S7999 CONTROLINKS™ DISPLAY MODULE

7

65-0262

Air-Fuel-FGR

This area of the display shows the current positions of the 
actuators as a percentage of their closed-to-open range, from 
“00%” to “100%”.

A--%—shows the air actuator position.

F--%—shows the position of the currently selected fuel 
actuator.

R--% or H--%—shows the position of the FGR actuator. If the 
system does not included an FGR actuator, then this item is 
blank. The “H” indicates that an FGR hold (an option enabled 
during commissioning) is currently active because the R7999 
XmA input is (or has been) below the Enforce threshold and 
has not yet crossed the Release threshold, whereas “R” 
indicates normal, no-hold FGR operation.

Pushbuttons

The two lefthand (SCROLL) pushbuttons scroll the second 
line up and down through a list of menu items. 

The third pushbutton (

) provides a toggle function.

 The fourth pushbutton (

) provides a change level 

function.

In the top-level menu, an item that provides access to a 
submenu is indicated by a right-pointing arrowhead ( ) 
following the submenu description (Inputs/Outputs, Motor 
Settings, Configuration Settings, Fault History and Line 2 
Legend). Pressing the change level button when a submenu 
description is displayed will shown the first item of submenu 
information and will cause an identifier for the submenu to 
appear in the LINE2 area in the top right corner of the display. 
Each submenu item has a left-pointing arrowhead (

 ) to 

indicate that the change level pushbutton may be used to exit 
the submenu and return to the top-level menu. In the top-level 
menu, the LINE2 area is blank.

The toggle button cycles the second line of the display 
between the main display and whichever second line was 
most recently shown by using the scroll and change level 
pushbuttons. This provides a way to quickly return to the main 
display. The toggle button may also be used to compare the 
main display to some other item by quickly toggling between 
them.

NOTE:

If the display has just been powered up, or if the 
scroll buttons have been used to return to the main 
display, then there is no other second line as 
described above for the toggle pushbutton. In this 
case the Run Time item from the top-level menu is 
used.

The top-level menu and each of the submenus wrap around, 
that is, scrolling down beyond the last item causes the first 
item to appear; and scrolling up beyond the first item causes 
the last item to appear.

The pushbuttons are disabled while the display is starting up. 
An up/down arrow indicator appears in the lower left corner of 
the display after initialization is complete and the buttons are 
enabled.

All of the selectable second line messages are shown in 
Table 3. Submenu items are shown indented under their 
top-level menu description.

Содержание ControLinks S7999

Страница 1: ...ating Status Source of demand control Actuator positions Hold status Total cycles Total hours of operation Run time Fault history of six most recent faults Fault code Fault message Cycles at time of fault Diagnostic information Input Output status Demand control input and position Fuel selection Fuel position Motor settings Light off position of fuel air and FGR purge position of fuel air and FGR ...

Страница 2: ...ating 40 F 40 C to 140 F 60 C Storage 60 F 51 C to 150 F 66 C Humidity 85 percent relative humidity continuous noncondensing Vibration 0 5G environment Mechanical Dimensions See Fig 1 Weight 4 ounces 124 grams unpacked Display 40 character 2 rows by 20 columns Approvals Underwriters Laboratories Inc Component Recognized IRI Acceptable Federal Communications Commission Part 15 Class B emissions EN6...

Страница 3: ...r reaches the saturation point The S7999 ControLinks is designed to operate in a maximum 85 RH continuous noncondensing moisture environment Vibration Do not install the S7999 where it can be subjected to vibration in excess of 0 5G continuous maximum vibration Weather The S7999 is not designed to be weather tight If installed outdoors the S7999 must be protected by an approved weather tight enclo...

Страница 4: ...ting a Display Module 1 Do not route the Display Module wiring in conduits that carry line voltage circuits 2 Avoid routing the Display Module wiring close to ignition transformer leadwires 3 Route the Display Module wiring outside of conduit if properly supported and protected from damage 7 Maximum wire lengths a DM The maximum length interconnecting wire is 4000 ft 1219m 8 Install all electrical...

Страница 5: ...he Manual Potentiometer input Manu however the LF input is on so the normal rate request is overridden and the system is firing at the Lightoff rate Rate The RATE item shown in Fig 5 is the current firing rate request that is driving the R7999 Possible values are shown below using dashes to represent the positions where digits would appear C shows the CmA input current requested rate as a percenta...

Страница 6: ...nd line of the display however when the display is first powered up this area is used to indicate the progress of the initialization of the S7999 display itself Fig 6 Display module LINE2 area during display initialization After the display is first energized or connected it must wait to receive 15 different configuration information records from the R7999 before it is fully functional Although th...

Страница 7: ...entifier for the submenu to appear in the LINE2 area in the top right corner of the display Each submenu item has a left pointing arrowhead to indicate that the change level pushbutton may be used to exit the submenu and return to the top level menu In the top level menu the LINE2 area is blank The toggle button cycles the second line of the display between the main display and whichever second li...

Страница 8: ... Input On Off ON indicates Manual is selected OFF indicates Auto is selected FSelect1 T5 Fuel 1 Input On Off FSelect2 T6 Fuel 2 Input On Off Alarm T7 Alarm Output On Off HFP T8 High Fire Proven Output On Off LFP T9 Low Fire Proven Output On Off HF T10 High Fire Input On Off MV T11 Main Valve Input On Off LF T12 Low Fire Input On Off LCI T13 Limit Control Input On Off LCO T14 Limit Control Output O...

Страница 9: ... XmA Hold is configured as None Purge FGR FGR Actuator position during PURGE On curve Closedb Man Limit Manual Limit configuration setting Enabled Disabledb Indicates if the R7999 was commissioned to enable the Manual Potentiometer to limit the maximum firing rate CL Rev M NvV BBB ControLinks R7999 software revision and build code M major N minor V version BBB build code Display Rev BBB Display S7...

Страница 10: ... Fig 7 through 9 show a lockout condition that illustrates the three display module messages Pressing the scroll or toggle buttons will suspend the cycling of the fault messages until either the buttons are used to return to the main display or 60 seconds elapse with no buttons pressed Special Condition Displays Seven special condition display can be shown that preclude normal system operation as ...

Страница 11: ...NKS DISPLAY MODULE 11 65 0262 Fault Blink Codes and Actions The Fault Blink Codes and respective corrective actions are found in form 65 0238 Fig 10 Display module flush mounting outline M5082B 1 8 in DIA 2 3 175 mm ...

Страница 12: ... Control Home and Building Control Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: