CIPer
TM
MODEL 30 CONTROLLER - INSTALLATION AND OPERATIONS GUIDE
31-00206 - 02
20
Steps To Perform Provisioning Service
1.
Navigate to the
ProvisioningNiagara
palette, add a new
NetworkJobPrototype
to any place in the
station under Config (NiagaraNetwork for example) and name the job prototype (example -
CIPer30_1.1.4_Upgrade).
2.
Click the
(+)
icon from
Steps run for each station
section, select
Upgrade Out-of-date Software
, and
then click
OK
.
You can view the list of jobs defined for the required stations.
3.
Click the (+) icon from
Stations to include in the job
section, select the checkbox to select a specific
station, or select the
Check All
option to select the all listed station, and then click
OK
.
NOTE
Make sure to increase the Device Reboot Timeout from 10 minutes to 15 minutes if you are
connecting more than 6 expansion IO to the CIPer Model 30 controller.