background image

2    

Honeywell Sensing and Control

Enclosed Basic Series Limit Switches

ISSUE 5

  

 

88173

FIELD ADJUSTABLE ACTUATOR MODELS

Some enclosed basic switches are field adjustable. This in-

cludes models with the nomenclature “2RN2”, ”2RQ2”, ”2RN28”, 
”2RQ28”, “2RN62”, “2RQ62”, “RQ2X2”, “RN2X1”. 

ADJUSTABLE RANGE

ADJUSTABLE RANGE

360~ ABOUT THE PLUNGER AXIS

LEVER BASE

RETAINING NUT

LEVER

RETAINING NUT

 The lever can be adjusted in two ways. The following process 
details how to perform the adjustments.

Adjusting the horizontal position of the lever. 

1.   Loosen the lever base retaining nut, so that the lever assem

-

bly is free to rotate about the axis of the plunger.

2.   Rotate the lever to the desired position. The lever is adjust

-

able 360 degrees about the axis.

3.   Once the desired position is reached re-tighten the lever 

base retaining nut. The lever base should not be able to 
rotate when properly tightend. 

Adjusting the vertical position of the lever.

1.   Loosen the lever retaining nut, so that the lever freely rotates. 
2.  Set the position of the lever to the desired position. Roller 

levers should be positioned so that they are able to actuate 
the plunger. 

3.   Once the desired position is reached re-tighten the lever re-

taining nut. When pushed the lever should act upon the lever 
mechanism to actuate the switch.  

N18 TYPES

If actuator or basic switch is replaced, the actuator may need 
adjustment to duplicate original switch operating point. To adjust 
operating point, remove lower seal band from base of seal boot. 

“Peel back” seal boot to expose bushing. With basic switch 

unoperated, 

slowly turn bushing clockwise until basic switch op-

erates. 

Do not turn further after operating click is heard. 

Turn 

bushing back 1/2 turn. Tighten jam nut on bushing.

MAINTAINED CONTACT (RESET) MODELS

Listings with an “X” in their part number are maintained contact 

switches. These switches remain actuated after the operating 
force on either plunger has been applied. The actuated plunger 

will “reset” when the opposing plunger is actuated. 

NOTE: The top plungers (the plungers on the stationary portion 
of the housing) provide more accurate and uniform operation 

than the “reset” plungers and should be used when closely held 

operating characteristics are required.  

Vertical Adjustment Range

N2 & Q2 - Roller lever

225°

To adjust: loosen

hex nut, adjust arm

to desired position,

tighten hexnut.

N4 & Q4 - Hand op.

180°

N62 & Q62 - Rod lever

225°

N28 & Q28 - One way

180°

1.  One lever arm serration: 8.18°.
2.  One serration of lever arm and fluted washer as a unit: 8°.

3.  One serration of lever arm with one serration of fluted washer 

in opposite direction: 0.18°.

LUBRICATING INSTRUCTIONS for Roller Plunger 
Switches only (N80, N81, Q8, Q9, Q81)

For maximum life, periodically put a drop or two of lightweight 

oil on the roller. Specific application conditions will determine 
lubricating frequency.

Содержание 88173

Страница 1: ...age of this document MOUNTING 1 Mount switches on flat rigid surface E6 Side Mounting Pattern 25 4 mm 1 00 in 2X CLEARANCE HOLE FOR 6 MOUNTING SCREW E6 SIDE MOUNTING V6 Flange Mounting Pattern 41 6 mm 1 63 in 2X Ø 4 3 mm 0 17 in MOUNTING HOLES V6 FLANGE MOUNTING G1 Side Mounting Pattern 31 0 mm 1 22 in 75 0 mm 2 95 in 2X Ø 5 5 mm 0 216 in MOUNTING HOLES G1 SIDE MOUNTING H1 Flange Mounting Pattern ...

Страница 2: ...or or basic switch is replaced the actuator may need adjustment to duplicate original switch operating point To adjust operating point remove lower seal band from base of seal boot Peel back seal boot to expose bushing With basic switch unoperated slowly turn bushing clockwise until basic switch op erates Do not turn further after operating click is heard Turn bushing back 1 2 turn Tighten jam nut...

Страница 3: ... Remove the cover or the flange base by loosening the two screws that secure it Once the cover of the flange base is removed the switch terminals will be exposed Switch terminals will be labeled according to the contact they connect to Please refer the terminal layout section for more information on circuit dia grams and terminal screw layout Connect wire to terminals by loosening terminal screws ...

Страница 4: ...PA41 N62 actuators rod lever 6PA140 E6 Q62 actuators rod lever 6PA62 N4 actuators manual button 6PA9 Q4 actuators manual button 6PA7 N18 actuators spring 6PA195 N18 actuators spring and bushing 6PA187 E6 Conduit seal 2PA1 2PA6 2PA16 Seal boot black elastomer 10PA2 Seal boot orange silicon 10PA1 Bottom cover E6 3PA13 E6 Bottom cover V6 3PA14 V6 Pilot light for BZG H 15LT1 Conduit Sealing Packets Pa...

Страница 5: ...cular purpose In no event shall Honeywell be liable for consequential special or indirect damages While we provide application assistance personally through our literature and the Honeywell web site it is up to the customer to determine the suitability of the product in the application Specifications may change without notice The information we supply is believed to be accurate and reliable as of ...

Страница 6: ...onics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information Honeywell 2PA17 6PA104 6PA105 6PA106 6PA107 6PA108 6PA109 6PA111 6PA112 6PA113 6PA114 6PA115 6PA116 6PA117 6PA62 2PA6 6PA7 ...

Отзывы: