SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES

5

63-2651—1

WARNING

The secondary of the 5 amps current transformer 

must be shorted together before the power may be 

turned on to the monitored device.

For applications in which the normal operating current is 

greater than 250 Amps or for conductor diameters larger that 

3/4 in. (19 mm) in diameter, and external 5 Amps Current 

Transformer (C.T.) must be used as shown in Fig. 6.

Fig. 6. Current transformer

Latch Operation

Pressing down on the two (2) side tabs and swinging the cover 

open opens the split core current switch as shown in Fig. 7. 

Lifting up the latch with a flat-tip screwdriver as shown in Fig. 8 

can also open the unit. Press down firmly on the cover to close 

the current switch. An audible “

click

” will be heard as the tab 

slides over the tongue on the base.

CAUTION

Mating surfaces of the magnetic core are exposed 

when the sensor is open. Silicone grease, present 

on the cores to prevent rust, can capture grit and 

dirt if care is not exercised. Operation can be 

impaired if anything prevents good contact 

between pole pieces. Visually check the mating 

parts of the core before closing the current sensor.

Fig. 7. Opening sensor by hand

Fig. 8. Opening with a screwdriver

Wiring

Honeywell recommends the use of a 2 conductor 16 to 

22 AWG (1.3 to 0.3 mm

2

) shielded cable or twisted wire, 

copper wire only, for all current switch output applications. A 

maximum wire length of less than 98.4 feet (30 meters) should 

be used between the current switches and the Building 

Management System or controller.

NOTE: When using a shielded cable, be sure to connect only 

(1) end of the shield to ground at the controller. Con-

necting both ends of the shield to the ground may 

cause a ground loop.

When removing the shield from the sensor end, make sure to 

properly trim the shield so as to prevent any chance of 

shorting. The current switch output terminals represent a solid-

state switch for controlling AC and DC loads and is not polarity 

sensitive. The recommended torque to be used on the terminal 

block connections is 5.93 in-lbs. (0.67 Nm). The aperture (hole) 

size of the current switch is 3/4 in. (19 mm) and will accept a 

EXAMPLE:  FOR CURRENTS UP TO 600 AMPS, USE A 600:5 RATIO C.T.

 AS 

SHOWN. 

INSULATED  

       CONDUCTOR

600:5 RATIO 5A C.T. 

WIRE NUT 

M25295A

C

U

R

L

US

C

US

R

U

L

M25298

M25299

C

US

R

U

L

Содержание CSS-O-A300-001

Страница 1: ... less servicing than differential pressure switches flow switches and paddle wheels These current switches should be used in applications in which a current switch with adjustable trip point is required A current switch can be used to monitor fan and pump status motors compressors and electrical equipment for proper operation A change in the operating current may indicate motor failure belt loss s...

Страница 2: ...t See Table 1 Hysteresis Dead Band 10 Setpoint typical Status Indication Red LED Above Trip Point Green LED Below Trip Point Aperture Hole Size 3 4 in 19 mm Accepts up to 350 MCM 17 3 mm cables Dimensions See Figures 1 and 2 DIN Rail Size 1 3 8 in 35 mm Unit Weight CSS 0 21 lb 0 1 kg CSP 0 23 lb 0 1 kg Enclosure Rating Color UL94 5VB Burgundy Operating Temperature Range 5 to 104 F 15 to 40 C Opera...

Страница 3: ...RMINAL BLOCK 13 64 5 TYP ON TRIP 2 27 32 72 M23581A 3 3 8 86 1 3 8 35 9 64 4 2 17 64 58 63 64 25 OUTPUT 0 3A 200 VDC VAC ADJ TRIP TRIP ON ABOVE TRIP POINT TRIP OFF ADJ RANGE 0 8 250A FRONT VIEW RIGHT SIDE VIEW LEFT SIDE VIEW TOP VIEW M23580A ADJ TRIP Adj Range 2 0 250A TRIP ON Above Trip Point Output 0 3A 200 VDC VAC ON OFF TRIP TRIP 1 2 13 2 27 32 72 7 32 6 TYP 3 21 64 85 1 3 8 35 9 64 4 3 4 19 4...

Страница 4: ...is below the adjustable trip point IMPORTANT The current switch should be used on insulated con ductors only The current switch may be mounted in any position using the 2 8 x 3 4 in 19 mm Tek screws and the mounting holes in the base or snapped directly on to the 1 3 8 in 35 mm DIN rail See Figures 3 and 4 Leave a minimum distance of 1 in 25 mm between the current switch and any other magnetic dev...

Страница 5: ...etween pole pieces Visually check the mating parts of the core before closing the current sensor Fig 7 Opening sensor by hand Fig 8 Opening with a screwdriver Wiring Honeywell recommends the use of a 2 conductor 16 to 22 AWG 1 3 to 0 3 mm2 shielded cable or twisted wire copper wire only for all current switch output applications A maximum wire length of less than 98 4 feet 30 meters should be used...

Страница 6: ... M25302 RELAY CONDITIONER 24 VAC COIL 120 VAC LINE DI STATUS M23933 DDC CONTROLLER DO RELAY COIL OR CONTACTOR 24 VAC COIL TRANSFORMER Problem Solution Red LED is on but the current switch didn t activate Disconnect the wires from the current switch output Measure the resistance across the contacts with an Ohmmeter See Table 2 below for resistance readings for a good unit Red LED didn t turn on and...

Страница 7: ...SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT STATUS SWITCHES 7 63 2651 1 ...

Страница 8: ...ITCHES U S Registered Trademark 2007 Honeywell International Inc 63 2651 1 C H Rev 06 07 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising ou...

Отзывы: