69-0895—1

4

C7189A WALL MOUNT TEMPERATURE SENSOR

Home and Building Control
Honeywell Limited-Honeywell Limitée
740 Ellesmere Road
Scarborough, Ontario
M1P 2V9

QUALITY IS KEY

Helping You Control Your World

69-0895—1  J.H.  Rev. 5-95   Printed in Mexico

CHECKOUT

Allow the C7189 Wall Mount Temperature Sensor to soak
in the air moving through the room for a minimum of five
minutes before taking a resistance measurement.

With an accurate thermometer (

±

1

°

F [0.5

°

C]), measure the

temperature at the sensor location, allowing time for the
thermometer to stabilize before reading. Remove one wire
from one of the C7189 wiring terminals. Use an ohmmeter
to measure the resistance across the sensor. Then verify
sensor accuracy with the temperature/resistance curve of
Fig. 3.

CALIBRATION

The C7189 Remote Sensor is calibrated at the factory and
cannot be recalibrated in the field.

Home and Building Control
Honeywell Inc.
1985 Douglas Drive
Golden Valley, MN 55422

Fig. 3. C7189 Sensor Resistance vs. Temperature Performance Characteristics.

OHM RESISTANCE

°F
(°C )

M6357

RESISTANCE DECREASES 18.6 OHMS PER 1°F 
CHANGE OR 33.4 OHMS PER 1°C CHANGE.

1

1

2000

2100

1900

1500

1600

1700

1800

1400

 TEMPERATURE

40

(4)

50

(10)

60

(16)

70

(21)

80

(27)

90

(32)

100

(38)

1300

1000

1200

2200

2300

46

48

50

52

54

56

58

60

62

64

66

68

70

72

74

76

78

80

82

84

86

88

90

92

94

96

98

100

7.8

8.9

10.0

11.1

12.2

13.3

14.4

15.6

16.7

17.8

18.9

20.0

21.1

22.2

23.3

24.4

25.6

26.7

27.8

28.9

30.0

31.1

32.2

33.3

34.4

35.6

36.7

37.8

2131 to 2094

2094 to 2057

2057 to 2019

2019 to 1982

1982 to 1945

1945 to 1908

1908 to 1871

1871 to 1833

1833 to 1796

1796 to 1759

1759 to 1722

1722 to 1685

1685 to 1647

1647 to 1610

1610 to 1573

1573 to 1536

1536 to 1499

1499 to 1461

1461 to 1424

1424 to 1387

1387 to 1350

1350 to 1313

1313 to 1275

1275 to 1238

1238 to 1201

1201 to 1164

1164 to 1127

1127 to 1089

ROOM TEMPERATURE

OHMS OF

RESISTANCE

°F

°C

Содержание C7189A

Страница 1: ...tallation is complete check out product operation as provided in these instructions CAUTION Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage Location and Mounting Locate the C7189 Wall Mount Temperature Sensor where the setting will not be subjected to tampering 1 Choose a location for the sensor on an inside wall about 5 ft 1 5 m above the floor A h...

Страница 2: ... not possible Ground the shielded cable to the GND terminal on the W8900 Important Erratic temperature readings from a sensor can occur as a result of any of the wiring practices described below These practices must be avoided to assure proper operation Use shielded cable to reduce interference if rerouting of sensor wiring is not possible a Do not route temperature sensor wiring with building pow...

Страница 3: ...IRED GROUND TO GND TERMINAL ON W8900 GND C R RH RC C7189 W8900 S1 S S1 S Fig 2 Wiring Diagram for the C7189 Sensor to the W8900 Remote Module OPERATION The C7189 Wall Mount Temperature Sensor converts room temperature to a resistance that the controller can interpret The C7189 has a negative temperature coeffi cient NTC which means that the resistance decreases as the temperature increases Fig 3 s...

Страница 4: ... recalibrated in the field Home and Building Control Honeywell Inc 1985 Douglas Drive Golden Valley MN 55422 Fig 3 C7189 Sensor Resistance vs Temperature Performance Characteristics OHM RESISTANCE F C M6357 RESISTANCE DECREASES 18 6 OHMS PER 1 F CHANGE OR 33 4 OHMS PER 1 C CHANGE 1 1 2000 2100 1900 1500 1600 1700 1800 1400 TEMPERATURE 40 4 50 10 60 16 70 21 80 27 90 32 100 38 1300 1000 1200 2200 2...

Отзывы: