ENI7003R8 KO65 2013 

5. INSTALLATION AND WIRING

CAUTION 

INSTALLATION 

When Installing this Product… 

1.  Read these instructions carefully. Failure to follow 

them could damage the product or cause a 

hazardous condition. 

2.  Check the ratings given in the instructions and 

marked on the product to make sure the product 

is suitable for the application. 

3.  Installer must be a trained, experienced, flame 

safeguard service technician. 

4.  After installation is completed, check out the 

product operation as provided in these 

instructions. 

 

WARNING 

Fire or Explosion Hazard. 
Can cause property damage, 
severe injury, or death. 

Carefully follow safety requirements when installing a 
burner control. 

 

CAUTION 

Electrical Shock Hazard or Equipment/ 
Control Damage.   

Disconnect power supply before beginning installation, 

to avoid electrical shock or equipment damage.. 

 

IMPORTANT 

1. Wiring connections for the relay modules are 

unique;  refer to Fig. 3-2 or the appropriate 

Specifications for individual subbase wiring. 

2. Wiring must comply with all applicable codes, 

ordinances and regulations. 

3. Wiring must comply with NEC Class 1   

(Line Voltage) wiring. 

4. Loads connected to the DBC2000E must not 

exceed those listed on the relay module label or the 

Specifications; see Table 3. 

5. Limits and interlocks must be rated to 

simultaneously carry and break current to the 

ignition transformer and fuel valve(s).   

6.  All external timers must be listed or component 

recognized by authorities who have proper 

jurisdiction. 

 
 

7.  For on-off gas-fired systems, some authorities 

who have jurisdiction prohibit the wiring of any 

limit or operating contacts in series between the 

flame safeguard control and the main fuel 

valve(s). 

8.  Two UV flame detectors can be connected in 

parallel. 

9.  This equipment generates, uses and can radiate 

radio frequency energy and, if not installed and 

used in accordance with the instructions, can 

cause interference with radio communications. It 

has been tested and found to comply with the 

limits for a Class B computing device of Part 15 of 

FCC rules, which are designed to provide 

reasonable protection against such interference 

when operated in an industrial or commercial 

environment. Operation of this equipment in a 

residential area can cause interference, in which 

case, the users, at their own expense, may be 

required to take whatever measures are required 

to correct this interference. 

10. This digital apparatus complies with the 

requirements as stated in the EN298 standard. 

11. Do not install the Burner Controller under any 

circumstances in the following locations. 

 Where chemicals or corrosive gases are 

present, such as ammonia, sulfur, chlorine, 

ethylene compounds, acids, etc. 

 Install the relay module where the relative 

humidity never reaches the saturation point. 

The relay module is designed to operate in a 

maximum 85% relative humidity continuous, 

noncondensing, moisture environment. 

Condensing moisture can cause a safety 

shutdown or damage the device. 

 Where temperatures exceed the maximum 

specification for this device. 

 Where excessive continuous vibration exists. 

12. Do not bundle power wiring and high voltage 

ignition cable with the flame detector wiring, or run 

them in parallel within the same conduit. High 

voltage cables must be kept separated at least 10 

cm from the Burner Controller. 

13. Use proper grounding work in accordance with 

the engineering standards for electrical equipment 

14. Connect the high voltage cable of the ignition 

transformer properly to the ignition electrode. A 

poor connection can cause an electrical shock or 

damage the equipment. Additionally the ignition 

transformer must be properly grounded according 

the standards. 

Содержание DBC2000 Series

Страница 1: ...pment during start up of the burner Safe start check before and during pre purge Dual flame amplifier for UV IR or flame rod sensor Automatic recycle once per 24h of uninterrupted heat demand Frontal jack plug Ø 3 5mm to read the flame signal with a microampere meter An electrical sub base lock reset and safety limit terminals are swapped to avoid that a Standard model is used systems wired for an...

Страница 2: ...when no post purge feature is enabled terminal 12 jumpered to line voltage Sequence at flame failure immediate lock out Table 2a Sequence timing Enhanced and Ultimate Models Waiting for AFS Waiting for HF Pre purge Ignition Pilot only Main trial Main stabilization Post purge Flame failure response 300s max 300s max 35s 1 3s 5s 3s 2 4s 2 15s 3 1s max 1 Default pre purge time is 35s Other timings on...

Страница 3: ...rod or rectifying optical sensors C7012A G UV or IRD1020 1 IR 15m 14µA min 4µA max When using a flame rod the current on the flame jack plug is inverted See also Fig 4 2 Flame detector leads are colour coded The blue lead wire must be connected to the F terminal T23 and the white lead wire to the G terminal T24 The UV sensing tube is polarity sensitive Reversing the lead wires even momentarily wil...

Страница 4: ...of the device Therefore avoid touching the lead wires to avoid an electrical shock Reset switch When the DBC2000 is in Lockout condition press the internal or remote reset button one time to reset the DBC2000 and stop the alarm The reset button must be held for a minimum of 3 seconds If the heat demand is still present the DBC2000 will perform the start sequence normally when the fault condition h...

Страница 5: ...ENI7003R8 KO65 2013 5 4 DIMENSIONS Fig 1 External Dimensions in mm Fig 2 Mounting dimensions of sub base and terminal layout ...

Страница 6: ...n parallel 9 This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions can cause interference with radio communications It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated i...

Страница 7: ...o Terminal 7 and main valve 2 to Terminal 12 for the VPS function 3 When using Interrupted Pilot connect the pilot valve to Terminal 6 Connect the main valves to Terminal 7 Enhanced and Ultimate models connect main valve 1 to Terminal 7 and main valve 2 to Terminal 12 for the VPS function 4 When using direct ignition DBI jumper Terminals 15 and 22 And connect the Main DBI valves to Terminal 5 5 Wh...

Страница 8: ...or the Standard and Enhanced Ultimate models This is to prevent that a Standard model can be used by mistake in a system that is wired for an Enhanced or Ultimate model Fig 3 1 Terminal layout Fig 3 2 Example of wiring to external equipment see fig 3 3 for more ...

Страница 9: ...re examples of wiring to external equipment Fig 4 1 Wiring a flame detector CAUTION There is line voltage on flame sensor inputs Don t touch the lead wires of the UV detector or the flame sensing electrode to avoid an electrical shock ...

Страница 10: ...e flame sensor wiring whilst 1 Using a flame rod the multi meter will show the real flame current in µA 2 Using a UV sensor C7027 C7035 or C7044 the current in the sensor lead wires will be in the range of 20 25mA inverted values Fig 4 3 Measuring flame signal with multi meter µA range selection using a jack plug STD ENH Models flame detector select only ULT Model bus connector and address switche...

Страница 11: ...oes straight into running modulate after pilot stabilization STD model To enable DBI mode apply line voltage to terminal 22 on the wiring base Practically this means that a jumper is placed between terminals 1 L and 22 ENH ULT models To enable DBI mode make the correct DIP switch setting on the front of the DBC2000E SW2 DBI PI select Factory set to PI SW2 off See fig 4 5 to locate the DIP switches...

Страница 12: ...ve outputs are energized T5 and T6 FLAME ON When a flame is detected after the ignition trial has ended Safety1 the pilot stabilization time starts After completion of the pilot stabilization time the Main valves are energized T7 ON Note Enhanced Model also T12 ON The Main trial for ignition takes place Safety2 After completion of the main trial time Interrupted pilot valve is deenergized T5 OFF T...

Страница 13: ...ENI7003R8 KO65 2013 13 ...

Страница 14: ... If a non critical error is detected such as opening of the air flow switch during post purge DBC2000 holds the sequence during the lock out time allowing time for the error to rectify and then goes into lock out For all types of errors the status LEDs indicate the status information to the operator Fig 6 to Fig 13 show the sequence of DBC2000 in case of some error And Table 8 shows the status of ...

Страница 15: ...is present Pilot Ignition Air flow switch goes OFF Ignition failure flame signal is not present after ignition trial Pilot only Air flow switch goes OFF No flame signal Main ignition Air flow switch goes OFF No flame signal Main ignition Stabilization Air flow switch goes OFF No flame signal Run Air flow switch goes OFF No flame signal Post purge No power is supplied to Terminal 3 because of inter...

Страница 16: ...as described in the EC type examination certificate issued by DVGW CERT GmbH in Bonn with pin number 0085CM0138 in conformity with the essential requirements of the Low Voltage Directive 2006 95 EC based on EN 60730 2 5 in conformity with the essential requirements of the EMC Directive 2004 108 EC on immunity based on EN 298 immunity requirements Conformity with the essential requirements of the E...

Страница 17: ...g We cannot assume that the product can be safely used beyond the mentioned designed lifetime This lifetime is based on use of the control according manufacturer s instructions Regular inspection of the control by authorized personnel in accordance with guidelines of the appliance manufacturer is required After reaching the designed lifetime the product has to be replaced by authorized personnel N...

Страница 18: ...n examples Example 1 Calculation of the minimum test time per valve in a 2 threaded pipe train Pi 150 mbar Qm 60 dm 3 h Gas valves used 2 size with 0 5 meter pipe To be calculated Tp s Calculation From Table a 2 L 0 5m Vp 2 3 dm 3 2 x 150 x 2 3 Tp s 60 Using the formula above the minimum test time Tp 11 5s The DBC2000E2 must be set to 15s test time see page 11 Example 2 NOTE to allow a 3 valve con...

Страница 19: ...0 22 0 08 0 06 0 15 0 24 0 33 0 42 0 18 0 12 0 28 0 43 0 59 0 74 0 31 1 0 19 0 44 0 68 0 93 1 2 0 49 1 0 69 1 1 1 5 1 9 2 3 0 8 1 0 71 1 4 2 0 2 7 3 3 1 3 2 1 3 2 3 3 3 4 2 5 2 2 0 2 2 7 4 4 6 0 7 7 9 3 3 3 3 2 9 5 4 7 9 10 13 5 DN65 3 2 4 9 7 5 8 2 9 8 3 3 DN80 4 4 6 9 9 4 12 14 5 0 DN100 6 5 10 5 14 4 18 22 7 9 Threaded connections sizes in inches Flanged connections sizes in DN If L 0m it means...

Страница 20: ...ENI7003R8 KO65 2013 20 Page intentionally left empty ...

Страница 21: ...ENI7003R8 KO65 2013 21 Page intentionally left empty ...

Страница 22: ...ENI7003R8 KO65 2013 22 Page intentionally left empty ...

Страница 23: ...ENI7003R8 KO65 2013 23 Page intentionally left empty ...

Страница 24: ...ENI7003R8 KO65 2013 24 Honeywell Industrial Combustion Luchthavenlaan 16 1800 Vilvoorde Belgium http hic emea honeywell com ...

Отзывы: