rating 77 mA The actuator on the W7751H mounts directly onto the VAV box damper shaft and has up to 70 lb in torque 8 Nm 90 degree stroke and 90 second timing at 60 Hz The actuator on the W7751H can accommodate the optional field installed auxiliary switches NOTE Mounting thermostat sensor greater ...

Страница 2: ...duit NOTE The assembly is intended only for mounting to a horizontal shaft The W7751H actuator is shipped in the fully clockwise CW position 90 degree The W7751H Assembly must be mounted to a horizontal damper shaft to assure proper heat dissipation from the controller housing Mount the W7751H so that the actuator is parallel with the VAV box damper housing In general it is recommended that a wash...

Страница 3: ...damper opening angle 45 60 or 90 degrees Fig 5 Determining rotation direction CW or CCW for damper opening If damper shaft diameter is 3 8 inch 10 mm round or square use part 201391 Shaft Adapter shipped with the W7751H Smart VAV Actuator Ensure it is placed opposite set screws See Fig 6 The adapter centers a 3 8 in 10 mm shaft in the hub Failure to use the adapter on a 3 8 in 10 mm shaft causes t...

Страница 4: ... yet Before the part no 201614 Range Stop Pin which is shipped with the W7751H Smart VAV Actuator can be inserted in either the 45 or 60 degree CW slot the damper actuator must be driven fully open CCW To do this the controller on the W7751H must be wired powered and connected to the portable PC via the Serial LonTalk Adapter SLTA The SLTA connects to the controller on the W7751H via the jack for ...

Страница 5: ...a verified earth ground for each controller in the group See Fig 10 Controller configurations are not necessarily limited to three devices but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer See System Engineering form 74 2949 for power wiring recommendations All loads on an Excel 10 Controller must be powered by a single transformer Keep the ea...

Страница 6: ...he portable PC via the SLTA The SLTA connects to the controller on the W7751H via Network Access Jack on the T7770 Wall Module or by B Port on the Q7750A Zone Manager From E Vision Software drive the W7751H actuator and halt the motion at the desired position for switch operation NOTE When installed angular position indicator on the switch face moves from 90 to 0 degrees during CCW motion and from...

Страница 7: ...air solid conductor wire For nonplenum areas use CMP listed cable In plenum areas use CMP listed cable Do not bundle output wires with sensor digital input or LONWORKS Bus wires Ensure that neither LONWORKS Bus wire is grounded In noisy high EMI environments avoid wire runs parallel to noisy power cables motor control centers or lines containing lighting dimmer switches Keep at least 3 in 76 mm of...

Страница 8: ...T BE TWISTED TOGETHER BEFORE INSERTING INTO THE TERMINAL BLOCK MICROBRIDGE DP SENSOR AIR FLOW DP PICKUP AIR FLOW DIRECTION LOW HI 2 M6410 SERIES 60 VALVE ACTUATOR COM STEM UP STEM DOWN TRIAC EQUIVALENT CIRCUIT TWO OR THREE WAY VALVE SET PT 1 2 3 4 5 6 7 8 9 10 11 12 EARTH GROUND 24 VAC COM OUT 1 OUT 2 E BUS COMM OUT COMM IN 24 VAC NOTE LOAD POWER WIRE IS CONNECTED TO TERMINAL 1 W7751H M10526 1 2 2...

Страница 9: ... the Excel 10 FTT Termination Module Installation Instructions form 95 7554 Correct placement of the termination module s is required for proper LONWORKS Bus communications Step 2 Startup Broadcasting the Service Message The Service Message allows a device on the LONWORKS Bus to be positively identified The Service Message contains the controller neuron ID number and therefore can be used to confi...

Страница 10: ...appears in one of the following allowable states 1 Off no power to the processor 2 Continuous on processor is in initialized state 3 Slow blink controlling normal state 4 Fast blink when the Excel 10 VAV Controller has an alarm condition When an Excel 10 has an alarm condition it reports it to the central node on the LONWORKS Bus Also the Excel 10 VAV Controller variables AlarmLogX where X is 1 th...

Страница 11: ... BLOCK ML7984B REHEAT VALVE ACTUATOR PWM OUTPUT FROM CNTRL PWM H 24 VAC PWM VALVE ACTUATOR 24 N 24 H T6 T5 C B W R SERIES OR PARALLEL FAN CONTACTOR 24 VAC SET PT 1 2 3 4 5 6 7 8 9 10 11 12 24 VAC COM OUT 1 OUT 2 E BUS 24 VAC W7751H M10530 WALL MODULE EARTH GND SENSOR BYPASS LED NOT EARTH GROUND TRIAC EQUIVALENT CIRCUIT 3 2 4 1 1 2 3 4 REVERSE WIRES INCREASE DECREASE TO REVERSE ACTION DIRECT REVERS...

Страница 12: ... only if used for Energy Management Q7740A B and Q7751A Devices for use on an Energy Management and or Smoke Control 14507287 Series Power Supplies W7751B2010 W7751D2016 W7751F2011 W7751H2025 Series 9 W7761A2010 Q7750 Q9200 XFL521 XFL522 XFL523 XFL524 XL500 XLINK Connect the controller with the laptop PC To do this the controller on the W7751H must be wired powered and connected to the portable PC...

Отзывы: