background image

L8148A,E,J AQUASTAT® RELAYS

60-2278—9

4

Fig. 2. Internal view of L8148A Aquasta® Relay.

Fig. 3.  Internal view of L8148E Aquastat® Relay.

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

WARNING

Explosion Hazard.

Can cause severe injury, death or property 

damage.

This product is intended for use only in systems with a 

pressure relief valve.

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or equipment 

damage.

1. Disconnect power supply before beginning 

installation to prevent electrical shock or equipment 

damage.

2. Never apply a jumper across (or short) terminals 

B1, B2, or B3. This burns out the transformer.

Mounting (Standard Models)

Boilers have tappings to allow immersion well (which must be 

ordered separately) to be mounted horizontally so boiler water 

of average temperature can circulate freely around the well.

1.

Turn off all power and drain the boiler.

2.

If no tapping is provided, prepare one properly sized 

and threaded, and locate near the top of the boiler.

3.

Coat the well threads sparingly with pipe dope, install 

the well in the boiler tapping, and tighten securely.

NOTE: Do not attempt to tighten by using the case as 

a handle.

4.

Refill the boiler and check for water leakage.

5.

Increase sensitivity of the bulb by coating with a good 

heat-conductive compound. When used, coat the bulb 

completely.

6.

Insert the bulb element into the well until it bottoms. If 

necessary, slightly bend the tube inside the case to hold 

the bulb against the bottom of the well.

NOTE: Some models have a tubing length adjustable to 3 in. 

(76 mm). In these models, pull out extra tubing from 

inside the case, if needed.

7.

Center the loop of excess tubing in front of the 

immersion well so it cannot touch any electrical parts.

M8926

VOLTAGE
BARRIER

TRANSFORMER

SWITCHING
RELAY

HIGH
LIMIT
DIAL

M8927

TRANSFORMER

SWITCHING
RELAY

HIGH
LIMIT
DIAL

GROUNDING SCREW

Содержание Aquastat L8148A

Страница 1: ...or adding zone valve system wiring L8148E models are available with plug for connecting Aquastat Relay directly to D892 M892 Vent Dampers All devices include transformer to provide power for the low voltage control circuit Different models provide switching of line low or millivoltage burner circuit Case available for horizontal or vertical mounting Combinations of two insulation and two insertion...

Страница 2: ...92 M892 Vent Dampers 180 F to 240 F 82 C to 116 C scale range without well and spud L8148J Aquastat Relay with zone control terminals without well and spud See Fig 3 Scale Range 140 F to 240 F 60 C to 116 C Additional Features Heat conductive compound for better bulb response in oversized well For more information on heat conductive compound see Material Safety Data Sheet MSDS form 69 0955 Case ca...

Страница 3: ... Heat Anticipator Setting 0 2A Standard Scale Range 180 F to 240 F 82 C to 116 C Differential Nonadjustable Finish Gray enamel Optional Specifications Scale Range 140 F to 240 F 60 C to 116 C High Limit Dial Stop Case Dimensions See Fig 1 Accessories 107408 Heat Conductive Compound 4 oz can For more information see form 69 0955 Heat Conductive Compound 124904 Well Adapter For ordering information ...

Страница 4: ...andard Models Boilers have tappings to allow immersion well which must be ordered separately to be mounted horizontally so boiler water of average temperature can circulate freely around the well 1 Turn off all power and drain the boiler 2 If no tapping is provided prepare one properly sized and threaded and locate near the top of the boiler 3 Coat the well threads sparingly with pipe dope install...

Страница 5: ...ls extra tubing inside the case can be pulled out if needed 4 Make sure the wide end of the adapter fits into the hole in the case Position the immersion well clamp snugly over the flange on the adapter and tighten the clamp screw 5 Insert the sensing bulb into the well as shown in Fig 4 Distribute heat conductive compound prior to insertion 6 Securely tighten setscrew if present on old well again...

Страница 6: ...ansformer must be used to power zone valves CONTROLLER CASE IMMERSION WELL CLAMP ADAPTER IMMERSION WELL SPUD BOILER OLD IMMERSION WELL ASSEMBLY BACK OF CONTROLLER CASE IMMERSION WELL CLAMP SCREW ADAPTER SENSING BULB HEAT CONDUCTIVE COMPOUND SETSCREW CAPILLARY TUBE C IMMERSION WELL CLAMP IMMERSION WELL CLAMP SCREW SHORT TUBE FITS IN CENTRAL RECESS OF ADAPTER BEND THE CAPILLARY TUBE TO HOLD THE SENS...

Страница 7: ...T MEANS AND OVERLOADPROTECTION AS REQUIRED REMOVE JUMPER WHEN ADDING L6006 LOW LIMIT CONTROLLER CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED B1 IS 1 4 IN TAB TERMINAL 1 2 3 4 4 1 2 3 M2842A L8148A 4 T T 1 2 3 4 5 6 T T 1 2 3 4 5 6 T T 1 2 3 4 5 6 G L2 L1 T T C1 C2 B2 B1 F F T T L1 HOT L2 PUMP PUMP PUMP T87F T87F T87F R845 RELAY R845 R845 C554 R8184G BURNER AND IGNITI...

Страница 8: ... L2 L1 L1 G G Z Z W T T TV TV B1 B1 B2 B2 C1 C1 C2 C2 R R R B B B W W M1621B L1 HOT L1 HOT L2 L2 1 1 2 4 3 TO LOW VOLTAGE BURNER CIRCUIT TR TH TH TR T87F ZONE 3 T87F ZONE 2 T87F ZONE 1 L8148E CIRCULATOR HIGH LIMIT L2 L1 G Z T TV B1 B2 C1 C2 R B W END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIR...

Страница 9: ...PROTECTION AS REQUIRED CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED B1 IS 1 4 IN TAB TERMINAL 1 2 3 3 L8148E 2 1 M1620A LOW VOLTAGE GAS VALVE eg VR8300 TR TH THTR L1 HOT L2 1 2 3 1 2 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED B1 IS 1 4 IN TAB TERMINALS M8888 T...

Страница 10: ...MV MV PV PV GND BURNER 24V GND 24V TH W SPARK VENT DAMPER PLUG THERMOSTAT L8148E STANDARD MODELS G L1 1K2 HIGH LIMIT L2 Z W 1K T TV B1 C1 B2 C2 VR8304 WIRING HARNESS D892 M892 B R 1K1 M2298D PV PV MV MV 24V GND 24V S8600 L1 HOT L2 1 1 2 3 4 5 L8148E 4 2 3 FUSE 5 1 2 3 5 6 PRONG FEMALE MOLEX RECEPTACLE IN L8148E AND 5 PRONG MALE MOLEX PLUG ON CABLE 1K1 B1 B2 L1 C1 C2 L2 CIRCULATOR POLARIZED 4 PRONG...

Страница 11: ...LVE PP PP TH2 TH1 W R R R B B B 24V THERMOSTAT L8148J CIRCULATOR G G L1 L1 L2 B3 B2 B1 HIGH LIMIT TP TV T W Z C1 C2 TR TH THTR LOW VOLTAGE GAS VALVE eg VR8300 1K3 TP Z W T TV 1K2 AUTO MANUAL SWITCH 1K1 C1 C2 B3 B2 B1 L2 L8148J M1793B TV T W W Z B1 B2 C1 C2 L1 L2 G L8148 CIRCULATOR ZONE 1 CIRCULATOR ZONE 2 CIRCULATOR ZONE 3 L1 HOT L2 1 2 3 4 5 6 1 2 3 4 5 4 6 POWER SUPPLY PROVIDE DISCONNECT MEANS A...

Страница 12: ...at the relay contacts make to complete the line voltage circulator circuit and also the burner circuit when the boiler water temperature is below the high limit The high limit switch shuts off the burner if boiler water temperature exceeds the high limit setting The AUTO MANUAL switch only L8148J millivolt models operates the burner during electrical power failure With the switch at MANUAL the bur...

Отзывы: