3. Description

Speed controlled compact booster unit with a vertical high-pressure pump as 
a safety device to separate potable water from category 5 fluids according to 
EN 1717 .
Fully automatic, fully wired Compact Booster Unit with modular design 
comprising a single pump system and a buffer tank for the hygienic separa-
tion of potable water and category 5 fluids according to DIN EN 1717, on a 
common base frame.
The modular design makes it possible to disconnect modules for installation 
in buildings with limited space.
The system is switched on and off regulated by pressure, the flow rate is 
controlled via frequency inverter..
Separation of systems as a means to protect potable water from being 
contaminated by fluids of the category 5 according to EN 1717

3.1 Overview

The system comprises one multi-speed high-pressure rotary pump with inlet 
and outlet shut-off valves. They can be locked with padlocks against 
unauthorised closing. They make it possible to disassemble the pump or the 
check valves without having to empty the pipeline system. The check valve 
on the pumping side prevents liquid from backing up on the pump and 
flowing backwards through it, and it relieves the floating ring seal. 
The fully automatic Compact Booster Unit with compact design comprising: 
• vertical high-pressure pump 
• frequency converter adapted on the motor to ensure a constant supply 

pressure to the points of consumption

construction and operation is according to DIN 1988,EN 1717 and EN 
13077. 

Figure 1:

CBU146 Construction

3.1.1 Installation type

• Fixed installation 

3.2 Intended use

The compact booster unit may only be operated in such areas as described 
in the other applicable documents. 
Non-intended operation of the compact booster unit can result in danger to 
persons, systems, the surroundings and the environment. 
• Operate the compact booster unit only if it is in perfect working condition. 
• Do not operate the compact booster unit if it is only partially assembled. 
• The compact booster unit may only be used to pump the medium as 

described in the documentation of the respective version. 

• Never operate the compact booster unit without pump medium. 
• Observe the values for minimum pumping rates (avoiding damage 

because of overheating, storage damage, ...). 

• Observe the values for maximum pumping rates (to avoid damage due to 

overheating, floating ring seal damage, cavitation damage, storage 
damage, ...). 

• Do not throttle the input of the compact booster unit (to avoid cavitation 

damage). 

• Other modes of operations, if not mentioned in the documentation, have 

to be coordinated with the manufacturer.

3.3 Non-intended use

The compact booster unit is not designed for operation outside. Tempera-
ture, light and moisture can lead to malfunctions and damaging devices. 
• Do not operate the compact booster unit outside.
• Operate the compact booster unit only as intended.
• Do not fill aggressive or flammable medium into the medium lines of the 

system.

• No mechanical stress on housings (e.g. by depositing objects or as a 

step).

• Do not perform any external modifications on the device housing. Do not 

paint housing parts and screws!

• Do not disassemble the compact booster unit more than is necessary for 

purposes of installation and maintenance.

Pump medium

Non-potable water 
Without aggressive, abrasive and solid 
components 

Flow rate 

see chapter  5. Technical data

Pumping head 

Adjustable within the range of pump characte-
ristics, preset to 60m
see chapter 5. Technical data

Medium temperature 

up to 30 °C 

Ambient temperature

up to 40 °C

Nominal pressure

PN 16 

Inlet pressure

1.5 - 8 bar (depending upon the model)

Supply voltage

3/PE, AC 400 V, 50 Hz 

1 Inlet 

5  Base 

frame 

2  Buffer tank 

Check valve

3  Display 

7

Inlet shut-off valve 

4

Pump 8 

Outlet 

shut-off 

valve 

4

2

1

5

8

6

7

3

Содержание CBU146

Страница 1: ...CBU146 Compact Booster Unit To ensure the quality of potable water according to EN1717 Instructions 32303735 001 ...

Страница 2: ...ndicator LED 8 4 4 Mode of operation 8 5 Technical data 9 5 1 Noise expectancy values 9 5 2 Authorised environmental conditions 9 6 Shipping 10 6 1 Check condition upon delivery 10 6 2 Transportation 10 7 Assembly 10 7 1 General safety instructions 10 7 2 Installation according to EN1717 10 7 3 Inspection before assembly 11 7 3 1 Installation site 11 7 4 Installing the compact booster unit 11 7 5 ...

Страница 3: ... with local regulations that are not covered by the manual 1 4 Further safety regulations Besides the safety instructions presented in this manual and its intended use the following safety regulations are valid Accident prevention regulations safety and operating regulations Safety regulations for handling hazardous substances Applicable standards and laws 1 5 Unauthorised operation types The limi...

Страница 4: ...ronmental hazard caused by leakage of hazardous substances Danger area Type of hazard Reduction of hazard Pipelines Injury through high pressure Clear pipelines of pressure and medium prior to assem bly maintenance shut down Danger area Type of hazard Reduction of hazard Injury from cables Danger to life Electric shock of 230 400V from electric voltage Connect up protective earth system Always swi...

Страница 5: ...l power supply companies 1 11Safety instructions for maintenance inspections and assembly work Alterations or modifications of the system are only permitted with the consent of the manufacturer Use only original parts or parts authorised by the manufacturer Use of parts other than those authorised may lead to loss of liability for any damage they may cause Perform service on the system only when t...

Страница 6: ...nd perfect condition This instruction manual is a part of the compact booster unit and has to be complete and accessible at all times Any instruction or page that is missing has to be replaced immediately 2 4 Illustrations The illustrations used are examples of one possible version of the compact booster unit and might differ in individual cases from the actual compact booster unit version 2 5 Sym...

Страница 7: ...t can result in danger to persons systems the surroundings and the environment Operate the compact booster unit only if it is in perfect working condition Do not operate the compact booster unit if it is only partially assembled The compact booster unit may only be used to pump the medium as described in the documentation of the respective version Never operate the compact booster unit without pum...

Страница 8: ...lug connectors to connect easily with the electrical equipment fitted to the supply container Messages sent via potential free contact for Alarms and warnings Pump run indicator 3 5 Options 4 Function 4 1 Inlet side On the inlet side there is a buffer tank It has a floating valve on its inlet to refill water The water level is measured with two float switches They send messages in the case of wate...

Страница 9: ...Weight m3 h m3 h m Inlet Pump P2 kW l mm mm mm kg CBU146 32A 060 0 6 7 0 86 G11 4 DN32 2 2 350 1543 800 1185 195 CBU146 40A 060 1 1 11 0 89 G11 4 DN40 3 0 350 1600 800 1185 218 CBU146 50A 060 1 6 19 0 85 G2 DN50 5 5 540 1965 800 1600 324 CBU146 65A 060 4 0 28 0 81 G2 DN65 7 5 540 1990 800 1600 346 CBU146 65B 060 4 0 34 0 100 G21 2 DN65 11 0 540 1990 800 1600 444 CBU146 80B 060 4 6 43 0 86 G21 2 DN...

Страница 10: ...e has to be solid level and horizontal Observe the weight information The compact booster unit is attached to wooden rails and wrapped in foil for transport and temporary storage All connection interfaces have protective lids Danger Danger for persons near by systems and the the environment that arises from the non intented use of the compact booster unit Operate the compact booster unit only as i...

Страница 11: ...pipelines so that they are free of tension The use of compensators with tie bars refer to the accessories section is recommended Caution Overflow not connected ª Danger of flooding the installation room Lead the overflow line to a drain with adequate dewatering capacity connection DN150 If compensators are used to damper vibrations their durability has to be ascertained Compensators have to be abl...

Страница 12: ...put shut off valve open loosen the ventilation screw and let the rest of the air out 11 Close the ventilation screw tightly 12 Check if the pump runs smoothly 8 3 1 Change switch on pressure 1 Click on the settings key indicated by as spanner symbol 2 Move up and down using the arrow keys to setting value 1 2 3 3 3 Press OK key 4 Move up and down using the arrow keys to desired setting value for t...

Страница 13: ...h the motor protection switch does not securely shut off the motor inlet lines Only perform maintenance work on the compact booster unit if you are sure that the compact booster unit is free of power Secure the compact booster unit against being switched on unintentionally Danger Danger of injury from electric voltage ª High shock currents and burns from direct and indirect contact with live parts...

Страница 14: ...the shut off drain and check valves function proper ly and don t leak 5 Clean the dirt trap in the pressure reducing valve if applica ble 6 Check the compensators for wear if applicable 7 Check the precharge pressure and if necessary check if the membrane pressure vessel leaks refer to Chapter 10 3 1 9 Check the switch on off points of the system 11 Check if the entire system is functioning proper...

Страница 15: ...propriate lifting moving of heavy modules or components ª Personal and property damage When moving heavy modules or components use suitable transport devices lifting devices and lifting accessories Warning Danger through improper disassembly Performance of tasks only by qualified personnel see section 1 12 B It is imperative to observe the laws and regulations on waste disposal of materials that a...

Страница 16: ...els then the TÜV has to be informed also The operating company or their customer herewith certifies to be fully trained in operation and maintenance of the compact booster unit The circuit diagrams and instructions were also delivered 1 Compact booster unit Series Size Serial number Order number 2 Customer Operating site Customer Operating site Name Address 3 operating data refer to circuit diagra...

Страница 17: ... handling The following safety precautions regarding rinsing medium residual fluids and their disposal are required We ensure that the above information is correct and complete and delivery will be made according to statutory requirements Type Order number Order item number3 Delivery date Range of application Pumped medium3 radioactive explosive corrosive poisonous hazardous to health biohazard fl...

Страница 18: ...ble water this central booster unit requires frequent maintenace contucted by enabled personal which needs to be documented after compleshion This compact booster unit is subject to the standards for potable water and guidelines for maintenance therein and have to be maintained regularly by qualified personnel and the results have to be documented Date Operating company Name Signature ...

Страница 19: ...MU1H 1376GE23 R1215 Translation of original 19 Honeywell GmbH GB ...

Страница 20: ...1 81309 http ecc emea honeywell com Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl Z A La Pièce 16 1180 Rolle Switzerland by its Authorised Representative Honeywell GmbH MU1H 1376GE23 R1215 Subject to change without notice 2015 Honeywell GmbH ...

Отзывы: