Product Features
Product Description
– two Style Y (Class B) or Style Z (Class A) speaker circuits (with optional ECC-50W-
25/70V Audio Amplifier installed)
– eight Style Y (Class B) or Style Z (Class A) speaker circuits (with optional ECC-50W-
25/70V
and
ECC-CE6 installed)
•
ECC-50/100 can be controlled by an FACP via the ANN/ACS (EIA-485) link. Compatible
FACPs include the MS-9600(UD)LS and MS-9200UDLS.
•
Integral supervised microphone
•
Microphone time-out feature which reverts back to prerecorded message if emergency page
exceeds the programmed time
•
Up to 14 recorded messages
•
14 prerecorded messages for fire, emergency, and weather alerts
•
Field-selectable message and custom message recording capability using the local
microphone, a USB port, or an external audio input
•
External Audio Input can be used for background music
•
Up to 60 second message duration for all messages
•
Integral tone generators field selectable for multiple tone types
•
Powered by integral AC power supply or batteries during AC fail
•
Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss
•
Piezo sounder for local trouble
•
100 event history log
•
Three Form-C relays:
– AC Power Loss Relay - TB1
– System Trouble Relay - TB2
– MNS Active - TB3
•
500 mA (0.5A) Special Application (auxiliary power) output for addressable modules when
interfaced with compatible addressable FACPs and End-of-Line power supervision relays
•
System Status LEDs (refer to “Controls and Indicators” on page 20)
•
Integral Dress Panel
•
Optional TR-CE semi-flush trim ring
•
Any combination of up to eight (8) of:
– Optional ECC-RM Remote Microphone (includes cabinet).
– Optional ECC-RPU Remote Page Unit (includes cabinet)
– Optional ECC-LOC (includes cabinet)
•
Optional ECC-CE6 Circuit Expander
•
Optional ECC-50W-25V amplifier, 50 watts, 25 volts
•
Optional ECC-50W-70V amplifier, 50 watts, 70 volts
•
Optional ECC-50DA distributed amplifier, 50 watts
•
Optional ECC-125DA distributed amplifier, 125 watts
•
Optional ECC-50BDA distributed amplifier, 50/100 watts
Содержание ECC-50/100
Страница 83: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 83 Notes ...
Страница 95: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 95 Notes ...
Страница 102: ...102 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Notes ...
Страница 106: ...106 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Страница 108: ...108 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Страница 114: ...Cut along dotted line ...
Страница 116: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...