Programming the Photocell Set-points (Continued)

Tip: Turn the lights off with the QuickSet Pro (UTILITIES  / LIGHTSPOT/MLS/LCM / 
IR REMOTE / HC5) to measure the perceived light level with no contribution from the 
controlled lighting.

 

Alternatively the SET-POINTS can be configured semi-automatically;

 

i) The Primary Interest is the Regulating Control Output.

With the photocell configured as DISABLED:-

Using the QuickSet Pro  (UTILITIES / LIGHTSPOT/MLS/LCM / SET LIGHT LEVEL) 
or HC5A  (+,- Scene 1) set the required light output from the controlled luminaires and 
then press and hold   OK (QuickSet Pro) or Scene 1 (HC5A) until the controlled lights 
"blink" to indicate that a new SET-POINT LOW has been stored and a calculated SET-
POINT HIGH has also been inserted. Using the QuickSet Pro the photocell can now be 
re-configured as ACTIVE or PASSIVE if required.

With the photocell configured as ACTIVE or PASSIVE:-

1) If the lights are not already on, switch them on manually by pressing ‘UTILITIES / 
LIGHTSPOT/MLS/LCM  /  IR  REMOTE  /  Lu  /  OK’  (QuickSet  Pro)  or  "+" 
(HC5A). Fluorescent lights do not reach full output until up to 15 minutes after being 
switched on, so ensure that the lights are fully warmed up before continuing.  

2) Wait until the time of day when the natural light level is at the point below which you 

would

 want the lights to be on, and above which you 

would not

 want the lights to be on.

3)  Start  the  internal  self-programming  mechanism  by  pressing  ‘UTILITIES  / 
LIGHTSPOT/MLS/LCM / SET LIGHT LEVEL / OK’ (QuickSet Pro) or Scene 1 (HC5A). 
The detector takes a photocell reading, adds a small amount and stores the value in 
SET-POINT HIGH. Then it turns the lights off, makes another measurement and stores 
the  value  in  SET-POINT  LOW.    The  lights  now  switch  on  again  to  acknowledge  a 
successful programming operation.

The two switching thresholds have now been set, and the difference between them is 
equal  to  slightly  more  than  the  contribution  made  by  the  electric  lighting. This  is  the 
perfect amount of hysteresis to ensure that the lights will not oscillate. 

 

6

Содержание Ex-Or MLS2021DF

Страница 1: ...uctions Note QuickSet Pro required for commissioning 1 MLS2021DSM MLS2021DALISM MLS2021DF MLS2021DSM for DSI ballasts MLS2021DALIF MLS2021DALISM for DALI ballasts Digital Gold PIR Detector with regulating photocell MLS2021DF MLS2021DALIF ...

Страница 2: ...or DALI luminaires a switched load of up to 6 Amps or a combination of the two When controlling DSI or DALI ballasts the ballast type must not be mixed The DSI or DALI input terminals on the ballasts should be connected in parallel with each other and to the Polarity Free Digital Output terminals on the rear of the detector Each DSI or DALI luminaire is controlled completely by its digital input a...

Страница 3: ... maintained NC NC 2 x MLS2021D In Parallel using Switched Output only LOAD Max 6Amps N E L Permanent or switched supply VOLT FREE OUTPUT VOLT FREE OUTPUT LIVE IN LIVE IN NEUTRAL NEUTRAL EARTH EARTH Any connection not shown is NO CONNECTION ONE SWITCH NC NC ONE SWITCH Relay outputs may be connected together in parallel to cover larger areas however the total load on all combined relay outputs must ...

Страница 4: ...ogrammed if desired by use of the infrared programming tool QuickSet Pro All settings are retained in the event of a power failure Commissioning The units are supplied with the factory default settings shown below which make further commissioning unnecessary in many applications To make use of the programmable settings an infrared commissioning tool is required QuickSet Pro A ten second time delay...

Страница 5: ...rolled lighting on entry when natural light is sufficient i e SET POINT LOW is exceeded but only ACTIVE mode will extinguish the lighting if natural light increases sufficiently during occupancy i e SET POINT HIGH is exceeded continuously for a period equal to OFF DELAY The lighting is restored immediately if the illumination level subsequently drops below SET POINT LOW iii Photocell DISABLED If t...

Страница 6: ...ready on switch them on manually by pressing UTILITIES LIGHTSPOT MLS LCM IR REMOTE Luminaire OK QuickSet Pro or HC5A Fluorescent lights do not reach full output until up to 15 minutes after being switched on so ensure that the lights are fully warmed up before continuing 2 Wait until the time of day when the natural light level is at the point below which you would want the lights to be on and abo...

Страница 7: ...neSwitch Dimming and the HC5A ImportantAdditional Notes 1 All terminals on this product are provided for final connections It is not intended that the productbe used as a junction box for loopingcables 2 A means for disconnection must be incorporated in the fixed wiring in accordance with the currentwiringregulations 3 Although nominally 12V the dimming output is not SELV and therefore should be t...

Страница 8: ...NDED LOAD VOLT FREE 6 Amps MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts COLOUR White RAL9010 MATERIAL Flame retardant PC ABS WEIGHT 210g flush version 187g surface version IP RATING 3X o o OPERATING TEMPERATURE 0 C to 40 C W4426G 6 0m 2 5m Fascia 10mm deep 8 100mm Honeywell Ex Or St Marks Court North Street Horsham West Sussex RH12 1BW UK Tel 44 0 1942 719229 Fax 44 0 1942 508753 Email technicals...

Отзывы: