background image

C7772A-E WALLPLATE TEMPERATURE SENSOR

68-0213—2

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2.

Honeywell Customer Care

1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

Models: 

See Table 1.

Dimensions: 

See Fig. 1.

Temperature Ratings:

Operating: 45°F to 99°F (7°C to 37°C).

Shipping: -40°F to 150°F (-40°C to 65°C).

Humidity Ratings: 

5 to 95% rh, non-condensing.

Approvals:

National Electrical Code (NEC) Class II.

Fig. 1. C7772 Dimensions in in. (mm).

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

5.

Follow local codes for installation and application.

IMPORTANT

All wiring must agree with applicable codes, 

ordinances and regulations.

CAUTION

Electrical Shock or Equipment Damage Hazard.

Can shock individuals or short equipment 

circuitry.

Disconnect all power supplies before installation.

Location

The C7772 Wallplate Temperature Sensor should be located 

where it can sample an average air temperature. Avoid 

locations where air stratification can cause sensing errors. 

The sensor mounts directly on a 2 in. x 4 in. conduit box with 

the screws provided.

Table 1. C7772 Models.

NOTE: TCR = temperature coefficient of resistance.

4-1/2

(114)

3-5/16

(84)

2-3/4 (70)

5/16 (8)

M16295A

Model

Sensor Type

Nominal Resistance

Resistance-Temperature 

Curve Type

Leadwire 

Color

C7772A

20K NTC Thermistor

20,000 ohms at 77°F (25°C)

Non-linear Negative TCR

Green/Blue

C7772B

PT 1000 (TCR=385) Platinum Film

1000 ohms at 32°F (0°C)

Linear Positive TCR

Red

C7772C

PT 100 (TCR=385) Platinum Film

100 ohms at 32°F (0°C)

Linear Positive TCR

Yellow

C7772D

PT 3000 Platinum Film

3,266 ohms at 32°F (0°C)

Linear Positive TCR

Blue

C7772E

1420 ohm Resistor

1420 ohms at 75°F (24°C)

Linear (15 ohms per °F)

Red/Violet

Содержание C7772 Series

Страница 1: ...ow profile wall mounted applications where durability and tamperproof construction is desired such as schools prisons and institutions FEATURES Low profile when mounted on industry standard utility conduit box Rugged brushed stainless steel wallplate Integral foam pad isolates wallplate sensor from conduit box Insulated screw terminals ensure reliable field wiring connection Models available with ...

Страница 2: ...use a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions 5 Follow local codes for installation and application IMPORTANT All wiring must agree with appl...

Страница 3: ...ibed below These must be avoided to assure proper operation 1 Do not route temperature sensor wiring with building power wiring next to control contactors near light dimming circuits electric motors or weld ing equipment 2 Avoid poor wiring connections 3 Do not mount sensor in an incorrect environment Connect the low voltage wiring from the controller terminals to the sensor screw terminals and ti...

Страница 4: ...ywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com C7772A E WALLPLATE TEMPERATURE SENSOR U S Registered Trademark 2005 Honeywell International Inc 68 0213 2 B B Rev 08 05 ...

Отзывы: