L8148A,E,J AQUASTAT® RELAYS

60-2278—9

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Home and Building Control Sales Office (check white pages of your phone directory).

2.

Home and Building Control Customer Relations

Honeywell, 1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not 

include normal manufacturing tolerances. Therefore, 

this unit may not exactly match the listed 

specifications. Also, this product is tested and 

calibrated under closely controlled conditions, and 

some minor differences in performance can be 

expected if those conditions are changed.

TRADELINE® Models

TRADELINE® models are selected and packaged for ease of 

handling, ease of stocking, and maximum replacement value. 

TRADELINE® model specifications are the same as those of 

standard models except as noted below.

TRADELINE® Models Available:

• L8148A Aquastat¨ Relay, without zone control terminals, 

without well and spud. See Fig. 2.

• L8148E Aquastat¨ Relay with Molex® plug for use with 

D892/M892 Vent Dampers; 180°F to 240°F (82°C to 

116°C) scale range; without well and spud.

• L8148J Aquastat¨ Relay with zone control terminals; 

without well and spud. See Fig. 3.

Scale Range:  

140°F to 240°F (60°C to 116°C).

Additional Features:

• Heat-conductive compound for better bulb response in 

oversized well. For more information on heat-conductive 

compound, see Material Safety Data Sheet (MSDS), form 

69-0955.

• Case can be vertically or horizontally mounted. 

• High-limit dial stop is factory-set at end of high-limit scale; 

can be adjusted.

• TRADELINE® pack with cross reference label and special 

instructions.

Standard Models

Models:  

See Table 2.

Electrical Ratings:

Table 1. Circulator Control Circuit (Amperes).

Voltage and Frequency: 120 Vac, 60 Hz.

Burner Control Circuits:

Line Voltage: Ratings same as for circulator above.

Low Voltage: 0.8A maximum at 24 Vac.

Millivoltage: 0.25A at 1/4 to 12 Vdc.

Approvals:

Underwriters Laboratories Inc. Listed: File No. MP466, Guide 

No. MBPR (models with well); Guide No. MBPR2 (models 

without well).

Canadian Standards Association Certified: File No. LR1620, 

Guide No. 400-E-O.

ANSI Miswiring: Models with 1/4 in. tab terminal meet ANSI 

Appliance Miswiring Standard.

Immersion Well Dimensions: 

Brass Spud for Boiler Fitting: 1/2 or 3/4 NPT.

Insulation Depth: 1-1/2 or 3 in. (38 or 76 mm).

NOTE: Not all models include wells. If well is not included 

but is needed, refer to form 68-0040 to order.

Insertion Length:  

3-3/8 in. (86 mm).

Maximum Pressure On Immersion Well:  

255 psi (1758 kPa).

Maximum Bulb Temperature:

40°F higher than setpoint, or up to 265°F (23°C higher than 

setpoint, or up to 129°C).

Material Safety Data Sheets (MSDS): 

For more information 

on heat-conductive compound, see form 69-0955.

Maximum Ambient Temperature:

150°F (66°C) with 1.2A, 24V load.

77°F (25°C) with 1.4A, 24V load.

Type

120 Vac

240 Vac

Full Load

7.4

3.7

Locked Rotor

44.4

22.7

Содержание Aquastat L8148A

Страница 1: ...or adding zone valve system wiring L8148E models are available with plug for connecting Aquastat Relay directly to D892 M892 Vent Dampers All devices include transformer to provide power for the low voltage control circuit Different models provide switching of line low or millivoltage burner circuit Case available for horizontal or vertical mounting Combinations of two insulation and two insertion...

Страница 2: ...92 M892 Vent Dampers 180 F to 240 F 82 C to 116 C scale range without well and spud L8148J Aquastat Relay with zone control terminals without well and spud See Fig 3 Scale Range 140 F to 240 F 60 C to 116 C Additional Features Heat conductive compound for better bulb response in oversized well For more information on heat conductive compound see Material Safety Data Sheet MSDS form 69 0955 Case ca...

Страница 3: ... Heat Anticipator Setting 0 2A Standard Scale Range 180 F to 240 F 82 C to 116 C Differential Nonadjustable Finish Gray enamel Optional Specifications Scale Range 140 F to 240 F 60 C to 116 C High Limit Dial Stop Case Dimensions See Fig 1 Accessories 107408 Heat Conductive Compound 4 oz can For more information see form 69 0955 Heat Conductive Compound 124904 Well Adapter For ordering information ...

Страница 4: ...andard Models Boilers have tappings to allow immersion well which must be ordered separately to be mounted horizontally so boiler water of average temperature can circulate freely around the well 1 Turn off all power and drain the boiler 2 If no tapping is provided prepare one properly sized and threaded and locate near the top of the boiler 3 Coat the well threads sparingly with pipe dope install...

Страница 5: ...ls extra tubing inside the case can be pulled out if needed 4 Make sure the wide end of the adapter fits into the hole in the case Position the immersion well clamp snugly over the flange on the adapter and tighten the clamp screw 5 Insert the sensing bulb into the well as shown in Fig 4 Distribute heat conductive compound prior to insertion 6 Securely tighten setscrew if present on old well again...

Страница 6: ...ansformer must be used to power zone valves CONTROLLER CASE IMMERSION WELL CLAMP ADAPTER IMMERSION WELL SPUD BOILER OLD IMMERSION WELL ASSEMBLY BACK OF CONTROLLER CASE IMMERSION WELL CLAMP SCREW ADAPTER SENSING BULB HEAT CONDUCTIVE COMPOUND SETSCREW CAPILLARY TUBE C IMMERSION WELL CLAMP IMMERSION WELL CLAMP SCREW SHORT TUBE FITS IN CENTRAL RECESS OF ADAPTER BEND THE CAPILLARY TUBE TO HOLD THE SENS...

Страница 7: ...T MEANS AND OVERLOADPROTECTION AS REQUIRED REMOVE JUMPER WHEN ADDING L6006 LOW LIMIT CONTROLLER CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED B1 IS 1 4 IN TAB TERMINAL 1 2 3 4 4 1 2 3 M2842A L8148A 4 T T 1 2 3 4 5 6 T T 1 2 3 4 5 6 T T 1 2 3 4 5 6 G L2 L1 T T C1 C2 B2 B1 F F T T L1 HOT L2 PUMP PUMP PUMP T87F T87F T87F R845 RELAY R845 R845 C554 R8184G BURNER AND IGNITI...

Страница 8: ... L2 L1 L1 G G Z Z W T T TV TV B1 B1 B2 B2 C1 C1 C2 C2 R R R B B B W W M1621B L1 HOT L1 HOT L2 L2 1 1 2 4 3 TO LOW VOLTAGE BURNER CIRCUIT TR TH TH TR T87F ZONE 3 T87F ZONE 2 T87F ZONE 1 L8148E CIRCULATOR HIGH LIMIT L2 L1 G Z T TV B1 B2 C1 C2 R B W END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIR...

Страница 9: ...PROTECTION AS REQUIRED CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED B1 IS 1 4 IN TAB TERMINAL 1 2 3 3 L8148E 2 1 M1620A LOW VOLTAGE GAS VALVE eg VR8300 TR TH THTR L1 HOT L2 1 2 3 1 2 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED B1 IS 1 4 IN TAB TERMINALS M8888 T...

Страница 10: ...MV MV PV PV GND BURNER 24V GND 24V TH W SPARK VENT DAMPER PLUG THERMOSTAT L8148E STANDARD MODELS G L1 1K2 HIGH LIMIT L2 Z W 1K T TV B1 C1 B2 C2 VR8304 WIRING HARNESS D892 M892 B R 1K1 M2298D PV PV MV MV 24V GND 24V S8600 L1 HOT L2 1 1 2 3 4 5 L8148E 4 2 3 FUSE 5 1 2 3 5 6 PRONG FEMALE MOLEX RECEPTACLE IN L8148E AND 5 PRONG MALE MOLEX PLUG ON CABLE 1K1 B1 B2 L1 C1 C2 L2 CIRCULATOR POLARIZED 4 PRONG...

Страница 11: ...LVE PP PP TH2 TH1 W R R R B B B 24V THERMOSTAT L8148J CIRCULATOR G G L1 L1 L2 B3 B2 B1 HIGH LIMIT TP TV T W Z C1 C2 TR TH THTR LOW VOLTAGE GAS VALVE eg VR8300 1K3 TP Z W T TV 1K2 AUTO MANUAL SWITCH 1K1 C1 C2 B3 B2 B1 L2 L8148J M1793B TV T W W Z B1 B2 C1 C2 L1 L2 G L8148 CIRCULATOR ZONE 1 CIRCULATOR ZONE 2 CIRCULATOR ZONE 3 L1 HOT L2 1 2 3 4 5 6 1 2 3 4 5 4 6 POWER SUPPLY PROVIDE DISCONNECT MEANS A...

Страница 12: ...at the relay contacts make to complete the line voltage circulator circuit and also the burner circuit when the boiler water temperature is below the high limit The high limit switch shuts off the burner if boiler water temperature exceeds the high limit setting The AUTO MANUAL switch only L8148J millivolt models operates the burner during electrical power failure With the switch at MANUAL the bur...

Отзывы: