background image

® U.S. Registered Trademark

EN0B-1023 GE02R0700

Copyright © 2000 Honeywell Inc. • All rights reserved

AQS51/61-KAM

COMBINED CO

2

-/TEMPERATURE

DUCT SENSOR/CONTROLLER

PRODUCT DATA

GENERAL

The AQS51-KAM and AQS 61-KAM sensors/controllers for

duct mounting measure the carbon dioxide (CO

2

) con-

centration and the temperature in the return or outside air.

They are used in ventilation and air conditioning systems to

control the amount of fresh outside air being supplied to the

occupants for acceptable indoor air quality and to reduce

unnecessary conditioning of outside air during low-

occupancy periods.
This Demand Controlled Ventilation (DCV) is a cost effective

solution to conserve energy and to ensure that the fresh

outside air supplied is no more than is necessary to meet the

actual requirements of the occupants at any given time.
The sensors/controllers offer separate 0(2)...10Vdc or

0(4)...20mA outputs for CO

 and temperature and in addition

a digital ON/OFF relay output with switching hysteresis for

alarm or other purposes.
The UART interface (RS232) for serial communication allows

a PC to be connected in order to perform maintenance

checks or reconfigurations during normal operation. If used

as a controller, each of these outputs can be configured to

provide a more complex ventilation strategy based on a

mixture of CO

2

 plus temperature measurements and to

assign a number of functions, including hierarchy.

For this analog output configuration, the software program

STRATEGY is available, which is part of the User Interface

Program Software package AQS-USP22 used for re-

calibration, change of the measurement range or other

service or set-up purposes.
The switching setpoint and differential of the relay output for

CO

2

 limit monitoring or plant/system ON/OFF control can be

adjusted within the measurement range. This output can be

used also as automatic fire threshold to switch off ventilation,

when CO

2

 levels exceed normal limit of e. g. 2500 ppm in

case of fire.

FEATURES

 

CO

2

 measurement range 0...3000 ppm corresponding

to 0...0.3% CO

2

. Factory-calibrated 0...2000 ppm

 

Multifunctional unit for temperature and CO

2

-

measurement or control

 

State-of-the-art Non-Dispersion-Infrared (NDIR)

technology to measure carbon dioxide gas

 

Automatic drift correction (ABC-algorithm) based on a

long term evaluation provides typical zero drift check

maintenance-intervals of up to 5 years

 

Standard output signals 0(2)...10 Vdc or 0(4)...20 mA

each for CO

2

 and temperature measurement or control

 

Programmable mixed controller signal output(s)

provides ventilation control strategies to match

exactly the application requirements

 

Digital ON/OFF relay output for CO

2

 limit monitoring

 

RS232 interface for configuration, parameter setting

or data exchange with a PC using Windows 95/98

 

User interface program on diskette for service,

recalibration and change of measurement ranges

 

Optional with 4-digit LCD display with the selectable

indication of:

 

- CO

2

 and room temperature alternating

- Error code

- CO

2

-concentration (ppm)

- Temperature (

°°°°

C)

- Analog Output1

- Analog Output2

Содержание AQS51-KAM

Страница 1: ...s analog output configuration the software program STRATEGY is available which is part of the User Interface Program Software package AQS USP22 used for re calibration change of the measurement range or other service or set up purposes The switching setpoint and differential of the relay output for CO2 limit monitoring or plant system ON OFF control can be adjusted within the measurement range Thi...

Страница 2: ...D indication Yellow Maintenance required Red Relay activated Power up time 1 min Ambient operating limits Temperature 0 50 C General Humidity 0 95 rh non condensing Operating principle Non dispersive infrared NDIR Gas sampling mode Diffusion and 3 mm gas inlet push on barb Response time 2 min diffusion or 10 sec 0 2 ltr min gas flow Measurement range 0 3000 ppm Converting range 0 2000 ppm 0 10 Vdc...

Страница 3: ...using the PC software STRATEGY Version 3 Digital relay output Single pole double throw SPDT switching potential free contact Factory adjusted switching setpoint and differential 1A 50 Vac 50VA or 1 A 24 Vdc 30 W Relay activated 1000 ppm Relay deactivated 900 ppm Sensor housing 84 x 142 x 46 mm Dimensions Sampling probe 203 mm Zigzag traces accessible after removing the cover Shortage with a screwd...

Страница 4: ...ions to provide different ventilation control strategies All sensor measurements can be addressed to these functions and mixed together by this software to form two independent and intelligent P I controllers The relay output contact CM NO is closed if the CO2 level exceeds the factory adjusted limit of 1000ppm and the contact CM NC is closed if the CO2 level is equal or below 900ppm These paramet...

Страница 5: ...Pos 7 cable entry bushings To make a hole insert a screwdriver into the groove and hit firmly Mount for each cable a cable entry bushing into the aspiration box and seal properly 7 Mounting the aspiration box to the sampling probe is performed by a snap in bayonet fitting Pos 10 Insert first the temperature sensor placed on the end of a 150mm long soldered on lead Fig 3 Pos 2 into the air inlet to...

Страница 6: ...G0 permitting a 3 wire configuration A single transformer may be used for the entire system Situations can occur where different transformers must be used NOTE2 AQS51 61 can supply both a voltage or a current output for OUT1 OUT2 To change between voltage and current output mode the hardware jumpers have to be set in accordance There is one jumper for AN1 and one for AN2 so that one output can be ...

Страница 7: ...2 Error code 3 CO2 concentration in ppm 4 Temperature in C 5 OUT1 value full scale 6 OUT2 value full scale To access the maintenance level short at level 5 OUT1 value ENTER MENU ENTER in sequence The maintenance mode is restricted to competent trained service personnel only For detailed information see the Service Checkout Instruction EN2B 0461GE02 LED Signals The standard sensor has two different...

Страница 8: ...sor probes are checked against failure by checking the valid dynamic measurement ranges Error Code and Actions Error Code Suggested Action 4 Indicate problems with the power supply Check power supply voltage 8 Indicates problem with OUT1 Could be too high an output load connected to the output Check OUT1 with a voltmeter and compare the output with the LCD reading for AQS61 KAM Disconnect the outp...

Отзывы: