T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS

69-1510-4

6

Table 3. Thermostat Installer Setup Options.

Select

Installer Setup 

Number (Press 

Time 

 key to 

change)

Factory Setting

Other Choices

(Press   or   key to change)

Actual 

Setting

Display

Description

Display

Description

Not Used.

1

Fan 
operation.

2

(Number 2 must 
be set to 1 to 
extend fan 
operation.)

0

Conventional 
applications 
where 
equipment 
controls fan 
operation in heat 
mode.

1

Heat pump or electric heat 
applications where 
thermostat controls fan 
operation in heat mode.

Not Used.

3

Heating cycle 
rate.

4

6

6—6 cph used 
for conventional 
heat.

1, 3, or 
9

1—1 cph used for radiant

 floor heat, gravity 
system.

3—3 cph used for hot 

water systems or high 
efficiency furnaces.

9—9 cph used for electric 

heat systems.

Not Used.

5 thru 11

System 
setting 
adjustment

12

1

Manual 

changeover

0 or 2

0—Auto changeover
2—Auto only

Adaptive 
Intelligent 
Recovery™ 
control.

13

1

Conventional 
recovery 
(system starts 
recovery at 
programmed 
time).

Adaptive Intelligent 
Recovery™ control is 
activated (system starts 
early so setpoint is 
reached by start of 
program period).

Not Used.

14 thru 15

Clock format.

16

0

12-hour clock 
format.

1

24-hour clock format.

Not Used.

17 thru 23

Outdoor 
temperature 
display 
(select 
models).

24

0

No outdoor 
temperature is 
displayed.

1

Outdoor temperature is 
displayed. Needs a 
C7089B1000 Outdoor 
Temperature Sensor to 
operate.

Not Used.

25 thru 32

Minimum off 
time for the 
compressor.

33

5

5 minute 
minimum off time 
for the 
compressor.

0 thru 4

Minimum number of 
minutes (0 thru 5) the 
compressor will be off 
between calls for the 
compressor.

Temperature 
range stops 
in heating.

34

32.0

Highest setting 
for heating 
setpoint.

4.5 to 
31.5

Temperature range (0.5°C 
increments) of heating 
setpoint settings.

Temperature 
range stops 
in cooling.

35

7.0

Lowest setting 
for cooling 
setpoint.

7.5 to 
37.0

Temperature range (0.5°C 
increments) of cooling 
setpoint settings.

Not Used.

36

Содержание Chronotherm IV T8602D

Страница 1: ...tat about 1 5m 5 ft above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat Wallplate Installation Th...

Страница 2: ... Securely tighten each terminal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to pre vent drafts from affecting the thermostat Fig 3 Typical hookup in heat and cool system with two transformers 1 5 METERS 5 FEET YES NO NO NO M10856 WIRES THROUGH WALL WALL MOUNTING HOLES M15044 MOUNTING SCREWS WALL ANCHORS 2 L1 HOT L2 M10855 FAN RELAY Y G THERMOSTAT RC HEA...

Страница 3: ...PPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CAN BE USED FOR CHANGEOVER VALVE ON SINGLE STAGE HEAT PUMP SYSTEMS AVAILABLE ON SELECT MODELS OT WIRES MUST HAVE A SEPARATE CABLE FROM THE THERMOSTAT CABLE 2 2 2 1 3 OT OT OUTDOOR TEMPERATURE SENSOR 3 RC W MILLIVOLT HEATING ONLY WALLPLATE R M2931 TH TH PP PP MILLIVOLTAGE GAS CONTROL LIMIT CONTROL MILLIVOLTAGE GENERATOR PILOTSTAT CON...

Страница 4: ...sly Auto Fan operates with equipment Fig 10 Thermostat System and Fan key locations NOTE Always press the keys with your fingertip or sim ilar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard M14624 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy INCREASE TEMPERATURE SETTING OR S...

Страница 5: ...ed See Fig 11 and 12 To advance to the next Installer Setup press the Time key To change a setting use the increase or decrease key To scroll the Installer Setup numbers backward press the Time key To exit the Installer Setup press Run Program Fig 11 Display of all LCD segments Fig 12 Display of Installer Setup number and setting CAUTION Electric Heat Configuration Hazard Can cause equipment damag...

Страница 6: ...uto only Adaptive Intelligent Recovery control 13 1 Conventional recovery system starts recovery at programmed time Adaptive Intelligent Recovery control is activated system starts early so setpoint is reached by start of program period Not Used 14 thru 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not Used 17 thru 23 Outdoor temperature display select models 24 0 No outdoor tem...

Страница 7: ...s to 1 5 C higher than actual room temperature 5 Display adjusts to 5 C lower than actual room temperature 1 0 Display adjusts to 1 0 C lower than actual room temperature 1 5 Display adjusts to 1 5 C lower than actual room temperature Furnace Air Filter Timer 43 0 Off 1 2 3 4 1 10 days 2 30 days 3 60 days 4 120 days Time counted when heat cool or fan is running Humidifier Pad Monitor 44 0 Off 1 2 ...

Страница 8: ...gram to exit the System Test M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Set Day Time Mon PM M14620 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Day Heat Cool Settings Daylight Time Copy Set Day Time PM Tue M14621 Time Set Pr...

Страница 9: ...escription Heating Equipment System Test Time 10 Enter heating equipment system test 11 Heat comes on When Installer Setup number 2 is 1 the system fan is also energized 10 Heat and system fan turn off Cooling Equipment System Test Time 30 Change from heating to cooling equipment system test 31 Cool and system fan come on 30 Cool and system fan turn off Fan Equipment System Test Time 40 Change fro...

Страница 10: ... identification code Example 02 software ID code 2 4 Press the increase key again to display the soft ware revision number Example 001 Revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the system test The system test times out after four minutes without any key presses CHECKOUT Outdoor Temperatur...

Страница 11: ...C equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat minimum off time is activated Wait up to five minutes for the system to respond System selection is not set to Heat Set system selection to Heat Heating setpoint is below ...

Страница 12: ... fan operation Conventional heating equipment turns on the fan when the furnace has warmed up to a setpoint Wait a minute after seeing the on indicator and then check the registers Heating or cooling equipment is not operating Verify operation of heating or cooling equipment in self test Outdoor tempera ture not displayeda Option not activated Enter Installer Setup number 24 and set to 1 Thermosta...

Отзывы: