LION System
Wiring
and Setting Up the System
29
EN1Z-0921GE51
R0315
Commissioning I/O Modules
Commissioning Panel Bus I/O Modules
During engineering, the HEX address of the Panel
I/O modules is defined.
NOTE:
With Panel Bus I/O modules it is essential that
the HEX switch be set to the address assigned by
the engineering tool.
The CLLIONLC01 Controller automatically commissions all
Panel Bus I/O modules.
Commissioning L
ON
W
ORKS
Bus I/O Modules
Commissioning is done using the engineering tool.
Updating Software
CARE is used to update the CLLIONLC01 Controller.
Software with Panel Bus I/O Modules
The CLLIONLC01 Controller’s firmware includes the firm-
ware for the Panel Bus I/O modules. Thus, whenever the
CLLIONLC01 Controller’s firmware is updated, the firmware
of the Panel Bus I/O modules is automatically updated, too.
Example
Status before update: The CLLIONLC01 Controller was
loaded with controller firmware V3.01.03, which included the
corresponding Panel Bus I/O module firmware (see Fig. 41).
When the controller firmware is updated from V3.01.03 to
V3.02.02, if newer firmware is available for individual Panel
Bus I/O modules, their firmware will be automatically up-
dated, too. In this example, newer Panel Bus I/O module
firmware is, indeed, available for all but the CLIOP830A
Mixed Panel Bus I/O modules. As a consequence, the firm-
ware of all of the Panel Bus I/O modules – except for the
CLIOP830A Mixed Panel Bus I/O modules – will be
updated, accordingly.
CLLIONLC01
firmware V3.01.03
CLLIONLC01
firmware V3.02.02
CLIOP821A
firmware V1.01.01
CLIOP821A
firmware V1.01.05
CLIOP821A updated
to V1.01.05
CLIOP822A
firmware V1.01.01
CLIOP822A
firmware V1.01.05
CLIOP822A updated
to V1.01.05
CLIOP823A
firmware V1.01.00
CLIOP823A
firmware V1.01.04
CLIOP823A updated
to V1.01.04
CLIOP824A
firmware V1.01.00
CLIOP824A
firmware V1.01.04
CLIOP824A updated
to V1.01.04
CLIOP825A
firmware V1.01.00
CLIOP830A
firmware V1.00.02
CLIOP830A
firmware V1.00.02
CLIOP825A
firmware V1.00.02
CLIOP825A updated
to V1.00.02
CLIOP830A not updated
Fig. 41. Automatic updating of Panel Bus I/O module
firmware (example)
Software with L
ON
W
ORKS
Bus I/O Modules
You can update the L
ON
W
ORKS
I/O modules using CARE or
EXCELON.