background image

3

69-0446—2

Fig. 7—CT8602C heating/cooling circuit in a two
transformer (one for heating, one for cooling)
system with gas heat and electric cooling, RC
and R terminals. Remove factory-installed R-RC
jumper.

Setting and Adjustments

ADJUSTING CYCLE RATE

NOTE: MOST APPLICATIONS DO NOT REQUIRE A

CHANGE IN CYCLE RATE.

The room air temperature varies slightly from the com-

fort temperature setting with the cycling of the furnace or
air conditioner. The equipment cycles off and on as the
room temperature approaches the setpoint.

The cycle rate of this thermostat is set for heating at six

cycles per hour and for cooling at three cycles per hour as
shipped from the factory. The cooling cycle rate cannot be
adjusted. The heating cycle rate can be adjusted by turning
one or both cycle rate adjustment screws located on the
back of the thermostat. See Fig. 9. Back out the screw about
one-half to one turn, or turn in until tight.

ADAPTIVE INTELLIGENT RECOVERY™/
CONVENTIONAL RECOVERY

The thermostat is factory-set for Adaptive Intelligent

Recovery™, but can be converted to conventional recovery
using screw 3A on the back of the thermostat as indicated in
Fig. 9.

With Adaptive Intelligent Recovery™, the room reaches

the comfort temperature at the exact time programmed into
the thermostat. The control temperature increases gradu-
ally, and turns the equipment on and off several times to
reach the comfort temperature slowly and on time. There is
no wasted energy associated with rapid temperature changes
and temperature overshoot.

With conventional recovery, program the start time to

be earlier than the desired comfort time. It may require
some trial and error to arrive at the best starting time.

NOTE: If you adjust screw 3A for conventional recovery, an

indicator appears in the lower right corner of the thermo-
stat display as a reminder that the Adaptive Intelligent
Recovery™ feature is not active. (Fig. 10).

Fig. 10—Conventional recovery indicator.

SETTING TIME/TEMPERATURE

The display readout can be converted between a 12 and

24 hour clock or 

°

C and 

°

F using screws 2A and 2B as

indicated in Fig. 9.

INSTALLING BATTERIES

Power is supplied for the thermostat by three AA alka-

line batteries. Batteries are included with thermostat. Install
batteries in back of thermostat as shown in Fig. 11. The
display will flash 1:00 PM and room temperature.

When the batteries are going dead, the display will flash

REPL BAT. Set system switch to OFF. Remove the ther-
mostat from the wall and install three new AA alkaline
batteries. We recommend Energizer

®

 batteries. Change

L1 
(HOT)

L2

1

2

1

2

Y

RC

R

G

W

COOLING
CONTACTOR

24V

L1 
(HOT)
L2

1

24V

M118

HEATING
PRIMARY
CONTROL

FAN RELAY

WALLPLATE

POWER SUPPLY. PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

PRIMARY CONTROL SUCH AS GAS VALVE OR
ELECTRONIC IGNITION MODULE.

Fig. 8—CT8602C heating/cooling circuit in an oil
heating and electric cooling system. Heating
transformer is in oil primary, RC and R termi-
nals. Remove factory-installed R-RC jumper.

L2

L2

1

1

1

Y

RC

R

G

W

T

T

24V

M120

L1 
(HOT)

L1 
(HOT)

OIL PRIMARY

WALLPLATE

POWER SUPPLY. PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

COOLING
CONTACTOR

FAN RELAY

Fig. 9—Adjustments.

SYSTEM

GRAVITY

AIR/WATER

HOT

WATER

GAS/OIL

WARM AIR

ELECTRIC

WARM AIR

1A

OUT 1/2 

TO 1 TURN

OUT 1/2 

TO 1 TURN

OUT 1/2 

TO 1 TURN

OUT 1/2 

TO 1 TURN

1B

IN

IN

(FACTORY SETTING)

IN

IN

TIME/TEMP

DISPLAY

2A

2B

24 HR

IN

12 HR

o

o

C

F

OUT 1/2 

TO 1 TURN

OUT 1/2 

TO 1 TURN

IN

RECOVERY
SELECTION

ADAPTIVE

INTELLIGENT ™

CONVENTIONAL

3A

IN

(FACTORY SETTING)

OUT 1/2 TO 1 TURN

M8857

3A 1A 1B

2A 2B

PM

SET
PT

TUE

LEAVE

INDICATES 
THERMOSTAT IS SET FOR 
CONVENTIONAL RECOVERY

M8878

Содержание CT8602C

Страница 1: ...prevent drafts from affecting thermo stat operation LOCATION Install thermostat and wallplate about 5 ft 1 5m above the floor in an area with good air circulation at room temperature Do not install the thermostat where it may be affected by drafts or dead spots behind doors in corners or under cabinets hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unhe...

Страница 2: ...event electrical shock or equipment damage The shape of the terminal barrier permits insertion of straight or conventional wraparound wiring connections Either method is acceptable Refer to Table 1 and Fig 4 through 8 for wiring guide lines NOTE Keep all wiring restricted to ribbed area surrounding terminals Fig 3 to assure thermostat wallplate contact TABLE 1 TERMINAL CROSS REFERENCE FOR STRAIGHT...

Страница 3: ...onalrecovery an indicator appears in the lower right corner of the thermo stat display as a reminder that the Adaptive Intelligent Recovery feature is not active Fig 10 Fig 10 Conventional recovery indicator SETTING TIME TEMPERATURE The display readout can be converted between a 12 and 24 hour clock or C and F using screws 2A and 2B as indicated in Fig 9 INSTALLING BATTERIES Power is supplied for ...

Страница 4: ...splay will read 1 00 PM and room tempera ture It will go off for a few seconds then begin to flash on and off Press Press TIME or to set the current time Press Press to set the current day Each press of the DAY KEY advances the display one day If the display does not come on Check mounting of thermostat to wallplate If loose or misaligned remove thermostat and reinstall on wallplate making sure it...

Страница 5: ...about 10 F 6 C below room tempera ture The heating equipment should shut off COOLING CAUTION Do not operate cooling if outdoor temperature is below 50 F 10 C Refer to manufacturer s rec ommendations NOTE When cooling setting is changed thermostat will wait up to five minutes before turning on the air condi tioner This delay protects the compressor Move the system switch to COOL and the fan switch ...

Страница 6: ...nk 04 Blank 01 Blank 00 Blank CHECK EACH POSITION 12 See note A OFF 08 Blank 13 Microprocessor mask no and revision no 09 Blank 14 Blank HEAT 14 Heating on 1 14 Heating off OFF 10 Blank 11 Normal operating display CHANGE TO LAST PERIOD SKIP NEXT PERIOD PRESENT SETTING PRESENT SETTING PRESENT SETTING WARMER COOLER AHEAD RETURN LEAVE BACK WAKE SLEEP DAY SET HEAT COOL SET PRESENT DAY TIME SET PRESENT...

Отзывы: