Procedure 3: Using Niagara Provisioning Service
Following are the dist files required to upgrade CIPer Model 30 controller and Expansion IO using for
Provisioning Service:
Files Required for Niagara Provisioning Service
Tools
File Name
Version
WEB-O3022H Firmware
honeywell-IPCSIO.dist
1.1.0.76
WEB-O9056H Firmware
honeywell-IPCIO.dist
1.1.0.140
Baseboard Firmware
honeywell-IPCBASE.dist
1.1.1.146
OS QNX
honeywell-IPCQNX.dist
7.0.4.4
JRE
honeywell-azul-ejre-ipcqnx-arm.dist
1.8.0.282
IPC Tools
honeywell-IPC-tool.dist
4.10.0.1.1.257
IPC Module
honeywell-IPC-module.dist
4.10.0.154
Niagara Core Software
nre-core-honeywell-IPCQNX-arm.dist
4.10.0.154.4
Niagara Config Software
nre-config-honeywell-IPC.dist
4.10.0.154.6
Niagara provisioning service allows you to upgrade multiple CIPer Model 30 controllers and Expansion IO
For additional information on setting up provisioning service see the
CIPer Model 30 Installation and
or open the following ORD (
local:
module://docProvisioning/doc/ProvisioningInstall.html)
on your workbench:
NOTE
Installing the honeywell-IPC-factory.dist file is not possible by Provisioning Service.
NOTE
The station names in each of the CIPer Model 30 controllers must be unique in order to
add them as a remote Niagara station in the Niagara station manager. The station in the
CIPer Model 30 controller need not be running in order to update the controller. You must
configure the platform connection of the controller to perform the update.
By default, only one station will be upgraded at a time. In order to upgrade multiple
controllers at the same time do the following
Navigate to the AX property sheet of the job prototype and set the
Force unsafe parallel
execution
to
True
, refer to the screenshot below.