S7999 CONTROLINKS™ DISPLAY MODULE

9

65-0262

a

 If XmA Hold is configured as “None”, temperature may show other values outside the -40°F to +1400°F range for S7999 software builds prior to 

2007.

b

 UNKNOWN will be displayed for R7999 software builds prior to 170.

Prog Stop        FGR

Programmed stop of actuator.

00% to 100

F2(1) Idle Stop

Current inactive fuel

00% to 100

Either F2 or F1 will be shown, 

whichever is the inactive fuel.

Config Settings

Top level prompt for 
configuration parameter 
settings.

Press the Change Level button to 

enter the submenu.

XmA Hold

Temperature Sensor hold

None
LOP
FGR
LOP + FGR

Indicates if auxiliary temperature 
sensor is used  and type of hold: 
lightoff point, FGR closed, or both.

XmA Minimum

Temperature Sensor minimum 
input

-40°F to +1400°F

a

N/A

Not Applicable (N/A) is indicated if 
XmA Hold is configured as None.

XmA Maximum

Temperature Sensor maximum 
input

-40°F to +1400°F

a

N/A

Not Applicable (N/A) is indicated if 
XmA Hold is configured as None.

XmA Enforce

Temperature Sensor setting to 
enforce XmA Hold condition.

-40°F to +1400°F

a

N/A

Not Applicable (N/A) is indicated if 
XmA Hold is configured as None.

XmA Release

Temperature Sensor setting to 
release the XmA Hold 
condition.

-40°F to +1400°F

a

N/A

Not Applicable (N/A) is indicated if 
XmA Hold is configured as None.

Purge FGR

FGR Actuator position during 
PURGE

On curve
Closed

b

Man Limit

Manual Limit configuration 
setting.

Enabled
Disabled

b

Indicates if the R7999 was 

commissioned to enable the Manual 

Potentiometer to limit the maximum 

firing rate.

CL Rev.          M.NvV  BBB

ControLinks™ R7999 software 
revision and build code

M = major; N = minor; V = version; 

BBB = build code.

Display Rev.               BBB

Display S7999 Software Build 
Code

BBB = build code.

DiagCode

Diagnostic Codes

Possibly useful for debugging display 

problems.

Fault History
(Six most recent faults)

Top level prompt for fault 
history information.

Press the Change Level button to 

enter the submenu.

*Fault Code nn*                          Fault Code Number

0-94

For fault descriptions, see form 65-

0238, R7999A,B ControLinks™ 

Controller.

*Fault Message*

Description of the fault code.

*In (state)*

State in which the fault 
occurred.

*Fault Cycle nnn*

Cycle when fault occurred.

0 to 999999

Line 2 Legend

Top level prompt for on-line 
help to describe letter codes 
on the second line of the main  
display.

The Line 2 legend submenu describes each of the letter codes 
that may appear on the second line of the main display. Each 
item in this submenu shows a flashing letter code on the second 
line, in the position where it normally appears on the main 
display, along with a description of the letter code in the first line 
of the display.

Table 3. Selectable Messages.

Selectable Message/Display

Description

Possible States/Range 

Comments

Содержание ControLinks S7999

Страница 1: ...ating Status Source of demand control Actuator positions Hold status Total cycles Total hours of operation Run time Fault history of six most recent faults Fault code Fault message Cycles at time of fault Diagnostic information Input Output status Demand control input and position Fuel selection Fuel position Motor settings Light off position of fuel air and FGR purge position of fuel air and FGR ...

Страница 2: ...ating 40 F 40 C to 140 F 60 C Storage 60 F 51 C to 150 F 66 C Humidity 85 percent relative humidity continuous noncondensing Vibration 0 5G environment Mechanical Dimensions See Fig 1 Weight 4 ounces 124 grams unpacked Display 40 character 2 rows by 20 columns Approvals Underwriters Laboratories Inc Component Recognized IRI Acceptable Federal Communications Commission Part 15 Class B emissions EN6...

Страница 3: ...r reaches the saturation point The S7999 ControLinks is designed to operate in a maximum 85 RH continuous noncondensing moisture environment Vibration Do not install the S7999 where it can be subjected to vibration in excess of 0 5G continuous maximum vibration Weather The S7999 is not designed to be weather tight If installed outdoors the S7999 must be protected by an approved weather tight enclo...

Страница 4: ...ting a Display Module 1 Do not route the Display Module wiring in conduits that carry line voltage circuits 2 Avoid routing the Display Module wiring close to ignition transformer leadwires 3 Route the Display Module wiring outside of conduit if properly supported and protected from damage 7 Maximum wire lengths a DM The maximum length interconnecting wire is 4000 ft 1219m 8 Install all electrical...

Страница 5: ...he Manual Potentiometer input Manu however the LF input is on so the normal rate request is overridden and the system is firing at the Lightoff rate Rate The RATE item shown in Fig 5 is the current firing rate request that is driving the R7999 Possible values are shown below using dashes to represent the positions where digits would appear C shows the CmA input current requested rate as a percenta...

Страница 6: ...nd line of the display however when the display is first powered up this area is used to indicate the progress of the initialization of the S7999 display itself Fig 6 Display module LINE2 area during display initialization After the display is first energized or connected it must wait to receive 15 different configuration information records from the R7999 before it is fully functional Although th...

Страница 7: ...entifier for the submenu to appear in the LINE2 area in the top right corner of the display Each submenu item has a left pointing arrowhead to indicate that the change level pushbutton may be used to exit the submenu and return to the top level menu In the top level menu the LINE2 area is blank The toggle button cycles the second line of the display between the main display and whichever second li...

Страница 8: ... Input On Off ON indicates Manual is selected OFF indicates Auto is selected FSelect1 T5 Fuel 1 Input On Off FSelect2 T6 Fuel 2 Input On Off Alarm T7 Alarm Output On Off HFP T8 High Fire Proven Output On Off LFP T9 Low Fire Proven Output On Off HF T10 High Fire Input On Off MV T11 Main Valve Input On Off LF T12 Low Fire Input On Off LCI T13 Limit Control Input On Off LCO T14 Limit Control Output O...

Страница 9: ... XmA Hold is configured as None Purge FGR FGR Actuator position during PURGE On curve Closedb Man Limit Manual Limit configuration setting Enabled Disabledb Indicates if the R7999 was commissioned to enable the Manual Potentiometer to limit the maximum firing rate CL Rev M NvV BBB ControLinks R7999 software revision and build code M major N minor V version BBB build code Display Rev BBB Display S7...

Страница 10: ... Fig 7 through 9 show a lockout condition that illustrates the three display module messages Pressing the scroll or toggle buttons will suspend the cycling of the fault messages until either the buttons are used to return to the main display or 60 seconds elapse with no buttons pressed Special Condition Displays Seven special condition display can be shown that preclude normal system operation as ...

Страница 11: ...NKS DISPLAY MODULE 11 65 0262 Fault Blink Codes and Actions The Fault Blink Codes and respective corrective actions are found in form 65 0238 Fig 10 Display module flush mounting outline M5082B 1 8 in DIA 2 3 175 mm ...

Страница 12: ... Control Home and Building Control Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: