69-0895—1

2

C7189A WALL MOUNT TEMPERATURE SENSOR

Run cable to a hole at the selected wall location. Pull

approximately 3 inches of wire through the opening.
Color-coded, 18 gauge thermostat wire is recom-
mended.

NOTE:

If the old thermostat has left marks on the wall
that are not covered by the C7189, order part no.
202689A Mounting Plate Accessory to mount
between the wall and the C7189.

RECYCLING NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash.

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of any control containing mercury in a
sealed tube.

If you have questions, call Honeywell Inc. at
1-800-468-1502, Monday through Friday, 7:00am
to 5:30pm.

Wiring

CAUTION

Keep wiring at least one foot away from large
inductive loads such as motors, line starters,
lightning ballasts, and large power distribution
panels. Failure to follow these wiring practices can
introduce electrical interference (noise), which can
cause erratic system operation. Use shielded cable
to reduce interference when rerouting is not
possible. Ground the shielded cable to the GND
terminal on the W8900.

Important

Erratic temperature readings from a sensor can
occur as a result of any of the wiring practices
described below. These practices must be
avoided to assure proper operation. Use shielded
cable to reduce interference if rerouting of sensor
wiring is not possible.
a. Do not route temperature sensor wiring with

building power wiring, next to control
contactors or near light dimming circuits,
electric motors or welding equipment.

b. Avoid poor wiring connections.
c. Avoid intermittent or missing building earth

ground.

CAUTION

Disconnect power supply before connecting to
wiring to prevent electrical shock or equipment
damage.

Wiring must comply with applicable codes, ordinances and
regulations.

Wire the C7189 Sensor to the W8900 Remote

Module terminals S1 and S. For an example of
general wiring of the C7189, see Fig. 2.

Push excess wire back into the hole. Plug the hole

using nonhardening caulk, putty or insulation to
prevent drafts from affecting performance.

Remove C7189 cover.
Mount the C7189 to the wall or junction box using

the screws and anchors provided.

Level the C7189 for appearance only. Device will

function properly even when not level.

Install C7189 cover.

5 FEET

(1.5 METERS)

YES

NO

NO

NO

M4476

Fig. 1. Typical Location for C7189 Sensor.

Содержание C7189A

Страница 1: ...tallation is complete check out product operation as provided in these instructions CAUTION Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage Location and Mounting Locate the C7189 Wall Mount Temperature Sensor where the setting will not be subjected to tampering 1 Choose a location for the sensor on an inside wall about 5 ft 1 5 m above the floor A h...

Страница 2: ... not possible Ground the shielded cable to the GND terminal on the W8900 Important Erratic temperature readings from a sensor can occur as a result of any of the wiring practices described below These practices must be avoided to assure proper operation Use shielded cable to reduce interference if rerouting of sensor wiring is not possible a Do not route temperature sensor wiring with building pow...

Страница 3: ...IRED GROUND TO GND TERMINAL ON W8900 GND C R RH RC C7189 W8900 S1 S S1 S Fig 2 Wiring Diagram for the C7189 Sensor to the W8900 Remote Module OPERATION The C7189 Wall Mount Temperature Sensor converts room temperature to a resistance that the controller can interpret The C7189 has a negative temperature coeffi cient NTC which means that the resistance decreases as the temperature increases Fig 3 s...

Страница 4: ... recalibrated in the field Home and Building Control Honeywell Inc 1985 Douglas Drive Golden Valley MN 55422 Fig 3 C7189 Sensor Resistance vs Temperature Performance Characteristics OHM RESISTANCE F C M6357 RESISTANCE DECREASES 18 6 OHMS PER 1 F CHANGE OR 33 4 OHMS PER 1 C CHANGE 1 1 2000 2100 1900 1500 1600 1700 1800 1400 TEMPERATURE 40 4 50 10 60 16 70 21 80 27 90 32 100 38 1300 1000 1200 2200 2...

Отзывы: