Parameter
Power up
Response
Off delay
On Sensitivity
Bus Connect
1st Zone
2nd Zone
3rd Zone
4th Zone
Corridor 1
Corridor 2
Global 1 Rx
Global 2 Rx
Manual I/P
Start Lamps
Entry Scene
Lamp Max
Dimming
Fade to Off
Vacant
Bright-Out
Photocell
Set Point Low
Set Point High
Default
Setting
ON
AUTO
20 min
100
YES
-
-
-
-
-
-
NO
NO
LOCAL
MAX
Scene 1
100%
100%
NO
OFF
NO
Disabled
1023
1023
Options
ON/OFF
Auto, Manual/Bus, Manual Only
1min - 96hrs, Disabled
0-100
YES/NO
1-100 addresses
1-100 addresses
1-100 addresses
1-100 addresses
1-100, Building Zone Span
1-100, Building Zone Span
YES/NO
YES/NO
LOCAL/SHARE
MAX/MIN
Scene 1-6
10% - 100%
Regulate 100% to 50%
YES/NO
(10 Alternative Exit Scenes)
YES/NO
Active, Passive, Disabled
1-1023
1-1023
Notes
Each of these settings
can be re-programmed,
if desired, by use of the
infrared programming
tool QuickSet Pro.
All settings are retained
in the event of a power
failure.
Commissioning
The units are supplied with the factory default settings shown below which make further
commissioning unnecessary in many applications. To make use of the programmable
settings, an infrared commissioning tool is required (QuickSet Pro). A ten-second time
delay is selectable from programmer to aid commissioning.
Sensitivity to Movement
While the factory settings will be correct for many applications, the sensitivity can be
adjusted if required. The ON RANGE setting controls the sensitivity, with higher
numbers giving greater sensitivity. Like all programmable parameters, the sensitivity
setting will be retained in the event of a power failure and can be re-programmed any
number of times.
Factory Default Settings
These are the settings to which the units have been programmed before they leave
the factory.
4