S7999 CONTROLINKS™ DISPLAY MODULE

65-0262

8

Table 3. Selectable Messages.

Selectable Message/Display

Description

Possible States/Range 

Comments

Total Cycles

Total number of equipment 
operating cycles

0 to 999999

Cycle will be updated each time main 
valve is energized.

Run Time

Total number of equipment 
operating time (hours:minutes)

0:00 to 999999:00

Hours:minutes will be updated while 
main valve input is energized.

Inputs/Outputs:

Top-level prompt for diagnostic 
information.

Press the Change Level button to 
enter the submenu.

CmA

Controller Input

4.0 to 20.0 mA

Firing Rate input.

ManPot

Manual Potentiometer

4.0 to 20.0 mA

Manual control potentiometer.

XmA

Auxiliary Input

4.0 to 20.0 mA

Temperature sensor input current.

XmA Temp

Auxiliary  Input

-40°F to +1400°F

Temperature sensor input in degrees 
Fahrenheit.

Current Fuel

Current fuel selected.

Fuel 1 or Fuel 2

The fuel selection as determined at 
ControLinks™ System startup.

F2(1) Position

Fuel actuator position for 
currently inactive fuel.

00% to 100%.

Either F2 or F1 will be shown, 
whichever is the inactive fuel.

Manual          T4

Manual/Auto Input

On/Off

ON indicates Manual is selected; OFF 
indicates Auto is selected.

FSelect1       T5

Fuel 1 Input

On/Off

FSelect2       T6

Fuel 2 Input

On/Off

Alarm            T7

Alarm Output

On/Off

HFP               T8

High Fire Proven Output

On/Off

LFP               T9

Low Fire Proven Output

On/Off

HF                 T10

High Fire Input

On/Off

MV                 T11

Main Valve Input

On/Off

LF                 T12

Low Fire Input

On/Off

LCI                T13

Limit/Control Input

On/Off

LCO              T14

Limit/Control Output

On/Off

Motor Settings

Top level prompt for motor 
setting information.

Press the Change Level button to 
enter the submenu.

Lightoff           F1(2)

Indicates fuel actuator 
programmed position during 
Lightoff.

00% to 100%

Either F1 or F2 will be shown, 
whichever is the active fuel.

Lightoff           Air

Indicates air actuator 
programmed position during 
Lightoff.

00% to 100%

Lightoff           FGR 

Indicates FGR actuator 
programmed position during 
Lightoff.

00% to 100%

Purge             F1(2)

Indicates fuel actuator 
programmed position during 
Purge.

00% to 100% 

Either F1 or F2 will be shown, 
whichever is the active fuel.

Purge                Air

Indicates air actuator 
programmed position during 
Purge.

00% to 100%

Purge               FGR

Indicates FGR actuator 
programmed position during 
Purge.

00% to 100%

Prog Stop        F1(2)

Programmed stop of actuator.

00% to 100

Either F1 or F2 will be shown, 

whichever is the active fuel.

Prog Stop        Air

Programmed stop of actuator.

00% to 100

Содержание ControLinks S7999

Страница 1: ...ating Status Source of demand control Actuator positions Hold status Total cycles Total hours of operation Run time Fault history of six most recent faults Fault code Fault message Cycles at time of fault Diagnostic information Input Output status Demand control input and position Fuel selection Fuel position Motor settings Light off position of fuel air and FGR purge position of fuel air and FGR ...

Страница 2: ...ating 40 F 40 C to 140 F 60 C Storage 60 F 51 C to 150 F 66 C Humidity 85 percent relative humidity continuous noncondensing Vibration 0 5G environment Mechanical Dimensions See Fig 1 Weight 4 ounces 124 grams unpacked Display 40 character 2 rows by 20 columns Approvals Underwriters Laboratories Inc Component Recognized IRI Acceptable Federal Communications Commission Part 15 Class B emissions EN6...

Страница 3: ...r reaches the saturation point The S7999 ControLinks is designed to operate in a maximum 85 RH continuous noncondensing moisture environment Vibration Do not install the S7999 where it can be subjected to vibration in excess of 0 5G continuous maximum vibration Weather The S7999 is not designed to be weather tight If installed outdoors the S7999 must be protected by an approved weather tight enclo...

Страница 4: ...ting a Display Module 1 Do not route the Display Module wiring in conduits that carry line voltage circuits 2 Avoid routing the Display Module wiring close to ignition transformer leadwires 3 Route the Display Module wiring outside of conduit if properly supported and protected from damage 7 Maximum wire lengths a DM The maximum length interconnecting wire is 4000 ft 1219m 8 Install all electrical...

Страница 5: ...he Manual Potentiometer input Manu however the LF input is on so the normal rate request is overridden and the system is firing at the Lightoff rate Rate The RATE item shown in Fig 5 is the current firing rate request that is driving the R7999 Possible values are shown below using dashes to represent the positions where digits would appear C shows the CmA input current requested rate as a percenta...

Страница 6: ...nd line of the display however when the display is first powered up this area is used to indicate the progress of the initialization of the S7999 display itself Fig 6 Display module LINE2 area during display initialization After the display is first energized or connected it must wait to receive 15 different configuration information records from the R7999 before it is fully functional Although th...

Страница 7: ...entifier for the submenu to appear in the LINE2 area in the top right corner of the display Each submenu item has a left pointing arrowhead to indicate that the change level pushbutton may be used to exit the submenu and return to the top level menu In the top level menu the LINE2 area is blank The toggle button cycles the second line of the display between the main display and whichever second li...

Страница 8: ... Input On Off ON indicates Manual is selected OFF indicates Auto is selected FSelect1 T5 Fuel 1 Input On Off FSelect2 T6 Fuel 2 Input On Off Alarm T7 Alarm Output On Off HFP T8 High Fire Proven Output On Off LFP T9 Low Fire Proven Output On Off HF T10 High Fire Input On Off MV T11 Main Valve Input On Off LF T12 Low Fire Input On Off LCI T13 Limit Control Input On Off LCO T14 Limit Control Output O...

Страница 9: ... XmA Hold is configured as None Purge FGR FGR Actuator position during PURGE On curve Closedb Man Limit Manual Limit configuration setting Enabled Disabledb Indicates if the R7999 was commissioned to enable the Manual Potentiometer to limit the maximum firing rate CL Rev M NvV BBB ControLinks R7999 software revision and build code M major N minor V version BBB build code Display Rev BBB Display S7...

Страница 10: ... Fig 7 through 9 show a lockout condition that illustrates the three display module messages Pressing the scroll or toggle buttons will suspend the cycling of the fault messages until either the buttons are used to return to the main display or 60 seconds elapse with no buttons pressed Special Condition Displays Seven special condition display can be shown that preclude normal system operation as ...

Страница 11: ...NKS DISPLAY MODULE 11 65 0262 Fault Blink Codes and Actions The Fault Blink Codes and respective corrective actions are found in form 65 0238 Fig 10 Display module flush mounting outline M5082B 1 8 in DIA 2 3 175 mm ...

Страница 12: ... Control Home and Building Control Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: