Honeywell Centra Line CLIF-CBUSLC Скачать руководство пользователя страница 10

CLIF-CBUSLC INTERFACE – INSTALLATION & COMMISSIONING INSTRUCTIONS 

EN1Z-1026GE51 R0417 

10 

lower, the automatic installation does not work: Please down-
load the appropriate USB driver prior to the installation at: 
 

http://catalog.update.microsoft.com/v7/site/ScopedViewRedire
ct.aspx?updateid=37e35bd4-d788-4b83-9416-f78e439f90a2

 

 
Please connect the controller to the PC as described in 
section "Windows 8" and perform the general installation 
procedures for drivers in Windows 10. 
 

Ethernet / RJ45 Socket 

The CLIF-CBUSLC is equipped with an Ethernet / RJ45 
socket featuring one LED. 
 

J1

J8

Ethernet / RJ45 socket

 

Fig. 7. Ethernet / RJ45 socket 

This Ethernet / RJ45 socket is a 10/100-Mbaud Ethernet 
interface permitting communication with a SUSI client like 
ARENA

AX

, ARENA

NX

, COACH

AX

, COACH

NX

, or ARENA 3.0 

(as per IEEEC 802.3)  
 

LINK/ACT.

 

Fig. 8. Ethernet / RJ45 socket 

 

NOTE:

 

The Ethernet / RJ45 socket is usually earth-
grounded. For additional information on earth 
grounding, see also "Appendix 1: Earth Grounding" 
on pg. 22. 

 

LEDs 

The CLIF-CBUSLC features the following LEDs: 

 

Fig. 9. CLIF-CBUSLC LEDs 

Table 5. CLIF-CBUSLC LEDs 

symbol

color 

function, description 

L1 yellow unused 

L2 yellow 

LED indicating that a SUSI client 
(ARENA

AX

, COACH

AX

 or ARENA 3.0) is 

connected 

Tx yellow 

RS485-1 status LED indicating trans-
mission of C-Bus signals 

Rx yellow 

RS485-1 status LED indicating reception 
of C-Bus signals.  

!

red 

status LED indicating hardware problems 

green power 

LED 

 
See also section "Troubleshooting" on page 21 for a detailed 
description of the behaviors of the LEDs and their meanings. 
 

RS485 Interface 

General 

The CLIF-CBUSLC has one C-Bus interface: 

  RS485-1 (consisting of push-in terminals 24 [GND-1], 25, 

and 26) is isolated. 

 

RS485-1 Bias and Termination Resistors 

RS485-1 is equipped with a three-position slide switch which 
can be used to switch its bias resistors OFF (position "MID" – 
this is the default and the 

only allowed setting

), ON (position 

"BIAS"), and ON with an additional 150

 termination resistor 

(position "END"). 
 

J1

J8

RS485-1

3-POSITION SLIDE SWITCH

MI

D

BI

A

S

EN

D

 

Fig. 10. RS485-1 three-position slide switch 

 
The slide switch setting must remain in the leftmost position 
for "MID". 

Содержание Centra Line CLIF-CBUSLC

Страница 1: ...Power Supply 13 RIN APU24 14 Lightning Protection 14 Engineering Commissioning 15 Required Preparations 15 Extra Parts 16 LonWorks Communications 17 General Information 17 Connecting to a LONWORKS Network 17 C Bus Connection 18 C Bus Topologies 18 C Bus Cables 18 Connecting CLIF CBUSLC via RS485 1 to C Bus 19 Effect of Poll Rate Subscribed Points on CPU Load 20 C Bus Related Size Recommendations 2...

Страница 2: ...nly accessory equipment which comes from or has been approved by Honeywell Information as per EN 60730 Purpose The purpose of the device is OPERATING CONTROL The CLIF CBUSLC is an interface device intended for HVAC in home residential commercial and light industrial environments Construction The CLIF CBUSLC is an independently mounted electronic control unit with fixed wiring Mounting Method The C...

Страница 3: ...ction IP20 mounted on walls with two accessory MVC 80 AC1 covers Fire class V0 Weight 0 6 kg excl packaging SYSTEM OVERVIEW Overview of Hardware Table 4 Overview of hardware feature description max cable length no bus interfaces RS485 1 isolated C Bus communication 1200 m 1 Ethernet Interface e mail communication browser access 100 m 1 SUSI IP communication 100 m 1 USB 2 0 Device Interface as Netw...

Страница 4: ...TIONS EN1Z 1026GE51 R0417 4 System Architecture ARENA NX ARENA 3 xx CLIF CBUSLC IF LON2 IF LON2 PANTHER PANTHER LION SERVAL LION IP USB USB IP NETWORK IP NETWORK LonWorks via IP C BUS via IP CLIF CBUSLC HAWK L IP OR Fig 1 CentraLine C Bus System architecture ...

Страница 5: ...of the IF LON2 max 500 mA high speed 3 Ethernet RJ45 socket for SUSI communication 10 100 Mbit s 1 link LED and 1 activity LED 4 Three position slide switch for setting bias and ter mination resistance of RS485 1 MUST REMAIN IN MIDDLE POSITION 5 RS485 1 isolated for C Bus communication 6 RS485 2 non isolated DO NOT USE 7 Future functionality 8 LEDs 9 USB 2 0 Device Interface for connection to web ...

Страница 6: ...IF CBUS Interface will be connected to the Windows 7 PC as shown in the following figure CLIF CBUSLC 2 CLIF CBUSLC 1 WINDOWS 7 PC Driver Variants Depending on the firmware version there are two different ways to install the USB driver 1 On most PCs the update is done automatically with the Windows update function 2 In the case of firmware 4 00 00 or higher you can use the Microsoft driver from you...

Страница 7: ...pters folder in the Device Manager and then click Update Driver Software 8 Click Browse my computer for driver software 9 Click Let me Pick from a list of device drivers on my computer 10 Click Have Disk 11 Click Browse and navigate to the folder drive CARE drivers 12 Depending on your Windows operating system type 32 bit or 64 bit select the RNDIS USB driver 32 bit or the RNDIS USB driver 64 bit ...

Страница 8: ...BUS Interface to the Windows 8 PC you will need an USB cable of type A Male to type B Male Type B standard The CLIF CBUS Interface will be connected to the Windows 8 PC as shown in the following figure CLIF CBUSLC 2 CLIF CBUSLC 1 WINDOWS 8 PC PROCEDURE 1 Insert the A Male connector of the USB cable into an USB interface jack of the PC and insert the B Male connector into the controller s USB devic...

Страница 9: ...hen click Next button RESULT The Update Driver Warning message box displays 9 Confirm the warning by clicking Yes button RESULT The driver will be installed successfully as indicated by the final message box 10 Click the Close button Windows 10 In the case of controllers with firmware 4 00 00 or higher the appropriate driver is automatically installed with a Windows update In the case of controlle...

Страница 10: ...Grounding on pg 22 LEDs The CLIF CBUSLC features the following LEDs Fig 9 CLIF CBUSLC LEDs Table 5 CLIF CBUSLC LEDs symbol color function description L1 yellow unused L2 yellow LED indicating that a SUSI client ARENAAX COACHAX or ARENA 3 0 is connected Tx yellow RS485 1 status LED indicating trans mission of C Bus signals Rx yellow RS485 1 status LED indicating reception of C Bus signals red statu...

Страница 11: ...stics of Generators and Receivers for Use in Balanced Digital Multipoint Systems only one driver com municating via an RS485 interface may transmit data at a time Further according to U L requirements the RS485 interface may be loaded with a max of 32 unit loads A max of 29 C Bus devices may be connected IMPORTANT The cable length affects the baud rate See Table 7 Table 7 Baud rate vs max cable le...

Страница 12: ... voltage field wiring and Class 2 field wiring In the case of vertical mounting on DIN rails the CLIF CBUSLC should be secured in place using a commercially available stopper See also the CLIF CBUSLC Mounting Instructions MU1Z 1006GE51 Dimensions 24 25 26 27 28 29 30 31 32 24V 0 24V 1 GND1 485 1 485 1 n a n a GND2 485 2 485 2 n a 2 J1 J8 RS232 RS485 1 END BIAS MID 215 5 110 52 45 49 5 57 5 Fig 12 ...

Страница 13: ...incorrect wiring Higher voltages may damage the device Do not reconnect the power supply until you have completed the installation Fusing Specifications System Fusing We recommend that the system be equipped with an external fuse Fusing of Active Field Devices F2 depends upon given load Wiring Terminals The CLIF CBUSLC is equipped with push in terminal plugs Fig 14 Inserting removing wires from pu...

Страница 14: ...ide 001 120 Vac 24 Vac 50 VA 002 120 Vac 2 x 24 Vac 40 VA 100 VA from separate transformer 003 120 Vac 24 Vac 100 VA 24 Vdc 600 mA 004 240 220 Vac 24 Vac 50 VA 005 240 220 Vac 2 x 24 Vac 40 VA 100 VA from separate transformer 006 240 220 Vac 24 Vac 100 VA 24 Vdc 600 mA Table 11 Overview of CRT Series AC DC current transformer primary side max AC current max DC current CRT 2 230 Vac 2 A 500 mA CRT ...

Страница 15: ...l mask will then appear on the screen of your PC 3 When setting up your CLIF CBUSLC for the first time you will have to enter an administrator password This administrator password must contain 8 or more but not more than 31 characters uppercase letters lowercase letters numerals no whitespace characters 4 A login mask will appear You may now login using the administrator password 5 Press the CONFI...

Страница 16: ...rder no description TPU 11 01 Removable terminal plugs push in type complete set of 3 plugs for terminals 1 47 for the CLAXEH00ND100A TPU 45 01 Removable terminal plugs push in type complete set of 9 plugs for terminals 1 47 for the CLAXEH14ND100A and CLAXEH26ND100A MVC 80 AC1 Terminal cover color RAL9011 package of ten ...

Страница 17: ...4 non shielded twisted pair solid conductor wire When possible use Honeywell AK3781 AK3782 AK3791 or AK3792 cable US part numbers See Excel 50 5000 LONWORKS Mechanisms Product Literature no EN0B 0270GE51 for details including maximum lengths Use wire with a minimum size of 20 AWG 0 5 mm2 and a maximum size of 14 AWG 2 5 mm2 IF LON2 Optionally communication with physical I O modules with room and z...

Страница 18: ...e Excel 500 Excel 100 LION PANTHER can also be connected CLIF CBUSLC Excel 100 Excel 500 PANTHER Fig 21 C Bus topology Excel 5000 C Bus Cables NOTE Observe national regulations for C Bus cables For Europe only shielded cable is permitted For the U S shielded or unshielded cable can be used Cable type Description Recommended for J Y ST Y 2 x 2 x 0 8 shielded twisted pair Europe inside cabinet A Y S...

Страница 19: ...C is connected at either of the line s two ends an additional termination resistor RT 120 Ohm is necessary NOTE Regardless of the position of the CLIF CBUSLC along the C Bus the 3 position switch must be set to MID Example CLIF CBUSLC and Connected C Bus Devices 24V 24 0 F1 230 V 24 V L GND 1 GND 1 5VISO RS485 1 RS485 1 47 kOHM 47 kOHM C BUS DEVICE 2 RS485 RS485 GND C BUS DEVICE 3 RS485 RS485 GND ...

Страница 20: ...as LONWORKS devices As many 25 I O modules combination of Panel Bus I O modules and LONWORKS I O modules are possible but with some risk Max 16 We recommend using only Panel Bus I O modules since they do not count as LONWORKS devices As many 25 I O modules combination of Panel Bus I O modules and LONWORKS I O modules are possible but with some risk No of time programs per controller up to 64 Max 6...

Страница 21: ...LIF CBUSLC L2 LED case bus LEDs meaning remedy 1 ON continuously after power up A SUSI client ARENAAX COACHAX or ARENA 3 0 is connected No action necessary 2 Dark No client is connected If you are unable to establish communication check IP address SUSI port number Tx and Rx LEDs Table 19 CLIF CBUSLC Tx and Rx LEDs case bus LEDs meaning remedy 1 Both Tx and Rx are flashing Normal operation RS485 1 ...

Страница 22: ...atory this is because electrical safety is provided by the use of SELV and transformers according to standard EN60742 Safety against unexpected start up of rotating moving machines If the application plant does not contain machines that can be harmful to the operator due to an unexpected start up the standard EN60204 1 is not applicable If such machines are encountered then EN60204 1 must be follo...

Страница 23: ...which is usually terminal 1 24V 0 and terminal 2 24V In the following example CPU 3 has a deviating numbering and must be connected accordingly NOTE When using a single transformer for several CPUs each CPU ground must wired separately to the star point NOTE If the field device transformer is physically far away from the CPUs earth grounding must still be performed for the controller NOTE Use one ...

Страница 24: ...us via RS485 1 3 10 disposal WEEE Directive 2002 96 EC 2 Ethernet RJ45 socket details 10 protocol version 2 Ethernet Interface RJ45 socket 5 External HMI power consumption 3 RJ45 socket 12 extra parts TPU 11 01 removable push in terminal plugs 13 TPU 45 01 removable push in terminal plugs 13 fusing 13 LEDs 5 L2 3 10 21 power LED 3 10 21 Rx 3 10 21 status LED 3 10 21 Tx 3 10 21 power supply failure...