RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
29
66-1162—2
APPENDIX B: RM7800L/40G,L, EC7840L IGNITION OPTIONS
Column 1 lists the ignition option.
Column 2 lists the figure letter that shows the connections for that option. The figure letters refer to the figures on pages 30–32.
Column 3 refers to the fuel changeover switch and how many connections or poles that would be required.
Table 17. RM7800L/40G,L, EC7840L Ignition Options
Ignition Options
Figure Letter
Fuel Changeover Poles
No Valve Proving
Single Fuel
-
MFEP 10s
A
-
-
MFEP 15s
B
-
-
DSI
C
-
Dual Fuel
MFEP timed for both
-
Gas 10s, Oil 10s
D
2
-
Gas 10s, Oil 15s
E
2
-
Gas 15s, Oil 10s
F
2
-
Gas 15s, Oil 15s
G
2
-
Gas 10s, Oil DSI
H
3
-
Gas 15s, Oil DSI
I
3
-
Gas DSI, Oil 10s
J
3
-
Gas DSI, Oil 15s
K
3
-
DSI both
L
2
Valve Proving on Gas
Single Fuel
-
MFEP 10s
M
-
-
MFEP 15s
Not Possible
-
DSI
N
-
Dual Fuel
MFEP timed for both
-
Gas 10s, Oil 10s
O
4
-
Gas 10s, Oil 15s
P
4
-
Gas 15s, Oil 10s
Not Possible
-
Gas 15s, Oil 15s
Not Possible
-
Gas 10s, Oil DSI
Q
5
-
Gas 15s, Oil DSI
Not Possible
-
Gas DSI, Oil 10s
R
4
-
Gas DSI, Oil 15s
S
4
-
DSI Both
T
4
Gas Direct Spark Ignition during VPS Selection (powering terminal 17) automatically
chooses 4 second Ignition Trial Period, regardless of configuration resistor JR1 status
CAUTION! The above options are ONLY suggestions—BE SURE to check local
approval agencies for timings acceptable for your application.