Emergency Command Center Manual —
P/N LS10001-000FL-E:G 5/3/2016
77
Programmed Activation by FACP
Programming
When using the FACP ACS-bus protocol, address 01 must be enabled in the FACP programming.
(Refer to the FACP user manual.) When using the ANN-Bus protocol, the FACP will automatically
detect the audio system connection during annunciator auto-configuration. No ANN-Bus address
selection is necessary at the FACP.
Once the FACP can communicate with the audio system, FACP zones Z33 through Z56 become
dedicated as output zones for speaker circuits 1 through 24 respectively. FACP zone Z32 is dedi-
cated to turn on all speaker circuits. FACP programming allows association between any address-
able SLC input device (module, detectors) with any of the speaker circuits. In addition, 1 of 14
messages can be generated over the selected speaker circuit.
Any fault in the audio system is sent to the FACP via the FACP Data Bus and is indicated as an
annunciator fault on the FACP display.
Column Descriptions for Table 3.2:
•
FACP
- the Fire Alarm Control Panel being used
•
Individual Audio Zone Control via FACP Data Bus
- ACS or ANN-BUS compatible FACPs
can control each audio zone on the ECC-50/100 (refer to Section 3.6.1.)
•
Individual Control of All Messages
- control of all voice messages in the ECC-50/100 can be
accomplished through the FACP Data Bus or by triggering the CMD inputs (refer to
•
Simultaneous Activation of All Audio Zones
- this is a single trip mechanism via a zone on the
FACP Data Bus or CMD input trigger that activates all the audio zones at the same time (refer
3.6.1 MS-9600(UD)LS and MS-9200UDLS
Important Notes:
1. For proper operation, a message must be assigned to each FACP zone that is programmed to
activate an audio speaker circuit.
2. The message repeat setting on the ECC-50/100 should be set to infinite. This will ensure that
lower priority activated zones will continue to broadcast the voice message.
3. CMD inputs are not used for activation when the FACP Data Bus is being used, however,
4.7K
Ω
ELRs must still be connected across CMD3 - CMD8.
FACP
Individual
Audio
Zone Control
via
FACP Data Bus
Individual Control of
All Messages
Simultaneous
Activation of All
Audio Zones
ACS
ANN
ACS
ANN
CMD
MS-9600LS software version 4 or higher
Yes
Yes
Yes
Yes
Yes
Yes
MS-9200UDLS software version 6 or
higher
(hardware revision 3)
Yes
Yes
Yes
Yes
Yes
Yes
MS-9200UDLS software version 4
(hardware revision 2)
Yes
No
Yes
(Limited)
1
1 Limited to five (5) messages- fire only.
No
Yes
Yes
MS-9200UDLS software version 2 or 3
(hardware revsion 1)
Yes
No
Yes
(Limited)
No
Yes
Yes
Table 3.2 FACP Message/Zone Control Capability
Содержание ECC-50/100
Страница 83: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 83 Notes ...
Страница 95: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 95 Notes ...
Страница 102: ...102 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Notes ...
Страница 106: ...106 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Страница 108: ...108 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Страница 114: ...Cut along dotted line ...
Страница 116: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...