CLIF-CBUSLC INTERFACE – INSTALLATION & COMMISSIONING INSTRUCTIONS
21
EN1Z-1026GE51
R0417
TROUBLESHOOTING
General
The following LEDs of the CLIF-CBUSLC can be used for troubleshooting purposes:
Power LED (green)
Status
LED
(red)
L2 LED (yellow)
Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LED
Power LED (green) of CLIF-CBUSLC
Table 16. CLIF-CBUSLC power LED
case power LED
meaning
remedy
1
ON
Normal operation
No action necessary.
2
OFF
Power supply not OK.
►
Check power supply voltage.
►
Check wiring.
►
If problem persists, replace hardware.
Status LED (red) of CLIF-CBUSLC
Table 17. CLIF-CBUSLC status LED
case status LED
meaning
remedy
1
OFF after
power-up
Normal operation.
No action necessary.
2
ON con-
tinuously after
power-up
– No or invalid firmware
►
Try powering down and then powering up the CLIF-
CBUSLC.
►
If problem persists, replace hardware.
L2 LED
Table 18. CLIF-CBUSLC L2 LED
case bus LEDs
meaning
remedy
1
ON
continuously
after power-up
A SUSI client (ARENA
AX
, COACH
AX
or
ARENA 3.0) is connected
No action necessary.
2
Dark
No client is connected
►
If you are unable to establish communication, check
IP address, SUSI port number, …
Tx and Rx LEDs
Table 19. CLIF-CBUSLC Tx and Rx LEDs
case bus LEDs
meaning
remedy
1
Both Tx and Rx
are flashing
Normal operation; RS485-1 is functioning
properly.
No action necessary
2
Both Tx and Rx
are OFF
No communication on RS485-1.
►
Switch ON communication on RS485-1. Further
handling like case 4 (below).
3
Rx is flashing
and Tx is OFF
Communication on RS485-1 has been
switched OFF, but the CLIF-CBUSLC is
receiving data from controllers.
►
Use client to establish a connection with correct
device ID and baud rate
4
Tx is flashing
and Rx is OFF
The CLIF-CBUSLC is attempting to establish
communication on RS485-1, but there is no
answer.
►
The communication rate (Kbaud) on RS485-1 has
not been correctly set; controllers on the C-Bus may
have been setup incorrectly; wiring problem or
hardware defect.