OneSwitch

OneSwitch  Dimming  affords  local  control  to  the  end-user  whereby  a  simple, 
momentary, push-to-make wall switch can be used to raise or lower the lighting level or 
toggle the output of the unit ON or OFF. A short press (less than 1 second) toggles all 
outputs from 

both

 OFF to 

both

 ON or from 

either

 ON to 

both

 OFF. A long press will ramp 

the digital output either up or down with no effect on the volt-free output. If the output 
prior to pressing the switch is above 90% the output will ramp down; if below 90% it will 
ramp up. If the latest press and the current press are within 5 seconds of each other it will 
ramp in the opposite direction.   A latching switch can be used to override the outputs 
OFF or ON at maximum output. 

User Overrides

The end-user can configure a number of lighting scenes that can be recalled using a 
hand-held override. With an HC5A hand-held controller lighting can be overridden OFF 
or ON, or a set level can be chosen, affecting either the controlled group or, with an MLS 
system, the whole zone. Regulating and switched loads can be adjusted independently 
through a combination of OneSwitch Dimming and the HC5A. 

Important Additional Notes

1.  All terminals on this product are provided for final connections.   It is not intended that the 

product be used as a junction box for looping cables.  

2.  A means for disconnection must be incorporated in the fixed wiring in accordance with the 

current wiring regulations.

3.  Although nominally 12V, the dimming output is not SELV and therefore should be treated 

with the same respect as mains with regard to wiring practice.  

4.  The dimming control output should be connected only to the control input of the ballasts - 

never to other detectors.

5.  Due  to  the  fact  that  the  photocell  is  on  the  ceiling  looking  down,  it  is  not  possible  for 

measurements made with a lux meter on the working plane to remain constant when daylight 
illuminates the ceiling and the working plane to a differing extent.  Therefore, products of this 
type should be regarded as capable of maintaining an APPROXIMATE light level only.

6.    This  equipment  switches  lights  no  more  frequently  than  would  a  responsible  human 

occupant.  However, manufacturers of some lighting types (e.g. ‘2D’ luminaires) may specify 
a maximum number of switching cycles in order to achieve a predicted lamp life.   Please 
check  with  the  manufacturer  of  the  luminaires  to  ensure  that  they  are  compatible  with 
automatic controls in this respect. 

7

Содержание Ex-Or MLS2021DF

Страница 1: ...uctions Note QuickSet Pro required for commissioning 1 MLS2021DSM MLS2021DALISM MLS2021DF MLS2021DSM for DSI ballasts MLS2021DALIF MLS2021DALISM for DALI ballasts Digital Gold PIR Detector with regulating photocell MLS2021DF MLS2021DALIF ...

Страница 2: ...or DALI luminaires a switched load of up to 6 Amps or a combination of the two When controlling DSI or DALI ballasts the ballast type must not be mixed The DSI or DALI input terminals on the ballasts should be connected in parallel with each other and to the Polarity Free Digital Output terminals on the rear of the detector Each DSI or DALI luminaire is controlled completely by its digital input a...

Страница 3: ... maintained NC NC 2 x MLS2021D In Parallel using Switched Output only LOAD Max 6Amps N E L Permanent or switched supply VOLT FREE OUTPUT VOLT FREE OUTPUT LIVE IN LIVE IN NEUTRAL NEUTRAL EARTH EARTH Any connection not shown is NO CONNECTION ONE SWITCH NC NC ONE SWITCH Relay outputs may be connected together in parallel to cover larger areas however the total load on all combined relay outputs must ...

Страница 4: ...ogrammed if desired by use of the infrared programming tool QuickSet Pro All settings are retained in the event of a power failure Commissioning The units are supplied with the factory default settings shown below which make further commissioning unnecessary in many applications To make use of the programmable settings an infrared commissioning tool is required QuickSet Pro A ten second time delay...

Страница 5: ...rolled lighting on entry when natural light is sufficient i e SET POINT LOW is exceeded but only ACTIVE mode will extinguish the lighting if natural light increases sufficiently during occupancy i e SET POINT HIGH is exceeded continuously for a period equal to OFF DELAY The lighting is restored immediately if the illumination level subsequently drops below SET POINT LOW iii Photocell DISABLED If t...

Страница 6: ...ready on switch them on manually by pressing UTILITIES LIGHTSPOT MLS LCM IR REMOTE Luminaire OK QuickSet Pro or HC5A Fluorescent lights do not reach full output until up to 15 minutes after being switched on so ensure that the lights are fully warmed up before continuing 2 Wait until the time of day when the natural light level is at the point below which you would want the lights to be on and abo...

Страница 7: ...neSwitch Dimming and the HC5A ImportantAdditional Notes 1 All terminals on this product are provided for final connections It is not intended that the productbe used as a junction box for loopingcables 2 A means for disconnection must be incorporated in the fixed wiring in accordance with the currentwiringregulations 3 Although nominally 12V the dimming output is not SELV and therefore should be t...

Страница 8: ...NDED LOAD VOLT FREE 6 Amps MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts COLOUR White RAL9010 MATERIAL Flame retardant PC ABS WEIGHT 210g flush version 187g surface version IP RATING 3X o o OPERATING TEMPERATURE 0 C to 40 C W4426G 6 0m 2 5m Fascia 10mm deep 8 100mm Honeywell Ex Or St Marks Court North Street Horsham West Sussex RH12 1BW UK Tel 44 0 1942 719229 Fax 44 0 1942 508753 Email technicals...

Отзывы: