Installation Guide

69-2199—09 4

The DS/BK terminal is used with a variable-speed fan. If 

the HVAC equipment has a DS, BK, ODD, or DHUM ter-

minal, wire that terminal to the HZ322 DS/BK terminal. 

When 2 or 3 zones are calling for cooling this terminal 

will be energized which will run the blower fan at the 

normal speed. When only 1 zone is calling for cooling 

the fan runs at a reduced speed which will require less 

air to be by-passed. Refer to HVAC equipment manufac-

turer instructions.

For oil heat with a separate transformer for cooling, 

remove this jumper.  For other systems leave jumper 

in place and wire to HVAC R terminal with 18 gauge 

solid wire.

Connect DATS as shown.
For the placement of DATS in supply duct and 

troubleshooting assistance with the DATS, see the Discharge 

Air Temperature Installation Instructions Form Number 

69-1521.

5

Connect equipment as shown here and on page 5 and 6.

6

C7735A1000

M28024

SENSOR

DATS

DATS

8

Connect a dedicated transform-

er as shown.

DEDICATED

TRANSFORMER

R

C

M24806

R

C

POWER

L1

(HOT)

L2

RH

RC

W1/E

W2

Y1

Y2

G

O

B

DS/BK

M28025

HVAC

FAN RELAY

24 VOLT TRANS.

G

Y

Y2

C

R

W

COMPRESSOR

RELAY

W2

EQUIPMENT

WIRING

Fig. 7

Fig. 8

Fig. 10

7

When a wireless thermostat, Portable Comfort Control, 

wireless outdoor air temperature sensor, or other 

RedLINK™ wireless device is used, wire the THM4000 

Wireless Adapter Module to the ABCD terminals on the 

zone panel.

CAUTION: 

Only the THM4000R can be wired to the A-B-C-D terminals on the HZ322. Do not wire 

the A-B-C-D terminals of the THM5320R or THM5421R Equipment Interface Module to the A-B-C-D 

terminals on the HZ322 zone control panel. Doing so will damage the components.

M28193

A

B

C

D

WIRELESS

ADAPTER

WIRELES

S

CONNECT

POWER

THM4000R

CONNECTED

WIRELESS SETUP

Fig. 9

Содержание TrueZONE HZ322

Страница 1: ...HZ322 TrueZONE Zone Panel Professional Installation Guide HZ332 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT EMERGENCY HEAT ZONE 1 ZONE 2 ZONE 3 69 2199 09...

Страница 2: ...ondensing Temperature Ratings Shipping 20 F to 150 F 29 C to 66 C Operating 40 F to 165 F 40 C to 74 C Dimensions See Fig 1 Emissions Complies with FCC Class B part 15 requirements Read before install...

Страница 3: ...imum Dampers Ambient Temp Maximum Damper VA per Zone 100 F 38 C 28 8 160 F 71 C 16 8 Use an SDCR Slave Damper Control Relay for additional dampers Maximum dampers per panel is limited by trans former...

Страница 4: ...e and use the base as a template to drill mounting holes Attach the base to the wall stud roof truss or duct with appropriate screws not included Use two screws for attaching to a stud or roof truss o...

Страница 5: ...ne panel To connect wire to the panel strip approximately 1 4 in of insulation and push wire into terminal To release wire press the button on to p of the terminal In retrofit applications trim end of...

Страница 6: ...charge Air Temperature Installation Instructions Form Number 69 1521 5 Connect equipment as shown here and on page 5 and 6 6 C7735A1000 M28024 SENSOR DATS DATS 8 Connect a dedicated transform er as sh...

Страница 7: ...22 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT ZONE 1 ZONE 2 ZONE 3 EMERGENCY HEAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 1 DAMPER THERMOSTAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 2 DAMPER THERMO...

Страница 8: ...520 72 7 21 25 7 50267 76 7 6 3 5 7 2 1 7 50 1 6 77 2 25 22 1 29 5 25 77 25 7 1 29 5 9 48 30 17 86 6 7 6 0 6285 2 7 25 8 5 1 0 5 1 7 803 5 1 7 50 1 6 25 7 7 0 5 5 66 3725 21 1 9 5 5 7 0 5 25 7 0 5 0...

Страница 9: ...CONVENTIONAL NON HEAT PUMP THERMOSTATS OPTIONS TSTAT TIMER ZONES OFF ADVANCED CONFIG NO YES SAVE CHANGES NO YES COMPRESSOR STAGES 1 2 1 2 3 1 AUX HT ENABLED YES NO SET TO YES IF WIRELESS RADIO FREQUEN...

Страница 10: ...mit DAT HIGH LIMIT 110 F 180 F 160 F 110 deg F 180 deg F High temperature limit DATS Low Limit DAT LOW LIMIT 30 F 60 F 40 F 30 deg F 60 deg F Low temperature limit OT Temp Enabled OT SENSOR NO YES Dis...

Страница 11: ...il the Check out LED lights up Use the Adjust Setting and Next buttons to work through the checkout menu as listed below See the Configuration section on page 7 for instructions on using these buttons...

Страница 12: ...be sent to you This warranty does not cover removal or reinstallation costs This warranty shall not apply if it is shown by Resideo that the defect was caused by damage which occurred while the produ...

Отзывы: