Cut alo
ng do
tte
d
line.
This sheet must be framed and mounted adjacent to the control panel.
Document LS10039-000FL-E Rev A ECN 13-186 4/9/2013
ECC-50/100 and ECC-LOC OPERATING INSTRUCTIONS
Section 1 Operating Information
N
ORMAL
S
TANDBY
O
PERATION
.
1. Green AC P
OWER
indicator lit steadily.
2. Yellow T
ROUBLE
indicators off.
3. Green speaker zone indicators off.
A
LARM
C
ONDITION
.
1. Green speaker zone indicator(s) lit steadily.
2. Green S
YSTEM
IN
U
SE
indicator lit steadily.
3. Audio message plays.
4. Green F
IRE
S
YSTEM
A
CTIVE
indicator lit steadily (when FACP is in alarm).
5. Green MNS C
ONTROL
indicator lit steadily and relay activated (for mass
notification events).
A
LARM
R
ESET
.
After locating and correcting a fire alarm condition at the
FACP, the system will return to Normal Standby Operation. After correcting a
mass notification event, press the MNS C
ONTROL
button to clear the system
and return to Normal Standby Operation.
T
ROUBLE
C
ONDITION
.
Activation of trouble signal under normal operation
indicates a condition that requires
immediate
attention. Contact your local
service representative. Silence the audible signal by pressing the T
ROUBLE
S
ILENCE
switch. The trouble indicator will remain illuminated.
Section 2 Paging and Manual Message Control
1. Press the S
YSTEM
C
ONTROL
button if the green LED is not lit.
2. Press either the A
LL
C
ALL
button or individual speaker zone buttons. This
will override the evacuation tone/message if panel is in alarm and activate
desired speaker circuits.
3. Once the OK TO PAGE lights green, broadcast:
•By paging: Key the microphone by pressing the push-to-talk switch on side
of microphone and speak clearly into the microphone.
•By prerecorded message: Press the desired message button.
4. Press the A
LL
C
ALL
switch (or individual speaker zone buttons) to end
broadcast and continue evacuation tone/message.
5. Press the S
YSTEM
C
ONTROL
button to relinquish control of the audio
system.
Section 3 Switch Functions
A
LL
C
ALL
.
Activates all speaker circuits for broadcast.
MNS C
ONTROL
(for systems configured for mass notification operation
which has higher priority)
.
Activates the MNS Active Relay and the onboard
NAC. A second press turns these back off. For a combination fire and mass
notification system, pressing MNS C
ONTROL
will result in the shutdown of
audible FACP NACs and audio system speakers, allowing the system to
override the system. Pressing MNS C
ONTROL
again causes the FACP to re-
activate audible FACP NACs and audio system speakers.
S
YSTEM
C
ONTROL
.
Manually gains control of the audio system in preparation
for an ALL CALL, message activation, or general page. The green LED will turn on
steadily to confirm control. A second press is required after paging to relinquish
control of the system. The main console will have system priority based upon user
programming. In order for the LOC to gain control, the ECC must first relinquish
control of the system.
S
PEAKER
S
ELECT
1-24.
Manually activates or deactivates speaker zones
(circuits).
M
ESSAGE
S
ELECT
1-8.
Manually activates or deactivates stored
messages. 8th button becomes a “shift” for messages 9-14.
D
IAGNOSTIC
S
ELECT
.
selects a specific remote amplifier to examine
specific trouble conditions for the remote amplifiers. The fault LEDs with
wrench graphics represent the amplifier selected.
T
ROUBLE
S
ILENCE
.
Manually silences the local trouble sounder.
C
ONSOLE
L
AMP
T
EST
.
Tests the local LEDs and sounder.
Section 4 LED Indicators
F
IRE
S
YSTEM
A
CTIVE
.
Green LED that turns on steady when the FACP is
in alarm.
MNS C
ONTROL
.
Green LED that turns on steady when an operator has
initiated a mass notification event by pressing the MNS Control button or by
pressing an MNS message button.
S
YSTEM
C
ONTROL
.
Green LED that turns on steady when the main
console has control of the audio system.
S
YSTEM
IN
U
SE
.
Green LED text that turns on steady when the main
console, an LOC, an RPU, or an RM has control of the audio system.
S
PEAKER
Z
ONES
1-24.
Green LED per speaker circuit button that turns
on steady when a speaker circuit has been selected and is active. Yellow LED
per speaker circuit button that turns on steady when a speaker circuit fault
exists or when the speaker circuit has been turned off after having been
automatically turned on by the FACP.
OK
TO
P
AGE
.
Green LED text that turns on steady when the system is
ready for paging.
M
ICROPHONE
T
ROUBLE
.
Yellow LED text that turns on steady to indicate
a microphone wiring fault.
M
ESSAGES
1-8.
Red LED per message button that turns on steady when
the message has been selected and blinks when the message has been
overridden. Yellow LED per message button that turns on steady when no
message has been recorded or there is an associated command input fault. All
eight message button LEDs will turn on steady to indicate a message generator
fault. 8th button “shift” key red off when viewing messages 1-7 and on steady
when viewing messages 8-14. Yellow LED will turn on indicating a message
trouble in the group of messages not currently being viewed.
R
EMOTE
A
MPLIFIERS
1-8 F
AULT
.
Yellow LED per remote amplifier that
turns on steady when an amplifier has a fault.
LOC/RPU/RM 1-8 F
AULT
.
Yellow LED per remote console that turns on
steady when a remote console has a fault. Green LED per remote console that
turns on steady when a remote console is active.
M
AIN
C
ONSOLE
F
AULT
.
Yellow LED that turns on steady when the main
(or primary operator) console has a fault.
AC P
OWER
.
Green LED that turns on steady when AC power is present.
G
ROUND
F
AULT
.
Yellow LED that turns on steady when a ground fault
exists in the system.
C
HARGER
F
AULT
.
Yellow LED turns on steady when the battery charger
voltage is too high or low.
B
ATTERY
F
AULT
.
Yellow LED turns on steady when battery voltage is too
low.
D
ATA
B
US
F
AULT
.
Yellow LED that turns on steady when the main and
remote console(s) cannot communicate.
NAC F
AULT
.
Yellow LED that turns on steady when the onboard NAC
wiring is open or short-circuited.
NAC A
CTIVE
.
Green LED that turns on steady when the NAC output is on.
S
YSTEM
T
ROUBLE
.
Yellow LED that turns on steady when any fault exists
in the system.
A
UDIO
R
ISER
F
AULT
.
Yellow LED that turns on steady when the audio
riser wiring is open or short-circuited.
Section 5 Periodic Testing and Maintenance
To ensure proper and reliable operation, system inspection and testing should
be scheduled monthly, or as required by NFPA 72 or local fire codes. A
qualified Service Representative should perform testing.
B
EFORE
T
ESTING
:
Notify fire department and/or central alarm receiving
station if alarm condition is transmitted. Notify facility personnel of the test so
alarm sounding devices are ignored during the test period.
A
FTER
T
ESTING
:
Notify all fire, central station, and/or building personnel
when testing is complete.
In the event of trouble, contact the local
Fire-Lite Service Representative.
Name: __________________________________________________
Address: ________________________________________________
Telephone Number: _______________________________________
Содержание ECC-50/100
Страница 83: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 83 Notes ...
Страница 95: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 95 Notes ...
Страница 102: ...102 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Notes ...
Страница 106: ...106 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Страница 108: ...108 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Страница 114: ...Cut along dotted line ...
Страница 116: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...