K6210V1  2/09   Rev. C 

 

ADEMCO 745VSD3 

Voice Siren Driver

 

INSTALLATION AND SETUP GUIDE 

FEATURES 

  Generates siren as well as voice output in English, 

Spanish, and French.   

  Separate messages for FIRE, BURGLARY, and 

Carbon Monoxide (CO) conditions.   

  Separate siren sounds for FIRE, BURGLARY, and 

Carbon Monoxide conditions.   

  Terminal strip for secure connection to control panel.   

  Selectable input level (High/Low) for 

FIRE/BURGLARY/CO inputs.   

  Supervision feature for speaker and speaker wiring.   

  Compatible with 8 - 32 ohm speakers.   

  Operates on 12-16V DC; 15mA standby current draw  

  Small compact size for easy installation using double-

sided tape provided – measures 4” x 2-3/4” x 1-3/4”.  

 
NOTE:  745VSD3 annunciates alarms in the following 
priority order:  FIRE, Carbon Monoxide (CO), Burglary. 

 
WIRING CONNECTIONS 

IMPORTANT: 745VSD3 must be mounted in the control 
cabinet.  Wiring connections to the terminals are as 
follows:  

 

23

4

5

6

1

ON

78

745VSD3-001-V0

SW 1

1

2

3

4

5

6

7

8

- GROUND

+ POWER

SPEAKER

SPEAKER

FIRE INPUT

BURG/FIRE INPUT

CARBON MONOXIDE INPUT

SPEAKER SUPERVISION

8

1

VOICE/SIREN 
SELECTIONS 

(SEE TEXT)

 

 

 

Figure 1:  745VSD3 Voice Siren Driver Circuit Board 

 

TERMINAL DESCRIPTIONS 

 

Term

Function Notes 

1 (-) 

GND(-) 
GROUND 
INPUT 

Connect to panel’s  
aux power (-)  

2 (+) 

12VDC(+) 
INPUT 

Connect to 12VDC (+)  
source on panel.  

See “Fused 

Method for Providing Battery 
Power” on Page 3 if needed. 


SPKR 

SPKR 

SPEAKER 
TERMINALS 

Connect 8- , 16- , or 32-ohm 
15-watt speaker.  See Figure 6 
for multiple speaker config-
urations. 

 For Listed 

installations, Listed Ademco 
705-820, 713, or 746-32 
speakers must be used. 

5 F 

FIRE INPUT 

Connect the control panel’s 
output designated as the FIRE 
(steady) output to this terminal 
(unless this output was 
connected to terminal 6). 

6 B/F 

BURGLARY/ 
FIRE INPUT 

Connect the control’s Burglary 
(steady) output to this terminal. 
This terminal may also be 
used to trip the Fire message 
(or siren sounds) with a 
Temporal Fire signal input. For 
these secondary uses, no 
connection to terminal 5 is 
required. 

7 CO 

CARBON 
MONOXIDE 
INPUT 

Connect the control’s output 
designated as the Carbon 
Monoxide output to this 
terminal. 


SUPV 

SPEAKER/ 
WIRING 
SUPERVISION 
(OPTIONAL) 

To supervise speaker and 
associated wiring, connect to 
the high (+) side of a 24-hour 
zone that is activated by a 
short.  Disconnecting or 
shorting either speaker 
terminal to ground will appear 
as a short on the zone. Note 
that in series-connected 
multiple speaker systems, 
cutting any speaker will trip the 
panel’s supervision zone.  In 
parallel-connected speaker 
systems, each branch must be 
cut before the control’s 
supervision zone will trip.   
NOTE: Check the control’s 
documentation for supervision 
compatibility (most Honeywell 
controls are compatible.)   

Содержание ADEMCO 745VSD3

Страница 1: ...PUT Connect to 12VDC source on panel See Fused Method for Providing Battery Power on Page 3 if needed 3 SPKR 4 SPKR SPEAKER TERMINALS Connect 8 16 or 32 ohm 15 watt speaker See Figure 6 for multiple speaker config urations For Listed installations Listed Ademco 705 820 713 or 746 32 speakers must be used 5 F FIRE INPUT Connect the control panel s output designated as the FIRE steady output to this...

Страница 2: ...on Off selection 0 Output Number Select 17 7 Exit the panel s Programming mode 2 ANNUNCIATING CO ALARM ON VISTA 32 128 250 and variants a Hookup If using a VISTA 32 128 250 or other variant that supports CO Zone Response Type 14 Configure 7845VSD3 for a positive 12V trigger by setting DIP Switch 8 to ON On the panel configure a relay output 4204 4101SN to alert on Zone Response Type 14 Connect 745...

Страница 3: ...tches 5 8 SW1 switches 5 through 8 set bell test and trigger options as shown 2 3 4 5 6 1 ON 7 8 BELL TEST RINGBACK OPTIONS MUST BE ON FOR LISTED INSTALLATIONS BURG FIRE TRIGGER ON POSITIVE 12V TRIGGER OFF NEGATIVE 0V TRIGGER FIRE TRIGGER ON POSITIVE 12V TRIGGER OFF NEGATIVE 0V TRIGGER CARBON MONOXIDE TRIGGER ON POSITIVE 12V TRIGGER OFF NEGATIVE 0V TRIGGER 745VSD3 005 V0 Figure 4 SW1 Switches 5 8 ...

Страница 4: ...peaker 500mA max steady siren WARRANTY INFORMATION For the latest warranty information please go to http www security honeywell com hsc resources wa index html REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL THAT IS USED WITH THIS DEVICE FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE ALARM SYSTEM 2 Corporate Center Drive Suite 100 P O Box 9040 Melville NY 11747 Copyright 2009 ...

Отзывы: