LION System
Description
of the CLLIONLC01
35
EN1Z-0921GE51
R0315
Alarm and Power LEDs
The CLLIONLC01 is equipped with an alarm LED and a
power LED.
1
2
Fig. 52
Alarm LED (1) and power LED (2)
Alarm LED (1, red)
Off
Normal operation
On
Watchdog alarm output is powered.
The controller has encountered a
hardware problem.
The application has a fault.
The controller has been powered up
without an application or the operator has
manually stopped the application, e.g.,
using XL-Online. In this case, the LED will
light up and, simultaneously, the
watchdog relay will be activated
22 minutes after power-up without
application.
Flashing
The watchdog alarm output has not yet been
powered, although the controller has
encountered a problem.
The controller performs a warm start.
If the problem persists, the LED will become
lit constantly, see above.
See section "Troubleshooting" on page 39.
Table 33 Controller alarm LED
Power LED (2, green)
On
Normal operation
Flashing
One or more of the internal voltage
supplies are outside of the permissible
ranges.
The controller stops operation.
►
Check wiring or see section "Trouble-
shooting" on page 39.
Goes out
briefly
The operator has activated the reset
button
The controller is performing a warm
start
Table 34 Controller power LED
Watchdog
Watchdog status
Status
Signal on terminal 4
Failure (= alarm)
24 V
Normal operation
0 V
Table 35 Watchdog status 4
Permissible Load of Normally Open Contact
(Terminal 4)
Max. load
Min.
current
Per normally
open contact
(terminal 4)
19…29 VAC
current at cos
φ
≥
0.95: 0.5 A,
current at cos
φ
≥
0.6: 0.5 A
19…29 VDC
0.5 A resistive or inductive
10 mA
Table 36 Permissible load of terminal 4