T8602C CHRONOTHERM

® 

IV DELUXE PROGRAMMABLE THERMOSTATS

Troubleshooting Guide (continued)

Symptom

Possible Cause

Action

Cooling will not
come on.

No power to the thermostat.

Check for 24 Vac between R or RC and Y terminals  

If missing 24 Vac:

check if the circuit breaker is tripped—reset the
circuit breaker.

check if the system fuse is blown—replace the
fuse.  

check if the power switch on the HVAC equipment
is in the Off position—set to the On position.

check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is
activated.

Wait up to five minutes for the system to respond.

Enter Installer Setup number 33. Reconfigure minimum off
time (if required).

System selection is not set to
Cool.

Set system selection to Cool.

Cool setpoint is above room
temperature.

Check cooling setpoint. Set cooling setpoint to desired
temperature.

Heating or cooling
come on momen-
tarily and shut off

Heat or cool circuit is opening
up or becoming high
impedance.

Add resistor in parallel with load or install interface relay.

System on indicator
(flame=heat,
snowflake=cool) is  

Fan operation set for 0 (con-
ventional heat) when it should
be set for 1 (electric heat).

Enter Installer Setup number 2 and reconfigure the fan
operation.

displayed, but no
warm or cool air is
coming from the
registers.

Conventional heating
equipment turns on the fan
when the furnace has  
warmed up to a setpoint.

Wait a minute after seeing the on indicator and then check the
registers.

Heating or cooling equipment is
not operating.

Verify operation of heating or cooling equipment in self-test.

Outdoor tempera-
ture not displayed

a

Option not activated.

Enter Installer Setup number 24 and set to 1. Thermostat must
have OT terminals and a C7089B1000 installed.

Outdoor
temperature  

Outdoor sensor is connected
incorrectly.

Refer to C7089B1000 installation instructions and check wiring
between the thermostat and sensor.

display is incorrect

a

Wrong sensor.

Replace sensor with C7089B1000 sensor.

Thermostat
backlight appears
dim.

Backlight may fade over the life
of the batteries.

• Wait unit Replace Battery indicator is illuminated and

replace batteries.

• Replace batteries now.

a

 Select models.

Содержание Chronotherm IV T8602C

Страница 1: ...tructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instruc tions to check out the product operation Location Install the thermostat about 1 5m 5 ft above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermost...

Страница 2: ...ghten mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 for typical hookup A letter code is located near each terminal for identification CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 1 Loosen the terminal screws on the wallplate and connect the system wires See Fig 4 IMPORTANT Use 18 gauge color coded t...

Страница 3: ...ACTOR HEATING TRANSFORMER COOLING TRANSFORMER 2 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM AVAILABLE ON SELECT MODELS OT WIRES MUST HAVE A SEPARATE CABLE FROM THE THERMOSTAT CABLE 2 1 1 3 OT OT OUTDOOR TEMPERATURE SENSOR 3 Fig 4 Proper wiring technique M4826 FOR WRAPAROUND INSERTION STRIP 7...

Страница 4: ... FORWARD THROUGH INSTALLER SETUP OPTIONS DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTIONS DISPLAY INFORMATION SUCH AS PRESENT SETTINGS AND OUTDOOR TEMPERATURE RETURN TO NORMAL OPERATIONS ENTER INDEFINITE OR TIMED HOLD MODE SET CURRENT DAY AND TIME SET CURRENT OR PROGRAM DAY CHANGE BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME INCREASE TIME SETTING OR SCROLL FORWARD THRO...

Страница 5: ...used to customize the thermostat to specific systems Some of the options include temperature display system changeover and outdoor temperature display Installer Setup numbers are listed in Table 3 The table includes all the configuration options and the factory settings for the T8602 A combination of key presses are required to use the Installer Setup feature To enter the installer setup press and...

Страница 6: ... 23 Outdoor temperature display select models 24 0 No outdoor temperature is displayed 1 Outdoor temperature is displayed Needs a C7089B1000 Outdoor Sensor to operate Not used 25 thru 32 Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 Minimum number of minutes 0 thru 5 the compressor will be off between calls for the compressor Temperature range stops...

Страница 7: ... Time until DST is displayed M14622 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Daylight Time Copy Set Day Time AM DST Tue 4 Press Run Program M14623 Time Set Program System Fan Run Program Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Wake Room Sys...

Страница 8: ...est and Time to go back to the previous test Press Run Program to exit the system test 4 Press the increase key again to display the software revision number Example 001 Revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the system test The system test times out after four minutes without any key ...

Страница 9: ...wer temperature limits were reached Check the temperature setpoints Heating limits are 4 5 to 32 C Cooling limits are 7 to 37 C heating higher or the cooling lower The setpoint temperature range stops were configured Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops Heating will not come on No power to the thermostat Check for 24 Vac between R and W terminals If missing 24...

Страница 10: ...t is opening up or becoming high impedance Add resistor in parallel with load or install interface relay System on indicator flame heat snowflake cool is Fan operation set for 0 con ventional heat when it should be set for 1 electric heat Enter Installer Setup number 2 and reconfigure the fan operation displayed but no warm or cool air is coming from the registers Conventional heating equipment tu...

Страница 11: ...69 1567 11 T8602C CHRONOTHERM IV DELUXE PROGRAMMABLE THERMOSTATS ...

Страница 12: ...Taiwan R O C www honeywell com yourhome Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 Home and Building Control Honeywell 1985 Douglas Drive North Golden Valley MN 55422 ...

Отзывы: