Process Displays
AGA8DL & AGA8GS
94
900 Control Station User Guide
Revision 9
May 2014
Status
number
Block type
Severity
Description
46
AGA 8 - DETAIL
Warning
MOLE FRACTION FOR METHANE < 0.45 OR > 1.0
FOR NITROGEN < 0.0 OR > 0.5
FOR CARBON DIOXIDE < 0.0 OR > 0.3
FOR ETHANE < 0.0 OR > 0.1
FOR PROPANE < 0.0 OR > 0.04
FOR WATER < 0.0 OR > 0.0005
FOR H2S < 0.0 OR > 0.0002
FOR HYDROGEN < 0.0 OR > 0.1
FOR CARBON MONOXIDE < 0.0 OR > 0.03
FOR OXYGEN < 0.0 OR > 0.0
FOR BUTANES < 0.0 OR > 0.01
FOR PENTANES < 0.0 OR > 0.003
FOR H < 0.0 OR > 0.002
FOR HELIUM < 0.0 OR > 0.002
FOR ARGON < 0.0 OR > 0.0
49
AGA 8 - DETAIL
Warning
SUM OF MOLE FRACTIONS < 0.9999 OR > 1.0001
52
AGA 3 - ORIFICE
Error
FLOWING PRESSURE WAS <= 0.0 OR > 40000. PSIA
53
AGA 3 - ORIFICE
Error
FLOWING TEMPERATURE < -200. OR > 760. DEG F
55
AGA 3 - ORIFICE
Error
ORIFICE DIAMETER WAS >= 100.0 INCHES
56
AGA 3 - ORIFICE
Error
PIPE DIAMETER WAS >= 100.0 INCHES
57
AGA 3 - ORIFICE
Error
FLOWING OR STANDARD DENSITY WAS <= 0.0
LBM/FT^3
58
AGA 3 - ORIFICE
Error
DIFFERENTIAL PRESSURE WAS <= 0.0 INCHES H2O
65
AGA 3 – ORIFICE
Error
SUPERCOMPRESSIBILITY FACTOR WAS <= 0.0
66
AGA 3 – ORIFICE
Error
RELATIVE DENSITY AT STANDARD CONDITIONS WAS <
0.07 OR > 1.52
68
AGA 3 – ORIFICE
Error
COMPRESSIBILITY FACTOR AT STANDARD
CONDITIONS <= 0.0
69
AGA 3 – ORIFICE
Error
BETA RATIO (DO/DM) <= 0.0 OR => 1.0
75
AGA 3 – ORIFICE
Warning
ORIFICE DIAMETER WAS < = 0.45 INCHES
76
AGA 3 – ORIFICE
Warning
PIPE DIAMETER WAS <= 2.0 INCHES
77
GENERAL
CONFIG
Error
ERROR INVALID COMPANION BLOCK
INTERCONNECTION
78
GENERAL
CONFIG
Error
METER/COMPRESSIBLITY BLOCK UNITS ARE
INCONSISTENT
79
AGA 3 - ORIFICE
Warning
BETA RATIO (DO/DM) WAS < 0.1 OR > 0.75
99
GENERAL
OPERATION
N/A
Block is disabled – process value outputs are set to 0 and
error/warning pins are turned off.