34
OPERATION
STANDBY POWER
System Ground
Connections to a Building’s Electrical System
In some areas, generators are required by law to be registered with
local utility companies. Check local regulations for proper registration
and use procedures.
Improper connections to a building’s
electrical system can allow current
from the generator to backfeed into
the utility lines.
Such backfeed may electrocute
utility company workers or others
who contact the lines during a
power outage, and the generator
may explode, burn, or cause fires
when utility power is restored.
Consult the utility company or a
qualified electrician prior to making
any power connections.
Your generator can supply power to a building’s electrical system. If
the generator will be used as an alternative to utility company power,
an isolation switch must be installed to disconnect the utility lines
from the building when the generator is connected. Installation must
be performed by a qualified electrician and must comply with all
applicable laws and electrical codes.
Honda generators have a system ground that connects the generator
frame components to the ground terminals in the AC output
receptacles. The system ground is not connected to the AC neutral
wire. If the generator is tested with a receptacle tester, it will not show
the same ground circuit condition as for a home receptacle.
11/12/06 12:55:45 42Z26700_036
Содержание EM10000
Страница 2: ...11 12 06 12 51 30 42Z26700_002 ...
Страница 12: ...10 GENERATOR SAFETY ET12000 11 12 06 12 52 47 42Z26700_012 ...
Страница 75: ...73 TECHNICAL INFORMATION WIRING DIAGRAM EM10000 R K types 11 12 06 13 01 01 42Z26700_075 ...
Страница 76: ...74 TECHNICAL INFORMATION WIRING DIAGRAM EM10000 U type 11 12 06 13 01 10 42Z26700_076 ...
Страница 77: ...75 TECHNICAL INFORMATION WIRING DIAGRAM EM10000 M type 11 12 06 13 01 20 42Z26700_077 ...
Страница 78: ...76 TECHNICAL INFORMATION WIRING DIAGRAM ET12000 11 12 06 13 01 30 42Z26700_078 ...
Страница 85: ...83 MEMO 11 12 06 13 02 08 42Z26700_085 ...
Страница 86: ...84 MEMO 11 12 06 13 02 10 42Z26700_086 ...