SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES

63-2651—1

4

SAFETY

WARNING

For CSS-O,C ensure that all power sources are 

disconnected and locked out before installation as 

severe injury or death may result from electrical 

shock due to contact with high voltage wires.

CAUTION

This product is not intended to be used for life or 

safety applications.

CAUTION

This product is not intended for use in any 

hazardous or classified locations.

INSTALLATION

Make sure that all installations are in compliance with all 

national and local electrical codes. Only qualified individuals 

that are familiar with codes, standards and proper safety 

procedures for high voltage installations should attempt 

installation. The current switches will not require external 

power, since the power for the current switch is induced from 

the conductor being monitored.

WARNING

Never rely on the LEDs to determine whether 

power is present at the current switch. The red 

LED will indicate whether the current is above the 

adjustable trip point. The green LED will indicate 

whether the current is below the adjustable trip 

point.

IMPORTANT

The current switch should be used on insulated con-

ductors only!

The current switch may be mounted in any position using the 

(2) #8 x 3/4 in. (19 mm) Tek screws and the mounting holes in 

the base or snapped directly on to the 1-3/8 in. (35 mm) DIN 

rail (See Figures 3 and 4). Leave a minimum distance of 1 in. 

(25 mm) between the current switch and any other magnetic 

devices, such as contactors and transformers.

For applications in which the normal operating current is 

below the 0.8/2.0 Amps trip point (See Fig. 5), the conductor 

being monitored may be looped through the sensor 6/12 times 

giving you a total operating current of 6/12 times the original 

current.

Example: 

A small fan operating at 0.2 Amps can be wrapped through 

the sensor 6 times to give you a total operating current of 

1.2 Amps flowing through the CSS-O-A300-001. Another 

option is to use CSS-O-A200-001.

A small fan operating at 0.2 Amps can be wrapped through 

the sensor 16 times to give you a total operating current of 

3.2 Amps flowing through the CSP-O-A300-001. Another 

option is to use the CSP-O-A200-001.

Fig. 3. Sensor placed on DIN rail

Fig. 4. Sensor removed from DIN rail

Fig. 5. Wires through sensors

C

R

U

L

U

S

3X

M25289

3X

M25290

C

R

U

L

U

S

M25291

U

R

C

L

US

U

R

C

L

US

Содержание CSS-O-A300-001

Страница 1: ... less servicing than differential pressure switches flow switches and paddle wheels These current switches should be used in applications in which a current switch with adjustable trip point is required A current switch can be used to monitor fan and pump status motors compressors and electrical equipment for proper operation A change in the operating current may indicate motor failure belt loss s...

Страница 2: ...t See Table 1 Hysteresis Dead Band 10 Setpoint typical Status Indication Red LED Above Trip Point Green LED Below Trip Point Aperture Hole Size 3 4 in 19 mm Accepts up to 350 MCM 17 3 mm cables Dimensions See Figures 1 and 2 DIN Rail Size 1 3 8 in 35 mm Unit Weight CSS 0 21 lb 0 1 kg CSP 0 23 lb 0 1 kg Enclosure Rating Color UL94 5VB Burgundy Operating Temperature Range 5 to 104 F 15 to 40 C Opera...

Страница 3: ...RMINAL BLOCK 13 64 5 TYP ON TRIP 2 27 32 72 M23581A 3 3 8 86 1 3 8 35 9 64 4 2 17 64 58 63 64 25 OUTPUT 0 3A 200 VDC VAC ADJ TRIP TRIP ON ABOVE TRIP POINT TRIP OFF ADJ RANGE 0 8 250A FRONT VIEW RIGHT SIDE VIEW LEFT SIDE VIEW TOP VIEW M23580A ADJ TRIP Adj Range 2 0 250A TRIP ON Above Trip Point Output 0 3A 200 VDC VAC ON OFF TRIP TRIP 1 2 13 2 27 32 72 7 32 6 TYP 3 21 64 85 1 3 8 35 9 64 4 3 4 19 4...

Страница 4: ...is below the adjustable trip point IMPORTANT The current switch should be used on insulated con ductors only The current switch may be mounted in any position using the 2 8 x 3 4 in 19 mm Tek screws and the mounting holes in the base or snapped directly on to the 1 3 8 in 35 mm DIN rail See Figures 3 and 4 Leave a minimum distance of 1 in 25 mm between the current switch and any other magnetic dev...

Страница 5: ...etween pole pieces Visually check the mating parts of the core before closing the current sensor Fig 7 Opening sensor by hand Fig 8 Opening with a screwdriver Wiring Honeywell recommends the use of a 2 conductor 16 to 22 AWG 1 3 to 0 3 mm2 shielded cable or twisted wire copper wire only for all current switch output applications A maximum wire length of less than 98 4 feet 30 meters should be used...

Страница 6: ... M25302 RELAY CONDITIONER 24 VAC COIL 120 VAC LINE DI STATUS M23933 DDC CONTROLLER DO RELAY COIL OR CONTACTOR 24 VAC COIL TRANSFORMER Problem Solution Red LED is on but the current switch didn t activate Disconnect the wires from the current switch output Measure the resistance across the contacts with an Ohmmeter See Table 2 below for resistance readings for a good unit Red LED didn t turn on and...

Страница 7: ...SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT STATUS SWITCHES 7 63 2651 1 ...

Страница 8: ...ITCHES U S Registered Trademark 2007 Honeywell International Inc 63 2651 1 C H Rev 06 07 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising ou...

Отзывы: