INNCOM E7 THERMOSTAT USER GUIDE
17
36-00013—02
Contractor Mode
Contractor mode allows conditioning a space during the construction phase to a
defined set temperature and locking out the key pad to prevent tampering. To
configure this mode, do the following:
1.
Enter SERVICE MODE:
(1) Press and hold
o
F|
o
C.
(2) Press and hold MODE.
(3) Press and hold FAN.
(4) Release the three buttons.
2.
Use the UP/DOWN arrow buttons to display
ctr
. then press MODE to
select
ctr
.
3.
Use the UP/DOWN arrow buttons to select the target temperature (range: Off - 80 degrees F).
4.
Press FAN to continue. Once FAN is pressed, the display scrolls the set temperature and the unit
beeps
to con-
firm the value has been set.
5.
Press
o
F|
o
C twice to exit SERVICE MODE. The unit displays the target and measured temperature, and
the alert icon. Any key press to change set temperature, fan speed or mode are locked out.
EXIT CONTRACTOR MODE
1.
Enter SERVICE MODE (Step 1 in the previous section).
2.
Use the UP/ DOWN arrows to display
ctr
- - then press MODE to select
ctr
. Press FAN to turn off CONTRAC-
TOR MODE.
3.
Press
o
F|
o
C twice to exit SERVICE MODE.
Property Specific Configurations
Once initial setup is completed, the e7 can support a range of expanded Integrated Room Automation System
functionality. This additional functionality is deployed using Honeywell's software tools INNtool and engINN.
Training for INNtool and engINN for system design and commissioning is now included in the Level 2 and Level 3
classes.
INNCOM Authorized Systems Integrators should contact their respective E&ES Regional Support Teams to inquire
about enrolling in upcoming training sessions. If you have already received training or you are a Honeywell employee
supporting the INNCOM business, you can download the software here:
https://www.inncom.com/login