Controls & indicators

Numeric keypad.

Allows the entry

of numeric data.

q

Shift key.

The Shift/Function

key gives access to the main
functions of the panel.

q

Display test key.

Pressing the

Display Test key after entering
access code# will initiate a
sequence which illuminates all
the indicators in turn enabling
them to be checked.

# Coded entry is only
required if Cancel Buzzer and
Display Test functions are
configured for operation at
Access level 2.

q

Cancel Buzzer.

Pressing the

Cancel Buzzer button after
entering access code# will stop
the internal buzzer sounding.

q

System Reset.

The system

reset key when pressed after
entering access code will return
the system to its normal
operating state. If there are
uncleared fires or faults then
these conditions will re-occur.

q

Sound Alarms.

Pressing the

Sound Alarms button after
entering access code will sound
all of the system alarms. Should
only be pressed in an

emergency or at other agreed
times, ie for sounder tests etc.
Pressing the sound alarms
button does not action the
auxiliary relay.

q

Silence Alarms.

Pressing the

Silence Alarms button after
entering access code will
silence the system alarms.
Should only be pressed when
the emergency is over.

Indicators.

q

Fire.

When lit indicates that the

system has detected a fire.

q

Fault.

When lit or flashing

indicates that there is a fault
condition on the system which
requires rectification.

q

Zone Fire/Fault/Disablement.

Red indicator illuminates when
there is a zone fire, it can be a
steady or flashing indication.
For a zone fault the yellow
indicator is flashing. A lit zone
yellow indicator along with the
Disabled indicator is used to
show a disabled zone.

q

System Fault

. This indicator

when lit indicates that there is a
fault in the panel’s processor.

q

Power Fault

. When lit or flashing

indicates that there is a power
supply fault present.

q

Earth Fault

. This indicator when

lit or flashing indicates that there
is an Earth Fault on the system.

q

Sounder Fault

. When flashing in

conjunction with a flashing fault
indicator indicates a sounder
fault. When lit in conjunction with
the disabled indicator indicates
that the sounders are disabled.

q

Disabled

. Illuminates along with

the sounder or the zone
indicators to show a disabled
condition.

q

Test.

When lit indicates that the

panel is in Test mode.

q

Power.

When lit indicates that

the panel is powered up.

q

Delay

. When lit it indicates that a

delay will be effective after
detection of a fire before
activation of system alarms.

q

Access/Function

. The

Access/Function lamp will flash
when the shift key is pressed
and will be lit when the coded
functions are accessed.

Controls & indicators

Fire Panels

9

4188-424 issue 4_Part 1_10-09

Cancel
Buzzer

System

Reset

Sound
Alarms

Silence
Alarms

1

2

3

4

5

6

7

8

9

0

v

Shift or Function
key

Shift

Numeric
keypad

Display test
key

Display

Essential controls

Zones

FIRE

Fault

System

Power

Earth

Sounder

Disabled

Test

Delay

Access /
Function

Normally lit
to indicate
Power supply
healthy

The light is lit when
the Shift/Function key is pressed
or there is an entry to controls
with coded access

ZONE Fire, Fault or Disablement indications

Other Fault

indications

1

red

yellow

2

3

4

5

6

7

yellow

yellow

yellow

green

8

Power

yellow

Figure 13 Controls and indications

CONTROLS -

only available when an access code is entered.

Содержание 13270-01LB

Страница 1: ...al is intended for use by installers and commissioning engineers A separate Operating instructions and Log book has been supplied along with this booklet which must be forwarded on to the End User 4188 424 issue 4_Part 1_10 09 Data Installation and Commissioning guide Fire Control and Repeat panels Conventional 1 2 4 and 8 Zone panel range Content Page System design 2 Cables 4 Notes to installers ...

Страница 2: ... All manual call points used must have a 470 ohms series resistor Where a zone circuit is not being used the end of line capacitor unit or bipolar capacitor must be fitted across its terminals in the panel System design Fire Panels 2 4188 424 issue 4_Part 1_10 09 Un used Zone circuits must be terminated with an end of line Capacitor unit or bipolar capacitor End of line Capacitor unit or bipolar c...

Страница 3: ...schools and colleges Auxiliary Contacts These are normally open NO and normally closed NC contacts that change over when the panel goes into a fire condition The contacts are rated at 24V dc 1A for a resistive load and should not be used to switch voltages in excess of 50V The auxiliary circuits should be powered from an independent power supply NOTE There is no indication given at the panel of cl...

Страница 4: ... and Relay shown connected here are typical examples of external circuit Figure 6 Fire fault 24V outputs Length per circuit Type of circuit Recommended cables also see BS5839 Part 1 guidance 2m Mains power supply cord see power supply cord 1Km Zone circuit See BS5839 Part 1 2002 A2 2008 for guidance 1Km Sounder circuits 100m Auxiliary circuit 100m Common fire and fault circuit 100m Class change ci...

Страница 5: ... the installers responsibility to provide adequate fixtures and fittings for the type of construction surface onto which a product is to be installed as an aid to this decision the weight and overall size of each full assembly together with implications on cable entries and routing should be taken into consideration NOTE All these procedures assume that the cable gland steel box BESA box and other...

Страница 6: ...em wiring can be tested whilst not connected to the respective terminals at each system device CAUTION DO NOT undertake high voltage insulation tests WITH THE CABLES CONNECTED to their terminals This may damage the electronic circuitry in the product I Refit the front panel including the electronic assembly into the panel using four M3 screws and connect the transformer cable and earth cable see F...

Страница 7: ...Transformer Earth T1A T1B E Panel Backbox Transformer cables to electronic assembly Earth connection to the electronic assembly ve ve Bottom Plate instructions printed onto plate Ribs NOTE The metal plates are to be located under the ribs on the front panel and fixed in place using M3 screws Figure 10 Refitting electronic assembly 378mm wide 245mm high 60mm deep cross section of the wall to which ...

Страница 8: ...750mA Fuse 1 Zone panel 2 Zone panel 4 Zone panel 8 Zone panel Repeat panel SECTOR 1 SECTOR 2 SECTOR 3 SECTOR 4 SECTOR 5 SECTOR 6 SECTOR 7 SECTOR 8 BATTERIES 24V 1 8 All other fuses ie FS1 FS2 and FS11 are 20mm x 5mm diameter QB Quick Blow AS Anti Surge Fuses T1A T1B E CFR 24 CFT 0 CC1 CC2 R R NC NC NO NO Zn Zn To Zone and Sounder Circuits where n signifies circuit number 1 to 8 Sn Sn Auxiliary co...

Страница 9: ...is flashing A lit zone yellow indicator along with the Disabled indicator is used to show a disabled zone q System Fault This indicator when lit indicates that there is a fault in the panel s processor q Power Fault When lit or flashing indicates that there is a power supply fault present q Earth Fault This indicator when lit or flashing indicates that there is an Earth Fault on the system q Sound...

Страница 10: ...r or manual call point on a zone circuit b Connect the zone cable to the zone circuit terminals c Carry out zone open circuit and short circuit tests and check appropriate indications are given d Repeat the above for other zone circuits Sounder circuit tests a Transfer the end of line resistor unit to the last device on a sounder circuit b Connect the sounder circuit cable to the sounder circuit t...

Страница 11: ... a Fire indication is given for 10 seconds duration followed by a system reset Table 2 Test mode operation Config considerations Repeat panel config q The power up procedure for the repeat panel is the same as the main panel q The presence of a repeat panel needs to be set up at the main panel see Config and Test section Delay mode In the Delay mode there is a delay between detecting a fire and so...

Страница 12: ...eck that the Test indicator is On and the zone fault indicator is lit The zone can be tested without an alarm of fire How to set the panel to operate in Test mode B q Enter the AL2 access code and check that the Access function lamp is lit q Press the shift and 4 buttons followed by the number of the zone to be placed in test mode Check that the Test indicator is On and the zone fault indicator is...

Страница 13: ...n lamp is lit q Press the shift and 9001 buttons in sequence and check that the System LED is flashing q Input the new AL2 access code How to change AL3 password q Enter the AL3 access code and check that the Access function lamp is lit q Press the shift and 9002 buttons in sequence and check that the System LED is flashing q Input the new AL3 access code How to set and unset the Delay mode q Ente...

Страница 14: ...vel 2 q Enter 3 digit AL3 access code default 321 Press Shift Enter data 9000 000 001 To allow Display test at access level 1 q Enter 3 digit AL3 access code default 321 Press Shift Enter data 9000 001 001 To allow Display test at access level 2 default setting q Enter 3 digit AL3 access code default 321 Press Shift Enter data 9000 001 002 To allow Test condition at access level 2 default setting ...

Страница 15: ... silence alarms before reset q Enter 4 digit AL4 access code 7426 Press Shift Enter data 9000 033 followed by 000 for a Reset Silences and 001 for UK Linking How to set Sound Resound alarms configuration default is sound alarms at any time q Enter 4 digit AL4 access code 7426 Press Shift Enter data 9000 034 followed by 000 for a Sound Alarms at any time and 001 for Resound only How to set Zone sho...

Страница 16: ...fault A zone fault occurs when a zone circuit cable is open circuit or short circuit or the end of line capacitor unit has been disconnected or a detector has been removed What is a Sounder fault A sounder fault occurs when a sounder circuit cable is open circuit or short circuit or the end of line resistor unit has been disconnected What is a Mains power fault A mains failure occurs when the main...

Страница 17: ...shing Yes Are the Fault and Zone Fault indicators flashing Yes Are the Fault and Access Function indicators pulsing Yes Are the Fault and System Fault indicators On and is the Power On indicator Onor flashing Yes Are the Zone Fault and Disabled indicators lit Are the Sounder Fault and Disabled indicators lit Refer to Specialist help Yes Yes Refer to the Test mode see Page 11 18 18 Refer to the PSU...

Страница 18: ...ry fault Charger fault at Main Panel Steady Steady Auxiliary supply sounder output supply fault at Main Panel Slow Flash Slow Flash Mains failed at Repeat Panel Slow Flash Fast Flash Battery disconnected Battery fault Charger fault at Repeat Panel If Access Function indicator flashes slowly there is a comms fault between the Main Panel and the Repeat Panel NOTE If there is a PSU fault at the Main ...

Страница 19: ...slowly Normal Deactive Deactive Disable zone On On On Normal Active Deactive Disable Sounder On On On Normal Active Deactive Visual indications Audible indication Signals out Condition Fault Yellow Power Green Access Function Yellow Buzzer Aux Relay contacts Normally de energised Common fault Normally active Common fire Normally deactive Repeat Panel Link Fault Steady On Pulse slowly Pulse slowly ...

Страница 20: ...uct family standard Immunity requirements for components of fire intruder and social alarm systems IP rating BS5490 IP31 indoor Knock In cable entry points 13 top 13 back Terminal size 2 5mm2 maximum Battery standby with 1mA load per zone and 1A total sounder alarm load 72hr standby plus 0 5hr with alarm load Auxiliary contacts operates with fire Pair of normally closed NC and a pair of normally o...

Страница 21: ... power 60W 8 zone panel Internal supply 24V supply Feeds current limited zone circuit 24V fused output 24V dc 2V 2V or 24V 2V 4V battery operation current limited 5 ripple voltage 24V Sounder supply Feeds fused sounder circuit 24V dc 2V 2V 24V 2V 4V battery operation Current limited 5 ripple voltage Battery Charger Float voltage 27 3V 1 1 20degC Compensation 36mV K nominal Current limited 400mA 20...

Страница 22: ...ck In cable entry points Top back entries Terminal size 2 5mm2 maximum Battery supply sealed lead acid 2 off12V 2 1Ah 3 4Ah See applicable batteries as listed for Control panel Standby duration 72hr standby User access By means of code entry via numeric key pad AL1 Authorised user No code is required AL2 Site security 3 digit code 123 AL3 Site engineering 3 digit code 321 AL4 Engineers 4 digit cod...

Страница 23: ... call points MCP Part number Description 14112 08EN MCP Surface Red 470R 14112 48EN MCP Surface Red 470R c w cover 14112 19EN MCP Surface water resistant kit 14115 08 Keyswitch red surface 470R 14112 09NM Pack of 10 glasses Part number Description 71150 52NMA EN MCP Surface c w backbox EN54 version 470R 71150 55NMA EN MCP Surface with Cover and backbox EN54 version 470R 14115 08 Key Operated surfa...

Страница 24: ...ntent hereof without obligation to notify any person of such revisions of changes Hamilton Industrial Park Waterside Road Leicester LE5 1TN UK Website www gent co uk Telephone 44 0 116 246 2000 Tech Support www gentexpert co uk Fax UK 44 0 116 246 2300 4188 424 issue 4_Part 1_10 09 by Honeywell Do not dispose of with your normal household waste Do not burn WEEE Directive At the end of their useful...

Отзывы: