Additive Lines (6)
8 - 5
Model 1010 Application Pack CB
Part No.: 4418024 - Rev. 1
Programming Manual
Leaking Solenoid
Vol Limit
Enter the volume, that when detected within the leaking solenoid time
period, will result in an alarm.
Constraints:
Available only when the injection point is enabled and assigned an
arm.
Leaking solenoid alarm is enabled.
Enter a value in following range:
0 to 999 (100*)
NOTE:
The units for leaking solenoid volume limit will be ml in case of Metric units
and cc in case of US units.
Inj n No Flow Alarm
Enables or disables the No Flow Alarm for an injection point.
If there is no additive flow detected in the stipulated time after opening
the solenoid for the additive injection, the injector will increment the
solenoid retry count and wait for flow. If this continues to occur, when
the solenoid retry count exceeds the configured no of solenoid retries
then no additive flow timeout will be indicated.
Constraints:
Available only when the injection point is enabled and assigned an
arm.
Select one of the following options:
Enable
Disable*
No Additive
Flow Timeout
Enter the no flow timeout for additive in seconds.
Constraints:
Available only when the injection point is enabled and assigned an
arm.
No Flow Alarm is enabled.
Enter a value in following range:
1 to 9 (2*)
No Flow
Solenoid Retries
Enter the maximum number of retries after which a no flow timeout error
is reported.
Constraints:
Available only when the injection point is enabled and assigned an
arm.
No Flow Alarm is enabled.
Enter a value in the following range:
0 to 2 (2*)
Inj n Additive Deviation
Enables or disables the additive deviation alarm for an injection point.
Содержание Enraf 1010 CB
Страница 1: ...Programming Manual Load Computer 1010 CB ...
Страница 6: ...vi Model 1010 Application Pack CB Part No 4418024 Rev 1 Programming Manual Intentionally left blank ...
Страница 86: ...Recipes 7 9 4 Model 1010 Application Pack CB Part No 4418024 Rev 1 Programming Manual Intentionally left blank ...
Страница 98: ...Glossary 4 Model 1010 Application Pack CB Part No 4418024 Rev 1 Programming Manual Intentionally left blank ...