9
EN1C-0015SZ20 R0602
IMPORTANT
The notch and arrow on the faceplate must be
aligned in a vertical plane with the notch up and
the arrow pointing down.
The housing must be mounted with the conduit
opening approximately 45° below horizontal (see
Fig. 7)
To mount a C7061A (Fig. 8):
A The mounting flange is in two pieces. Loosen (but do not
remove) the three screws holding the flange together.
Fig. 6. Vertical mounting of C7061A/F
Fig. 7. C7061A mounting Positions
Fig. 8. Mounting the C7061A detector
Fig. 9. Mounting the C7061F detector
B Slightly rotate the detector so the slots in the back section
of the mounting flange clear the screws in the front section;
then separate the two sections.
C Screw the front section of the mounting flange onto the
sight pipe, reducer, or other fitting.
D Fit the slots in the back section of the mounting flange
(with the detector) over the three screws in the front
section, and rotate the detector so the screws hold the
flange together.
E Tighten the screws securely.
IMPORTANT
The rivit on on the faceplate must be at the top
(see figure 9). The C7061F can be mounted with
increments of 120°.
The C7061F has a rivet on the blank alurninium holder. The
cell must be positioned so that this rivet is at the top of the
installed cell. In certain applications the sensor must be turned
in order accoomplish this.
To turn the C7061 (Figure 9).
A Loose the 3 screws between the pipe connection and
bottom part of.
B Turn the C7061F in the most favorable position.
C Tighten the screws securely.