WIRING FOR BURG/FIRE INSTALLATIONS 

Refer to Terminal Descriptions on Page 1, and connect 
the panel bell output directly to the appropriate terminals.   

 

1.  ANNUNCIATING CO ALARM ON   
VISTA P Series 

(21iP/20P/15P/10P, variants)

  

a.  Hookup 

To achieve proper operation for Carbon Monoxide 
alarms with VISTA panels, configure the 745VSD3 for a 
negative (0V)  trigger by setting DIP Switch 8 to OFF.  
On the panel, configure a low-going output (Trigger 17) 
to alert on CO alarm. Connect 745VSD3 as shown: 

2

3

4

5

6

1

ON

7

8

SW 1

1

2

3

4

5

6

7

8

8

1

OUTPUT TRIGGER  HARNESS

TO 12 VOLT SOURCE

8-. 16-, or 
32-OHM 
SPEAKER

NOTE:  32-OHM SPEAKER 
REQUIRED FOR ETL
LISTED INSTALLATIONS

GROUND (-)

+12V

BELL

CO

FI/B

GR

OUND

T

O

 TRIGGER

VISTA 20P/15P/10P
CONTROL PANEL

745VSD3

745VSD3-002-V0

Set DIP Switch
 #8 to OFF

 

Figure 2:  VISTA P Series CO Trigger Configuration 

b. Programming Trigger Output (Vista P Series) 

1.  Enter panel’s Program mode. 
2.  Select field *79  

ƒ

 

*79 Enter Output No (enter 17) *  

ƒ

 

17 OUT Norm Low? (enter 0) *  

3.  Enter Output  No (enter 00) exits out of *79 menu. 
4.  Enter  *80 Output Function #  menu programming mode.   
5.  Configure the first Output function for the following: 

ƒ

 

Activated by Zone type option selection (2) 

ƒ

 

Enter Zone Type (14) Carbon Monoxide 

ƒ

 

Output Action Stay Closed selection  (2) 

ƒ

 

Output Number Select (17) 

6.  Configure the second Output function for the following: 

ƒ

 

Activated by Zone type option selection (2) 

ƒ

 

Enter Zone Type (22) Disarm 

ƒ

 

Output Action Off selection  (0) 

ƒ

 

Output Number Select (17) 

7.  Exit the panel’s Programming mode. 

 

2.  ANNUNCIATING CO ALARM ON  
VISTA-32, -128, -250  (and  variants) 

a.  Hookup 

If using a VISTA-32, -128, -250, or other variant that 
supports CO Zone Response Type 14
:  Configure 
7845VSD3 for a positive (+12V) trigger by setting DIP 
Switch 8 to ON.  On the panel, configure a relay output 
(4204/4101SN)) to alert on Zone Response Type 14.  
Connect 745VSD3 as shown: 
 

2

3

4

5

6

1

ON

7

8

SW 1

1

2

3

4

5

6

7

8

1

8

TO 12 VOLT SOURCE

8-. 16-, or 
32-OHM 
SPEAKER

NOTE:  32-OHM SPEAKER 
REQUIRED FOR ETL
LISTED INSTALLATIONS

GROUND (-)

+12V

CO

FI/B

745VSD3

TB2

12

11

10

9

8

7

6

5

4

3

2

1

(–) GROUND 

(+) 12V 

YEL

BLK

GRN

RED

13

14

15

16

DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER  

COVER TAMPER (REED) SWITCH

TB1

4204

4-PIN TOUCHPAD PLUG

3

2

RELAY

1

4

RELAY CONTACTS ARE

NOT SUPERVISED

TYPICAL

(SHOWN "OFF")

C

NC

NO

C

NC

NO

C

NC

NC

NO

C

NC

NO

EITHER OR BOTH
CAN BE USED

DATA IN
FROM CONTROL

DATA OUT
TO CONTROL

RELAY

RELAY

RELAY

4204 CONNECTIONS

Program Relay to Activate
on Zone Response Type 14 (CO)

745VSD3-003-V0

Set DIP Switch
 #8 to ON

 

Figure 3:  High End VISTA Configuration  

(4204 Relay shown) 

 

b. Programming Output (High End Vista) 

Refer to the diagram above, the terminal descriptions on 
Page 1, and the programming data for the panel and 
selected relay/output module to configure the activation 
and restore for Zone Response Type 14 (Carbon 
Monoxide). 
 

3.  ANNUNCIATING CO ALARM ON ALL 
OTHER PANELS 

Refer to the installation documentation for the control 
panel and to the “Terminal Descriptions” table on the 
previous page to properly connect and configure 
745VSD3.

 

Содержание ADEMCO 745VSD3

Страница 1: ...PUT Connect to 12VDC source on panel See Fused Method for Providing Battery Power on Page 3 if needed 3 SPKR 4 SPKR SPEAKER TERMINALS Connect 8 16 or 32 ohm 15 watt speaker See Figure 6 for multiple speaker config urations For Listed installations Listed Ademco 705 820 713 or 746 32 speakers must be used 5 F FIRE INPUT Connect the control panel s output designated as the FIRE steady output to this...

Страница 2: ...on Off selection 0 Output Number Select 17 7 Exit the panel s Programming mode 2 ANNUNCIATING CO ALARM ON VISTA 32 128 250 and variants a Hookup If using a VISTA 32 128 250 or other variant that supports CO Zone Response Type 14 Configure 7845VSD3 for a positive 12V trigger by setting DIP Switch 8 to ON On the panel configure a relay output 4204 4101SN to alert on Zone Response Type 14 Connect 745...

Страница 3: ...tches 5 8 SW1 switches 5 through 8 set bell test and trigger options as shown 2 3 4 5 6 1 ON 7 8 BELL TEST RINGBACK OPTIONS MUST BE ON FOR LISTED INSTALLATIONS BURG FIRE TRIGGER ON POSITIVE 12V TRIGGER OFF NEGATIVE 0V TRIGGER FIRE TRIGGER ON POSITIVE 12V TRIGGER OFF NEGATIVE 0V TRIGGER CARBON MONOXIDE TRIGGER ON POSITIVE 12V TRIGGER OFF NEGATIVE 0V TRIGGER 745VSD3 005 V0 Figure 4 SW1 Switches 5 8 ...

Страница 4: ...peaker 500mA max steady siren WARRANTY INFORMATION For the latest warranty information please go to http www security honeywell com hsc resources wa index html REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL THAT IS USED WITH THIS DEVICE FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE ALARM SYSTEM 2 Corporate Center Drive Suite 100 P O Box 9040 Melville NY 11747 Copyright 2009 ...

Отзывы: