Honeywell CSS-O-A300-001 Скачать руководство пользователя страница 2

SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES

63-2651—1

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE

®

 wholesaler or distributor, refer to the 

TRADELINE

®

 Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2.

Honeywell Customer Care

1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

Sensor Power: 

Induced from monitored conductor

Amperage Rating: 

0 to 200 Amps and 0 to 250 Amps 

(See Table 1)

Operating Frequency Range: 

40 Hz to 1 kHz

Isolation Voltage: 

2220 Vac

Max Sensing Current Voltage: 

600 Vac

Output Switch Rating:

CSS-O; CSP-O: 0.3 Amps @ 200 Vac/Vdc

CSS-C; CSP-C: 0.15 Amps @ 300 Vac/Vdc

Adjustable Trip Point (Setpoint): 

See Table 1

Hysteresis (Dead Band): 

10% Setpoint, typical

Status Indication:

Red LED - Above Trip Point

Green LED - Below Trip Point

Aperture (Hole) Size: 

3/4 in. (19 mm), Accepts up to 

350 MCM (17.3 mm) cables

Dimensions: 

See Figures 1 and 2

DIN Rail Size: 

1-3/8 in. (35 mm)

Unit Weight:

CSS: 0.21 lb (0.1 kg)

CSP: 0.23 lb (0.1 kg)

Enclosure Rating/Color: 

UL94-5VB/Burgundy

Operating Temperature Range: 

5° to 104° F (-15° to 40° C)

Operating RH Range: 

0 to 95% RH, non-condensing

Agency Approvals:

CE, UL

Environmental Compliance: 

RoHS-Directive 2002/95/EC

WEEE-Directive 2002/96/EC

NOTE: DO NOT use the LED’s to indicate whether the 

sensors have power applied to them.

Table 1. Operating Specifications

Product Number Core Type

Normal 

Position

Adjustable Trip 

Point

Output Switch 

Rating

Max. Current 

Cont.

Max. Current 

for 6 secs.

Max. Current 

for 1 sec.

CSS-O-A300-001

Solid

N.O.

1.0-250 Amps

0.30 Amps @ 

200 Vac/Vdc

250 Amps

500 Amps

1,000 Amps

CSS-O-A200-001

Solid

N.O.

0.5-250 Amps

0.30 Amps @ 

200 Vac/Vdc

250 Amps

500 Amps

1,000 Amps

CSS-C-A300-001

Solid

N.C.

1.0-250 Amps

0.15 Amps @ 

300 Vac/Vdc

250 Amps

500 Amps

1,000 Amps

CSP-O-A300-001

Split

N.O.

3.0-200 Amps

0.30 Amps @ 

200 Vac/Vdc

200 Amps

400 Amps

800 Amps

CSP-O-A200-001

Split

N.O.

2.0-200 Amps

0.30 Amps @ 

200 Vac/Vdc

200 Amps

400 Amps

800 Amps

CSP-C-A300-001

Split

N.C.

3.0-250 Amps

0.15 Amps @ 

300 Vac/Vdc

250 Amps

500 Amps

1,000 Amps

CSP-C-A200-001

Split

N.C.

2.5-250 Amps

0.15 Amps @ 

300 Vac/Vdc

250 Amps

500 Amps

1,000 Amps

Содержание CSS-O-A300-001

Страница 1: ... less servicing than differential pressure switches flow switches and paddle wheels These current switches should be used in applications in which a current switch with adjustable trip point is required A current switch can be used to monitor fan and pump status motors compressors and electrical equipment for proper operation A change in the operating current may indicate motor failure belt loss s...

Страница 2: ...t See Table 1 Hysteresis Dead Band 10 Setpoint typical Status Indication Red LED Above Trip Point Green LED Below Trip Point Aperture Hole Size 3 4 in 19 mm Accepts up to 350 MCM 17 3 mm cables Dimensions See Figures 1 and 2 DIN Rail Size 1 3 8 in 35 mm Unit Weight CSS 0 21 lb 0 1 kg CSP 0 23 lb 0 1 kg Enclosure Rating Color UL94 5VB Burgundy Operating Temperature Range 5 to 104 F 15 to 40 C Opera...

Страница 3: ...RMINAL BLOCK 13 64 5 TYP ON TRIP 2 27 32 72 M23581A 3 3 8 86 1 3 8 35 9 64 4 2 17 64 58 63 64 25 OUTPUT 0 3A 200 VDC VAC ADJ TRIP TRIP ON ABOVE TRIP POINT TRIP OFF ADJ RANGE 0 8 250A FRONT VIEW RIGHT SIDE VIEW LEFT SIDE VIEW TOP VIEW M23580A ADJ TRIP Adj Range 2 0 250A TRIP ON Above Trip Point Output 0 3A 200 VDC VAC ON OFF TRIP TRIP 1 2 13 2 27 32 72 7 32 6 TYP 3 21 64 85 1 3 8 35 9 64 4 3 4 19 4...

Страница 4: ...is below the adjustable trip point IMPORTANT The current switch should be used on insulated con ductors only The current switch may be mounted in any position using the 2 8 x 3 4 in 19 mm Tek screws and the mounting holes in the base or snapped directly on to the 1 3 8 in 35 mm DIN rail See Figures 3 and 4 Leave a minimum distance of 1 in 25 mm between the current switch and any other magnetic dev...

Страница 5: ...etween pole pieces Visually check the mating parts of the core before closing the current sensor Fig 7 Opening sensor by hand Fig 8 Opening with a screwdriver Wiring Honeywell recommends the use of a 2 conductor 16 to 22 AWG 1 3 to 0 3 mm2 shielded cable or twisted wire copper wire only for all current switch output applications A maximum wire length of less than 98 4 feet 30 meters should be used...

Страница 6: ... M25302 RELAY CONDITIONER 24 VAC COIL 120 VAC LINE DI STATUS M23933 DDC CONTROLLER DO RELAY COIL OR CONTACTOR 24 VAC COIL TRANSFORMER Problem Solution Red LED is on but the current switch didn t activate Disconnect the wires from the current switch output Measure the resistance across the contacts with an Ohmmeter See Table 2 below for resistance readings for a good unit Red LED didn t turn on and...

Страница 7: ...SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT STATUS SWITCHES 7 63 2651 1 ...

Страница 8: ...ITCHES U S Registered Trademark 2007 Honeywell International Inc 63 2651 1 C H Rev 06 07 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising ou...

Отзывы: