WARNING
PERSONAL INJURY
DO NOT USE these products as safety or emergency stop
devices or in any other application where failure of the product
could result in personal injury.
Failure to comply with these instructions could result in
death or serious injury.
Installation Instructions for the
Enclosed Basic Series Limit Switches
Sensing and Control
Issue 5
88173
GENERAL INFORMATION
• Honeywell’s Enclosed Basic Series of Limit Switches are
usable in many applications. The wide variety of actuators
offered and their robust diecast housing make them ideal for
applications that require reliable switching and performance.
There are several styles of enclosed basic switches, includ-
ing side and flange mounting switches as well high capacity
and double pole type.
• Refer to switch labeling for applicable electrical ratings and
certifications
• For technical product support, engineering drawings,
technical data, and additional information for products from
Honeywell’s Enclosed Basic Series of Limit Switches please
visit sensing.honeywell.com, or call the support numbers on
the last page of this document.
MOUNTING
1. Mount switches on flat, rigid surface.
E6 Side Mounting Pattern
25,4 mm
[1.00 in]
2X CLEARANCE HOLE FOR #6
MOUNTING SCREW*
E6 SIDE MOUNTING
V6 Flange Mounting Pattern
41,6 mm
1.63 in
2X Ø 4,3 mm [0.17 in] MOUNTING HOLES
V6 FLANGE MOUNTING
G1 Side Mounting Pattern
31,0 mm
[1.22 in]
75,0 mm
[2.95 in]
2X Ø 5,5 mm [0.216 in] MOUNTING HOLES
G1 SIDE MOUNTING
H1 Flange Mounting Pattern
41,9 mm
1.65 in
2X Ø 0.22 5,5 mm [0.22 in]
MOUNTING HOLES
H1 FLANGE MOUNTING
2. Boot-sealed and side-mounting switches use sealing wash
-
ers under screw heads on the sides between switch and
mounting surface on other side to maintain seal.
3. Unsealed, side mounting switches: Use lockwashers under
screw heads on one side; under nut on other side.
4. Connect conduit to conduit opening. Apply conduit sealing if
required by application.
INSTALLATION TIPS
1.
Do not lubricate any internal part of the switch.
The inter-
nal switch does not require any additional lubrication
2. When installing the switch, ensure
that it is not the low
point in the conduit run
. Doing so will ensure that con-
densation created in the conduit will not flow into the switch
housing.
3.
Do not enlarge the mounting holes on side mounting
switch
. Doing so will compromise the internal switching ele-
ment’s seal integrity.