EConnect™ Wireless Thermostat Kit TL9160AR
Installation in a 4-11/16’’ square junction box
ELECTRICAL HAZARD
Can cause electrical shock or equipment damage.
Disconnect AC power
before beginning installation.
Wiring must comply with local electrical
codes. Use special CO/ALR solderless connectors if supply wires are made of
aluminum.
1 Mount the junction box on the wall. Punch out
knockout(s), install strain relief bushing(s) and feed
the supply wires and the heater wires. Punch out
another knockout to install the antenna (step 2).
2 Remove the locknut from the antenna and peel
off the adhesive backing. Feed the antenna cable
through the knockout opening and mount the
antenna. Put the locknut and tighten.
Relay wires must be at the top
3 Clean the interior side of the junction box where
the relay will be installed. Peel off the adhesive
backing of the relay module and stick the relay
inside the junction box.
To heater
L2 L1 : For 240V application
N L : For 120V application
Blue
Black
Re
d
4 Connect the supply wires and heater wires to the
relay.
See page 6 if you are connecting more than one
heater.
5 Insert the antenna plug in the relay receptacle until
you hear a click.
6
Install a cover plate on the junction box
and
apply power to the heater. Do not put the antenna
cover back yet.
ELECTRICAL HAZARD
Can cause electrical shock. Install junction box
cover plate before applying power.