Specification for the Control panel
Fire Panels
21
4188-424 issue 4_Part 1_10-09
Specification for control panel’s Power supply
The control panel consists of single board containing both the control and indicating equipment and the power
supply. A 50VA mains transformer provides a low voltage (30Vac) supply into the power supply circuits. The on
board power supply circuits produce a regulated 24V dc supply, a 24V sounder supply and a battery charger
output.
Note the control and monitoring of the power supply unit is under direct control of the microprocessor of the
control and indicating equipment.
Mains supply
Mains
230V AC +10% -15% 50Hz
Fused at 3.15A
Typical standby power 6W
Maximum alarm power <60W (8 zone panel)
Internal supply
24V supply (Feeds current limited
zone circuit & 24V fused output)
24V dc +2V -2V (or 24V +2V -4V battery operation)
current limited
<5% ripple voltage
24V Sounder supply (Feeds fused
sounder circuit)
24V dc +2V -2V (24V +2V -4V battery operation)
Current limited
<5% ripple voltage
Battery Charger
Float voltage 27.3V +1% -1% @ 20degC
Compensation -36mV/K (nominal)
Current limited @ 400mA +20% -20%
Fused @ 3.15A
Reverse protection
Battery supply
Approved Batteries
12V, 2.1Ah YUASA
12V 2.8Ah YUASA
12V 3.4Ah POWERSONIC
Type and capacity
Sealed lead acid (value regulated)
2x12V, 2.1Ah min to 3.4Ah* max (1,2&4 zone panels)
2x12V, 2.8Ah min to 3.4Ah*max (8 zone panel)
* max capacity limited by internal panel size
Maximum current
1.6A (no mains present)
Final voltage
21.6V
Installation requirements
As per control panel
EN54 Part 4 data
I min -> 120uA
I maxa -> 21.6mA
I maxb -> 1.5A
Ri max-> 2
W
UVLO -> 18.5V
±
1.5V