Installation Guide

69-2199—09 8

ADVANCED CONFIGURATION

Table 6. Advanced Configuration.

Menu Name

Menu Title (LCD 

top line)

Menu Options (LCD bottom 

line; defaults in bold)

Menu option description

Notes:

Heat Fan

HEAT FAN 

CONTROL

[HVAC] PANEL

Fan control by HVAC

In heat mode, fan controlled by HVAC or 

turned on by panel in call for heat.

 HVAC [PANEL]

Fan control by Panel

Stage 2 Timer

STAGE 2 TIMER

     [5 MIN]   > – 

<   [60 MIN]  

     [5 MIN]   >

5 minutes–60 minutes

Number of minutes to delay before engaging 

second stage.

Purge Timer

PURGE TIME

[2] 3.5  5  MIN

2.0 minutes

Number of minutes panel will purge following 

call for heat or cool.

 2 [3.5]  5  MIN

3.5 minutes

 2  3.5  [5] MIN

5.0 minutes

Purge Fan

FAN IN PURGE

[HVAC] PANEL

Fan control by HVAC

Fan controlled by HVAC or panel during purge.

 HVAC [PANEL]

Fan control by Panel

Purge Dampers

PURGE DAMPERS

[UNCHANGD] OPEN

Dampers Unchanged

Damper position unchanged or all dampers 

open during purge.

 UNCHANGD [OPEN]

Dampers All Open

Auto Changeover Delay  CHANGEOVER 

DELAY

[15] 20  30  MIN

15 minutes auto changeover timer

Number of minutes to delay auto changeover 

when one zone is calling for heat and another 

is calling for cooling.

 15 [20] 30  MIN

20 minutes auto changeover timer

 15  20 [30] MIN

30 minutes auto changeover timer

DATS Enabled

DISCHARGE 

SENSOR

[NO] YES

Disabled

Enables or disables DATS. If Disabled, the 

Multistage DATS Inhibit setting is Disabled.

 NO [YES]

Enabled

DATS High Limit

DAT HIGH LIMIT

    [110 F]    > – <   [180 F]     

<   [160 F]    >

110 deg F–180 deg F

High temperature limit.

DATS Low Limit

DAT LOW LIMIT

     [30 F]    > – <    [60 F]     

<    [40 F]    >

30 deg F–60 deg F

Low temperature limit.

OT Temp Enabled*

OT SENSOR

[NO] YES

Disabled

Enables or disables wireless outdoor tempera-

ture sensor. If Disabled, the Multistage OT 

Temp Lockout setting is Disabled.

 NO [YES]

Enabled

OT Trip Point for 

Multistage Lockout

OT LOCKOUT 

TEMP

      [0 F]    > – <    [50 F]    

<    [50 F]    >

0 deg F–50 deg F

Above this temperature 2nd stage heat is 

locked out.

Multistage DATS 

Inhibit

DAT MSTG INHIBIT

NO [YES]

Enabled

Allow panel to downstage multistage equip-

ment when near DATS high or low limit.

 [NO] YES

Disabled

LCD Contrast Adjust

LCD CONTRAST

     [1]     > – <    [10]    

<   [5]     >

Contrast value 1–10

Sets LCD display contrast for ease of viewing. 

Lowest contrast is 1, highest contrast is 10.

Save Changes

SAVE CHANGES?

[NO] YES

Disabled

Saves or rejects the configuration settings.

 NO [YES]

Enabled

Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 

7 for instructions on using these buttons.

* Used only if Wireless Adapter THM4000R and Wireless Outdoor Sensor C7089R are used.

Press the Mode button until the Wireless LED lights 

up. The TrueZONE must be configured for wireless 

devices to select Wireless mode.

4

CONNECT WIRELESS DEVICES

HOME

MODE

BACK

NEXT

CONFIG

CHECK OUT

ADJUST SETTING

M28194

WIRELESS

Press Next to add devices.
While the display alternates the Press Connect and 

Exit screens, push the Connect button(s) on the 

wireless device(s).
-OR-
Follow the instructions that came with the wireless 

device(s).
Press Next to exit.

Fig. 15

Содержание TrueZONE HZ322

Страница 1: ...HZ322 TrueZONE Zone Panel Professional Installation Guide HZ332 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT EMERGENCY HEAT ZONE 1 ZONE 2 ZONE 3 69 2199 09...

Страница 2: ...ondensing Temperature Ratings Shipping 20 F to 150 F 29 C to 66 C Operating 40 F to 165 F 40 C to 74 C Dimensions See Fig 1 Emissions Complies with FCC Class B part 15 requirements Read before install...

Страница 3: ...imum Dampers Ambient Temp Maximum Damper VA per Zone 100 F 38 C 28 8 160 F 71 C 16 8 Use an SDCR Slave Damper Control Relay for additional dampers Maximum dampers per panel is limited by trans former...

Страница 4: ...e and use the base as a template to drill mounting holes Attach the base to the wall stud roof truss or duct with appropriate screws not included Use two screws for attaching to a stud or roof truss o...

Страница 5: ...ne panel To connect wire to the panel strip approximately 1 4 in of insulation and push wire into terminal To release wire press the button on to p of the terminal In retrofit applications trim end of...

Страница 6: ...charge Air Temperature Installation Instructions Form Number 69 1521 5 Connect equipment as shown here and on page 5 and 6 6 C7735A1000 M28024 SENSOR DATS DATS 8 Connect a dedicated transform er as sh...

Страница 7: ...22 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT ZONE 1 ZONE 2 ZONE 3 EMERGENCY HEAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 1 DAMPER THERMOSTAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 2 DAMPER THERMO...

Страница 8: ...520 72 7 21 25 7 50267 76 7 6 3 5 7 2 1 7 50 1 6 77 2 25 22 1 29 5 25 77 25 7 1 29 5 9 48 30 17 86 6 7 6 0 6285 2 7 25 8 5 1 0 5 1 7 803 5 1 7 50 1 6 25 7 7 0 5 5 66 3725 21 1 9 5 5 7 0 5 25 7 0 5 0...

Страница 9: ...CONVENTIONAL NON HEAT PUMP THERMOSTATS OPTIONS TSTAT TIMER ZONES OFF ADVANCED CONFIG NO YES SAVE CHANGES NO YES COMPRESSOR STAGES 1 2 1 2 3 1 AUX HT ENABLED YES NO SET TO YES IF WIRELESS RADIO FREQUEN...

Страница 10: ...mit DAT HIGH LIMIT 110 F 180 F 160 F 110 deg F 180 deg F High temperature limit DATS Low Limit DAT LOW LIMIT 30 F 60 F 40 F 30 deg F 60 deg F Low temperature limit OT Temp Enabled OT SENSOR NO YES Dis...

Страница 11: ...il the Check out LED lights up Use the Adjust Setting and Next buttons to work through the checkout menu as listed below See the Configuration section on page 7 for instructions on using these buttons...

Страница 12: ...be sent to you This warranty does not cover removal or reinstallation costs This warranty shall not apply if it is shown by Resideo that the defect was caused by damage which occurred while the produ...

Отзывы: