Operating Instructions for AL2 functions
Fire Panels
13
4188-424 issue 4_Part 1_10-09
How to disable sounders
q
Enter the AL2 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
1
buttons followed by
0
.
- Check that the Sounder and Disabled indicators are lit.
- The Sounder circuits are disabled.
How to enable sounders
q
Enter the AL2 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
2
buttons followed by
0
.
- The previously disabled sounders are now re-enabled.
How to change AL2 password
q
Enter the AL3 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
9001
buttons in sequence and check that the System LED is flashing
q
Input the new AL2 access code.
How to change AL3 password
q
Enter the AL3 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
9002
buttons in sequence and check that the System LED is flashing
q
Input the new AL3 access code.
How to set and unset the Delay mode
q
Enter the AL2 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
6
buttons.
- The
Delay mode
toggles between Delay and No Delay each time this operation is performed.
When Delay mode is selected the Delay lamp is lit.
How to exit from AL2, AL3 or AL4 to AL1
q
Press the
shift
button followed by
0
.
- Check that the Access/function lamp is extinguished.
- The panel is now in access level AL1.