RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
15
66-1162—2
Fig. 16. Select/Restart screen.
11.
Press down arrow to select.
12.
“
Getting Data
” will be momentarily displayed, followed
by the screen shown in Fig. 12.
Changing the Installed Postpurge
Fig. 17. Setting Postpurge time.
This screen allows for setting up the Postpurge for the
RM7800L/40G,L, EC7840L. This will be the time that the
Combustion Fan (terminal 5) will remain energized after the
demand ends.
NOTE: The device comes standard with 15-second Post-
purge.
13.
Use the +/- buttons to adjust the postpurge time.
Time changes:
0 to 60 seconds in 1-second intervals.
60 to 600 seconds in 10-second intervals.
10 to 60 minutes in 1-minute intervals.
14.
Press Enter (Left/Right arrow keys simultaneously)
when the correct postpurge time is displayed.
Fig. 18. Save Changes screen.
15.
Use the down arrow to save changes. “
Getting Data
” is
displayed momentarily.
The following steps are to confirm your selections.
Fig. 19. Confirmation Acknowledgement screen. (The
Valve Proving Test location is shown.)
16.
Press ENTER.
Fig. 20. Confirmation Correct screen.
17.
Use the down arrow to confirm correct.
NOTE: Using the up arrow during this step will take you back
to the beginning of the setup routine.
“
Getting Data
” will be displayed.
Fig. 21. Confirm screen.
18.
Press Enter.
Fig. 22. Confirm Correct screen.
19.
Use the down arrow to confirm correct.
“
Getting Data
” will be displayed.
The following steps are used to confirm your selection.
=Select
=Restart
M22764B
BACK
ENTER
Edit:
-
+
M22668
BACK
ENTER
Edit:
-
+
SETUP:Postpurge
±PostTime: 00:30
SU
=Save changes
=Restart
M22665B
BACK
ENTER
Edit:
-
+
CONFIRM:ValvProve
±VP When: BEFORE ?
M22670B
SC
BACK
ENTER
Edit:
-
+
=Confirm correct
=Incorrect
M22671B
BACK
ENTER
Edit:
-
+
CONFIRM: ValveProve
VP Time: 00:30 ?
M22672A
SC
BACK
ENTER
Edit:
-
+
=Confirm correct
=Incorrect
M22671B
BACK
ENTER
Edit:
-
+